MV Cable Testing
MV Cable Testing
safety in service. The testing procedures are standardized and involve various tests at different
stages of the cable's lifecycle, such as during installation, commissioning, and periodic
maintenance. The following details the common MV cable testing procedures.
1. Visual Inspection
Before any electrical testing, a thorough visual inspection is conducted to identify any visible
damage or defects, such as:
The insulation resistance test is one of the most fundamental tests for evaluating the condition
of the insulation system of MV cables.
Purpose:
To assess the insulation's ability to resist leakage current and identify defects such as moisture,
contamination, or insulation degradation.
Test Procedure:
The Very Low Frequency (VLF) test is commonly used for testing MV cables because it
provides reliable data on the integrity of the cable's insulation. VLF tests are safer and more
practical than traditional power frequency withstand tests.
Purpose:
To evaluate the insulation strength by applying an AC voltage at a low frequency (usually 0.01
Hz to 0.1 Hz), simulating real operating conditions without exposing the cable to excessive
stress.
Test Procedure:
Acceptance Criteria:
The Hi-Pot test is an older method of testing MV cables and involves applying a high voltage to
ensure that the insulation can withstand extreme electrical stress.
Purpose:
To assess the insulation’s capacity to withstand over voltages that may occur during operation
(such as from lightning strikes or switching surges).
Test Procedure:
A DC or AC high voltage is applied between the cable conductor and the ground.
The test voltage is higher than the operating voltage, typically 1.5 to 2.5 times the
cable's rated voltage.
The test is conducted for 15 minutes for DC and 5 minutes for AC.
Acceptance Criteria:
The Partial Discharge test is a non-destructive test that detects the presence of partial
discharges within the insulation, which can lead to long-term insulation failure.
Purpose:
To identify localized weak points or defects in the insulation that could eventually cause a
complete breakdown.
Test Procedure:
The test voltage is applied at 1.2 to 2.0 times the operating voltage.
The PD detector captures electrical pulses caused by partial discharges within the
insulation.
Acceptance Criteria:
The test aims to detect and localize any partial discharges within the cable's insulation.
No PD activity should be detected for the cable to pass the test.
This test checks the integrity of the metallic sheath or screening of MV cables.
Purpose:
To ensure that the cable's sheath provides a continuous path for fault currents and has no breaks
or discontinuities.
Test Procedure:
A low resistance ohmmeter is used to measure the continuity of the cable sheath.
The sheath is tested by applying low voltage DC to ensure that it provides a complete
circuit.
Acceptance Criteria:
The measured resistance should be low (in the milliohm range), indicating continuous
and intact metallic sheath or screen.
The Tan δ (Delta) test measures the dielectric losses in the cable insulation. This test helps
assess the quality and aging condition of the insulation.
Purpose:
To determine the level of dielectric loss in the insulation and whether it is suitable for continued
use.
Test Procedure:
Acceptance Criteria:
Lower tan δ values indicate healthy insulation, while higher values suggest insulation
aging or defects.
8. Commissioning Test
After all testing is completed and verified, a final commissioning test is conducted to ensure the
proper installation and operational readiness of the cable.
Test Procedure:
Conclusion
MV cable testing is critical to ensure the cables' integrity, safety, and performance throughout
their lifecycle. The testing procedures range from basic insulation resistance tests to advanced
partial discharge and VLF testing, ensuring the cable's insulation system is robust and reliable.
Adhering to IEC standards and following manufacturer recommendations for each type of test
ensures that MV cables perform optimally under various operational conditions.