PJC
PJC
PJC
Instantaneous Overcurrent
Self-reset or manual-reset relays Mechanical target available Up to 3 independent units per case Molded or drawout case available
Applications
I I
GE Multilin
Application
General Service: PJC relay is a high-speed, non-directional current relay that is designed for general service. Feeder Circuit Overcurrent Protection: is a common application for the PJC relay where time delay and directional selectivity are not required and where very short tripping times on high-fault currents are desired. On applications requiring time delay or directional selectivity, IFC or IBC should be used.
Continuous-current Rating: The relay coils are continuously rated as specified on the nameplate for frequencies of 25 to 60 Hz and DC. Ratings for continuous operation on AC are for the non picked-up position only. However, the limitation is mechanical, not thermal, and the relay life expectancy under continuously picked-up conditions is a matter of months. Self-or Hand-reset: Relays listed in this section have self-resetting contacts and hand-reset targets. Special models that are not listed are available having hand-reset contacts. Calibration: The standard relays are calibrated at 60 Hz. For 25 or 50 Hz and DC applications, this calibration is correct within approximately 10 percent. Mounting: The molded case relays are surface mounted and have studs for back connection. The draw out case relays can be surface or flush mounted.
Contact Ratings
The current-closing rating of the contacts is 30 A. The current carrying rating is 5 A continuously or 30 A for 2 sec.
Overcurrent Ratings
Calibration Points
0.032 0.064 0.08 0.12 0.16 0.32 1.6 0.8 1.6 8 3.2 16 6.4 16 32 64 0.05 0.1 0.125 0.188 0.25 0.5 4 1.25 2.5 20 5 40 10 25 50 100 0.08 0.16 0.2 0.3 0.4 0.8 10 2 4 50 8 100 16 40 80 160
Description
The PJC is a plunger relay that operates on the principle of electromagnetic attraction. The contacts are opened or closed by an armature which is attracted vertically into a small solenoid. Generally, the PJC is a single element relay, but these units can be mounted in the draw out case to provide a 2 or 3-unit relay. This grouping of units in a draw out case saves valuable panel space and provides for easy testing and checking. The basic PJC11, PJC12, PJC14 and PJC15 relays have mechanical targets. The PJC32 line of relays has a somewhat smaller base and thus allows 3 units to be mounted horizontally in the S1 or S-2 case with the conventional 0.2/2 A target sealin.
AC Circuits Noninductive V A
115 230 460 ---5 2 1 ----
Inductive A
2 1 0.5 ----
DC Circuits Noninductive V A
24 48 125 250 5 2 1 0.3
Inductive A
1.0 0.5 0.3 0.15
Relay Characteristics
High-speed Operation: The contact closing time is approximately 1 cycle (60 Hz basis) at twice the pickup setting. High Dropout: Contacts reset at approximately 90 to 95 percent of pickup on AC and 70 to 85 percent of pickup on DC when the relay has at least one circuit-closing contact.
Relay Models
PJC11A, 11X, 11Z, 11AV, 11AW, 12A, 12D PJC14C, 14D, 14F PJC32D, 32E PJC21A, 32C, 32F, 32G, 32H, 32J, 32L PJC15F
---------------Unless specified, standard contact arrangement will be supplied. To order other than standard contact arrangement, place the contact code behind the model number. Example: 12PJC11AV3A-Code 11. N.O. = normally open N.C. = normally closed
www.GEindustrial.com/Multilin
Connection Diagrams
Fig. 1. Internal connections diagram for the PJC32C relay (front view) Fig. 2. Internal connections diagram for the PJC32D relay (front view)
13 12 14
15 16 *
17 18 *
19 20
13 12 * 14
15 16 *
17 18 *
19 20
SI SI
SI SI
SI SI
SI SI MIDDLE SI
MIDDLE UNIT
