Manual of LPC-3500 LV Series Relays
Manual of LPC-3500 LV Series Relays
00)
LPC-3500 series devices are equipped with LPC 359X series display operation module:
1
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)
LPC-3597
RUN
↑
COM
↓
REM
ALARM
CANCEL
LPC-3598
RUN ↑
COM
REM
↓
CLOSE
CANCEL
OK
LPC- 3599
RUN ↑
COM
↓
REM
CANCEL
ALARM
↓
↓
RESET OK
FAULT
2
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)
Indicator lamp
Lamp Definition Color
Run The indicator lamp is for motor running. The lamp is dark when Green
motor is halted; the lamp blinks when motor starts, the lamp is
green when motor is under normal working status.
Com The indicator lamp is for filed bus communication. When one of Green
RS485/CAN/PROFIBUS networks work and report successfully,
the lamp is green; when abnormal, the lamp is dark.
Remote The indicator lamp is for control limits of authority. When device is Green
under local status, the lamp is dark; when device is under remote
status, the lamp is green.
Alarm The indicator lamp is for alarm. When device does protection Red
actions (alarm or trip), the lamp is red, will be dark after reset.
Fault The indicator lamp is for self checking. When device is abnormal Red
after self checking, the lamp is red, will be dark after reset.
Note 1: when device is under running status, indicator lamps shall indicate as mentioned in above
table; when device is under debugging & commissioning or when power is just switched on,
all the indicator lamps are lighted.
Press button/interface
Press Operation explanation
button/
interface
S(A)/<- S(A)/ <- is the left moving button, can control the forward direction starting of
motor under control display mode; can move the cursor one step to left under
editing mode;
S(B)/-> S(B)/ -> is the right moving button, can control the reverse direction starting of
motor under control display mode; can move the cursor one step to right under
editing mode;
STOP The button can stop the motor under motor control display mode.
Reset Using for resetting
↑ The button can up-turn the Menu or add 1 to the quality;
↓ The button can down-turn the Menu or minus 1 to the quality;
DBG For upgrading the software or communication between device and Stand-alone
debugging software; when using,typical wire will be used to connected with
PC and the device via DBG interface.
3
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)
Indicator lamp
Lamp Definition Color
Run The indicator lamp shows the status of the device. The lamp is Green
green when device is under running status; the lamp is dark
when device is under debugging status.
Com The indicator lamp is for filed bus communication. When one of Green
RS485/CAN/PROFIBUS networks work and report successfully,
the lamp is green; when abnormal, the lamp is dark.
Remote The indicator lamp is for control limits of authority. When device Green
is under local status, the lamp is dark; when device is under
remote status, the lamp is green.
Close The indicator lamp is for switch status indication. When the Red
switch is on, he lamp is red; when the switch is off, the lamp is
dark.
Fault The indicator lamp is for fault or self checking. When device is Red
abnormal after self checking or did the protection action/alarm,
the lamp is red, will be dark after reset.
Press button/interface
Press Operation explanation
button/
interface
CLO/<- CLO/ <- is the left moving button, can close the CB under control display mode;
can move the cursor one step to left under editing mode;
-> can move the cursor one step to right under editing mode;
OPEN The button can open the CB control display mode.
Reset Under control display mode, the button is for resetting the operation
↑ The button can up-turn the Menu or add 1 to the quality;
↓ The button can down-turn the Menu or minus 1 to the quality;
DBG For upgrading the software or communication between device and Stand-alone
debugging software; when using,typical wire will be used to connected with
PC and the device via DBG interface.
4
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)
5
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)
The LED main display screen is as follow when device is under normal running status:
In the main screen, user can press “CANCEL” button and go into the main Menu, also can
press the “S/(A)” button or other control buttons to operate the device as per requirements.
In the main screen, when device is under local status, user can do the control operation
(start/stop the motor) or reset the device.
① Control operation, take Startup A as example, as below:
After pressing the S/(A) button, the LED screen will show as below:
If quitting the “start A” control operation is required at this stage, please press “Cancel”
button, the LED display returns back to main screen, the control operation is cancelled this
time.
If confirming the “start A” control operation, please press “OK” button, the LED display
returns back to main screen, the control operation is done this time.
② Reset operation
6
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)
as below:
Via using the up/down button to choose the required function, then press “OK” to enter into
7
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)
Entering into this menu, could view all the measured values and status info as below:
8
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)
.Prot. Data 1
6
.Meas. Data
.Energy Data 3
6
.Phase Angle
.Signal Data 5
6
.Loop Display
current, zero sequence current, average current, Current unbalance rate, protection
power, over heat value(below is the screen snap of the LED display):
Measurement value display: 3 phase current, 3 phase voltage, active power, reactive
power, power factor, average current, current unbalance rate, frequency (below is the
9
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)
Signal quantity display: showing the status of DI & DO. If DI & DO has signal, the
below check will be filled; if DI & DO does not have signal, the below check will be blank.
10
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)
.Present Abno 1
8
.Act. Report
.DI Report 3
8
.Abnor. Report
.Run Report 5
8
.Ctrl. Report
.Startup Rep. 7
8
.Stat. Report
Present abnormal: display the current/present abnormality of the device, if the device is
Action report: display the protection action one by one, including the protection trip,
00-01-04 1/2
22:49:53.214 ->
Success
Ia 0.009A
Ib 0.015A
Ic 0.009A
Position changing report: displaying the historical position-changing info, including the
11
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)
00-01-11 1 / 48
22:30:28.280
DI2 0->1
Self checking report: display the abnormal situation during self checking of the device
itself;
Running report: display the report of the cool startup and entering debugging status, etc;
00-01-08 1 / 48
10:30:28.130
Cool startup
00-01-08 1 / 39
10:30:28.130
Panel Stop
00-01-08 1 / 39
06:59:243.138
Stop
Statistics report: display the system statistics info of the device program, including the
12
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)
running time of the motor; the tripping/closing times of the switch A (contacts A or CB),
the tripping/closing times of the switch B (contacts B or CB), the times of the motor, the
.Unbalance 1
18
.Earth Fault
Unbalance Rate
60%
Unbalance Time
30.00 s
Act Mode
off
Clearing the report by category, including clear all the report, clear the action report, clear
the position changing report, clear abnormal report, clear the running report, clear the
control report, clear the starting report. After selecting the wanted clear option, then
confirm via press the “OK” button, input the required password, then clearing the report
will be done.
Including the software version of the main module and display module, check code,
13
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)
Use password
1
.Password 9
.Net1 Setting
User Password
[ 0~ 9999]
0000
New Password
[ 0~ 9999]
0000
.Password 2
9
. Net1 Setting
Com. Protocol
MODBUS
Com. Address
99
BaudRate
485 - 19200
485-57600bps,485-115200bps,CAN-50k,CAN-80k,CAN-100k,CAN-125k.The Baud
14
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)
Analog quantity output setting: set the signal quantity related to 4-20mA output.
“4-20mA output” is used for the setting the signal quantity related to 4-20mA output,
settable as: NA,(Not available),IA, IB, IC, Iav, Uab, Ubc, Uca, Uav, f. “AO1 Ratio”
means the multiple of the full range of the signal quantity related to 4-20mA. If setting
“Ia” as the signal quantity, and the ratio is set as “1.0”, the rated current of device is 5A,
then 20mA means 5A, if the ratio is set as “1.2”, then 20mA means 5A*1.2=6A, the
4
.Net2 Setting 9
.4-20mA Output
4-20mA Output1
IA
AO1 Ratio
1.0
6
.Clock 9
.Language
Language
English
CT ratio and Zero sequence CT ratio: if the device CT is taken as the secondary CT, one
primary CT shall be equipped outside. The outside CT ratio and the outside zero
sequence CT ratio could be set. After setting the ratio, the measurement values will
15
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)
The info of the recorded wave could be set.”Wave data send” is for the setting of
whether actively send the wave record to main control. “wave date time” is for the
9
.Wave Set 9
WaveData Send
Disable?
WaveDate Time
5.00s
Energy settings: could set the active power and reactive power separately;
1
.Set Energy 2
.Set Stat. Inf
PE
782366.61KWH
16
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)
2
.Set Energy 2
.Set Stat. Inf
This menu is used for viewing the engineering selection, DI predefinition, DO predefinition,
I/O normal open or normal close, PLC logic and communication supervision. These info could
be viewed and revised when entering into “Device debugging” menu. For the stable running of
the load, when motor is under startup or running status, the “debugging menu” could not be
entered.
“Communication supervision” including NET1 statistics data, NET2 statistics data, DBG
statistics data, GPS statistics data, take NET1 statistics data as an example:
Device has two status: debugging status and running status. When entering in to the
“debugging” menu, the device is under debugging status.
Exiting the “debugging” status, the device will be restarted and back to running status.
There are below sub menu under device debugging: measurement accuracy-automatic,
protection accuracy-manual, measurement accuracy-manual, generating SOE, initiating the wave
record, DO checking, 4-20mA output, engineering configuration.
rated voltage and rated current, then press “OK” button to check as below screen snap
shows:
17
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)
.Gains Auto 1
8
.Prot. Gains
.Meas. Gains 1
3
.Prot. Gains
operating ……
Operate success
Protection accuracy-manual: manually check the measurement accuracy. Apply the rated
voltage and rated current, check the measurement accuracy of each channel one by one.