7 9 10 6 8 = SHORT FINGER *
Fig. 3. Internal connections diagram for the PJC32E relay (front view)
Fig. 4. Internal connections diagram for the PJC32F relay (front view)
13
11 12 13 14 15 16 19 20
15 14 16
17 18
19 20
12
*
* * * *MIDDLE TARGET * * RIGHT TARGET
S1 LEFT S1
RIGHT UNIT
1 2
3 4
5 6
9 8 10 = SHORT FINGER *
1 2
3 4
www.GEindustrial.com/Multilin
Connection Diagrams
Fig. 5. Internal connections diagram for the PJC32G relay (front view) Fig. 6. Internal connections diagram for the PJC32H relay (front view)
S1
*
1 3 5 7 9
1 2
3 4
5 6
10
(226A7242)
Fig. 7. Internal connections diagram for the PJC32J relay (front view)
Fig. 8. Internal connections diagram for the PJC32L relay (front view)
13 12 14
15 16
17 18
19 20
* L LEFT TARGET
* R
* L
* R
MIDDLE UNIT
MIDDLE TARGET R L
LEFT UNIT
1 2
3 4
1 2
3 4
5 6
7 8
9 10
www.GEindustrial.com/Multilin
Selection Guide
Molded Case Relays DC, OR 25, 50, 60 HZ AC Rating (A) Continuous One Sec
0.06 0.12 0.2 0.225 0.3 0.6 1.5 3 6 12 25 40 40 1.5 3 6 12 25 40 40 2.8 5.7 9.2 11.4 18.2 36.8 75 150 275 280 500 500 500 75 150 275 280 500 500 500
Calibraton Range
0.02-0.08 0.04-0.16 0.05-0.7 0.075-0.3 0.1-0.4 0.2-0.8 0.5-2 1-4 2-8 4-16 10-40 20-80 40-160 0.5-2 1-4 2-8 4-16 10-40 20-80 40-160
Contacts
2.5 (1.1)
4 (1.8)
4 Contacts (If contact arrangement is not specifed 2 N.O. & 2 N.C. will be supplied)
Drawout Case Relays Ratings (A) Continuous One Second Calibration Range ONE UNIT
0.12 0.3 0.6 1.5 3 6 12 25 25 25 1.5 3 6 12 25 25 25 5.7 18.2 36.8 75 150 275 275 275 275 275 75 150 275 275 275 275 275 0.04-0.16 0.1-0.4 0.2-0.8 0.5-2 1-4 2-8 4-16 10-40 20-80 10-160 0.5-2 1-4 2-8 4-16 10-40 20-80 40-160 PJC11AV23A AV10A AV8A AV1A AV2A AV3A AV4A AV5A AV6A AV7A PJC14C1A C2A C3A C4A C5A C6A C7A ---------2 Contacts PJC12D1A (If contact D2A arrangement is D3A not specified D4A 2 N.O. will be supplied) D5A D6A D7A ---4 Contacts ---(If contact ---arrangement is ---not specifed 2 N.O. & 2 N.C. ---will be ---supplied) ----
Contacts
Case Size
S1
8 (3.6)
12 (5.4)
N.O. contact may not remain closed when relay is in the latched-up position.
www.GEindustrial.com/Multilin
Selection Guide
Drawout Case Relays (cont...) TWO UNITS (BOTH UNITS RATED ALIKE) Ratings (A) Continuous One Second Calibration Range
1.5 3 6 12 25 25 25 1 5 10 1.5 3 6 12 25 25 25 1.5 3 6 12 25 25 25 1.5 3 6 12 25 25 25 75 150 275 275 275 275 275 73.5 375 500 75 150 275 275 275 275 275 75 150 275 275 275 275 275 75 150 275 275 275 275 275 0.5-2 1-4 2-8 4-16 10-40 20-80 40-160 0.4-10 2-50 4-100 0.5-2 1-4 2-8 4-16 10-40 20-80 40-160 0.5-2 1-4 2-8 4-16 10-40 20-80 40-160 0.5-2 1-4 2-8 4-16 10-40 20-80 40-160
15
Contacts
2 Contacts (If contact arrangement is not specified 2 N.O. will be supplied)
Case Size
S2
10 (4.5)
15 (6.8)
M2 13 (5.9) 19 (8.6)
4 N.O.
M2
14 (6.4)
20 (9.1)
2 N.O.
S1
8 (3.6)
12 (5.4)
THREE UNITS WITH OR WITHOUT 0.2/2.0 A TARGET AND SEAL-IN Contacts Model Number Number of Targets Seal-in (Each Unit)
PJC32C*A 2 N.O. 3 Targets Yes See Figure 3 PJC32D*A 1 N.O. & 1 N.C. 3 Targets Yes See Figure 4 PJC32E*A 1 N.O. & 1 N.C. 3 Targets No See Figure 5 PJC32F*A 2 N.O. 3 Targets Yes See Figure 6 PJC32G*A 2 N.O. See Figure 7 PJC32H*A 2 N.O. 3 Targets Yes See Figure 8 PJC32J*A 2 N.O. 3 Targets No See Figure 9 PJC32L*A 2 N.O. 2 Targets No See Figure 10 N.O. contact may not remain closed when relay is in the latched-up position. * Complete the model number by selecting the proper number from the table below.
12 (5.4)
18 (8.2)
www.GEindustrial.com/Multilin
0.5-2
23
1-4
24 34
Model Number* Calibration Range for Left and Right Units (A) 2-8 4-16 10-40
25 35 45 26 36 46 56 27 37 47 57 67
20-80
28 38 48 58 68 78
40-160
29 39 49 59 69 79 89
15