2
.Prot. Auto 8
.Prot. Gains
IA
0.000 A
1.000
Generating SOE: can simulate and generate kinds of SOE, including position-change
report, abnormal report, action report, running report, control report, start/stop report.
below:
18
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)
.Meas. Gains 4
8
.Generate SOE
.DI Report 1
6
.Abnor. Rrport
.DI 1 1
34
1->0
Operate success
Start the wave record: manually start the wave record once, the duration of the wave
5
.Start Wave 8
.Do Check
Operate success
DO check: testing the DO relay. Doing the close/open testing in the sequence of
19
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)
.Start Wave 6
8
.Do Check
DO1 0->1
DO1 1->0
DO2 0->1
DI check: testing the DI, give signal to each DI channel and see the check is color filled
or not. If no signal, the check will be blank, if there is signal, then the related check will
be color filled.
7
.Di Check 8
.4~20mA Output
1 2 3 4 5 6 7 8 9A B C
DI
Analogue output test: for testing the 4-20mA output. After entering the menu, edit the
required 4-20mA value, press “OK”, then the device will output the related DC quantity.
Note: when doing this test, please set the “related quantity” in the “analogue output” of
① Engineering selection configuration (showed after input the password), see below table:
20
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)
matched with
hardware or not?
phase currents)
current
switching
output
② DI predefinition
Choose the “allowed” of the “DI/DO definition”, then it is possible to make the DI
predefinition.
③ DO predefinition
Choose the “allowed” of the “DI/DO definition”, then it is possible to make the DO
predefinition.
21
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)
④ DI NO/NC settings
Set for the NO/NC of DI1-DI12 channels. Setting “NC” means negating the DI. Note: choose
the DI NO/NC.
⑤ PLC logic
22
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)
Logic 1 1
5
Logic 2
Press “confirm” key
Formula
A
Enter editable status
after pressing
“confirm”key,choose
Press “down” key
formula type:A,A&B.etc
Variable A
...
Input variable edit
interface
Press “confirm” key
Type
Enter editable status after
DI
pressing “confirm”key,swtich
input type by pressing “up” and
“down” key:DI,DO.etc;confirm by
Press “down” key pressing “confirm” key
Reverse
NO
Enter editable status after
pressing “confirm”key,swtich
input reverse weather or not by
pressing “up” and “down”
Variable
Press “down” keyconfirm by pressing “confirm”
Cont.A Status
key
Enter editable status after
pressing “confirm”key,swtich
variable define by pressing
Enter first interface by
“up” and “down”, confirm by
pressing “return”key,
pressing “confirm” key
enter next interface by
Input delay
pressing “down” interface
3000ms
Enter editable status after
pressing “confirm”key,it can be
editted from 0s to 3000ms
Press “down” key
DO_LOGIC_1
pressing “confirm”key,it can be
editted from DO_logic1 to
DO_logic5
Press “down” key
Output mode
High level
Enter editable status after
pressing “confirm”key
23
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)
⑥ recovering the default setting: make the device values, system settings, engineering
device will automatically indicate the related abnormal status, record the fault message, send
“device fault” signal, and do the interlock protection as per abnormal situations. Below is the
protection
accuracy factor
configuration configuration.
Logic
1. Display module indicates “Communication fault, check the connection”, which means there is
communication fault between main module and display module. The reasons and treatment
24
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)
measures are:
1) Check the wiring connection between main module and display module, confirming the
2) Check whether there is fault with the main module, if there are below faults (the running
lamp of main module does not blink, the field bus communication does not work, the
1) There is protection trip or protection alarm, please refer to “action report” for details, if
1) There is the self check fault, please refer to “abnormal report” for details, if required,
1) There is protection trip or protection alarm or device self checking fault, please refer to
“action report” or “abnormal report” for details, if required, please contact the
manufacturer.
1) There is protection action or protection alarm, please refer to “action report” for details,
1) There is the self check fault, please refer to “abnormal report” for details, if required,
1) The button battery for clock chip is not installed or with a low battery, please changes a
1) Wrongly set the clock time, please reset the clock time correctly;
2) The button battery for clock chip is with a low battery, please changes a new button
battery.
25
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)
9. “Clock” abnormal:
1) The device clock has not done the initiating settings, please set the current clock
correctly;
2) After setting the clock correctly, the device lose voltage and restart again, if still indicates
that “clock” is abnormal, it may be the problem with the clock chip, please contact the
manufacturer.
26