Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.

00)

Appendix 2 Operation manual of LPC-3500series protection,


measurement and control device

LPC-3500 series devices are equipped with LPC 359X series display operation module:

Sr. Device type Type of display operation


module
1 LPC-3511 LV line integrated protection, LPC-3598 display
measurement, control device operation module
2 LPC-3531/3532 LV motor integrated LPC-3597 display
measurement and control device operation module
3 LPC-3581 LV line integrated measurement LPC-3598 display
and control device operation module
4 LPC-3591 LV PT integrated measurement LPC-3599 display
and control device operation module

1
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)

1 Arrangement of display operation module

LPC-3597
RUN

COM

REM

ALARM
CANCEL

S(A)/← S(B)/→ STOP RESET


FAULT
OK

WISCOM SYSTEM CO,LTD


DBG

LPC-3598
RUN ↑
COM

REM

CLOSE
CANCEL

CLO/ OPEN RESET


FAULT

OK

WISCOM SYSTEM CO,LTD


DBG

LPC- 3599
RUN ↑
COM

REM
CANCEL
ALARM

RESET OK
FAULT

WISCOM SYSTEM CO,LTD


DBG

2
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)

2 Indicator lamp & press button

LPC-3597 Display operation module

Indicator lamp
Lamp Definition Color
Run The indicator lamp is for motor running. The lamp is dark when Green
motor is halted; the lamp blinks when motor starts, the lamp is
green when motor is under normal working status.
Com The indicator lamp is for filed bus communication. When one of Green
RS485/CAN/PROFIBUS networks work and report successfully,
the lamp is green; when abnormal, the lamp is dark.
Remote The indicator lamp is for control limits of authority. When device is Green
under local status, the lamp is dark; when device is under remote
status, the lamp is green.
Alarm The indicator lamp is for alarm. When device does protection Red
actions (alarm or trip), the lamp is red, will be dark after reset.
Fault The indicator lamp is for self checking. When device is abnormal Red
after self checking, the lamp is red, will be dark after reset.
Note 1: when device is under running status, indicator lamps shall indicate as mentioned in above
table; when device is under debugging & commissioning or when power is just switched on,
all the indicator lamps are lighted.
Press button/interface
Press Operation explanation
button/
interface
S(A)/<- S(A)/ <- is the left moving button, can control the forward direction starting of
motor under control display mode; can move the cursor one step to left under
editing mode;
S(B)/-> S(B)/ -> is the right moving button, can control the reverse direction starting of
motor under control display mode; can move the cursor one step to right under
editing mode;
STOP The button can stop the motor under motor control display mode.
Reset Using for resetting
↑ The button can up-turn the Menu or add 1 to the quality;
↓ The button can down-turn the Menu or minus 1 to the quality;
DBG For upgrading the software or communication between device and Stand-alone
debugging software; when using,typical wire will be used to connected with
PC and the device via DBG interface.

3
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)

LPC-3598 Display operation module

Indicator lamp
Lamp Definition Color
Run The indicator lamp shows the status of the device. The lamp is Green
green when device is under running status; the lamp is dark
when device is under debugging status.
Com The indicator lamp is for filed bus communication. When one of Green
RS485/CAN/PROFIBUS networks work and report successfully,
the lamp is green; when abnormal, the lamp is dark.
Remote The indicator lamp is for control limits of authority. When device Green
is under local status, the lamp is dark; when device is under
remote status, the lamp is green.
Close The indicator lamp is for switch status indication. When the Red
switch is on, he lamp is red; when the switch is off, the lamp is
dark.
Fault The indicator lamp is for fault or self checking. When device is Red
abnormal after self checking or did the protection action/alarm,
the lamp is red, will be dark after reset.
Press button/interface
Press Operation explanation
button/
interface
CLO/<- CLO/ <- is the left moving button, can close the CB under control display mode;
can move the cursor one step to left under editing mode;
-> can move the cursor one step to right under editing mode;
OPEN The button can open the CB control display mode.
Reset Under control display mode, the button is for resetting the operation
↑ The button can up-turn the Menu or add 1 to the quality;
↓ The button can down-turn the Menu or minus 1 to the quality;
DBG For upgrading the software or communication between device and Stand-alone
debugging software; when using,typical wire will be used to connected with
PC and the device via DBG interface.

4
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)

LPC-3599 Display operation module


Indicator lamp
Lamp Definition Color
Run The indicator lamp shows the status of the device. The lamp is Green
green when device is under running status; the lamp is dark
when device is under debugging status.
Com The indicator lamp is for filed bus communication. When one Green
of RS485/CAN/PROFIBUS networks work and report
successfully, the lamp is green; when abnormal, the lamp is
dark.
Remote The indicator lamp is for control limits of authority. When Green
device is under local status, the lamp is dark; when device is
under remote status, the lamp is green.
Alarm When RS485 communication is ok, the lamp is red; Red
Fault The indicator lamp is for self checking. When device is Red
abnormal after self checking, the lamp is red, will be dark after
reset.
Note 1: when device is under running status, indicator lamps shall indicate as mentioned in above
table; when device is under debugging & commissioning or when power is just switched on,
all the indicator lamps are lighted.
Press button/interface
Press Operation explanation
button/
interface
<- This is the cursor left moving button
-> This is the cursor right moving button
Reset Using for resetting
↑ The button can up-turn the Menu or add 1 to the quality;
↓ The button can down-turn the Menu or minus 1 to the quality;
DBG For upgrading the software or communication between device and Stand-alone
debugging software; when using,typical wire will be used to connected with
PC and the device via DBG interface.

5
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)

3 Device LED display description


3.1 Default display screen (taking LPC-3531 as example)

The LED main display screen is as follow when device is under normal running status:

In the main screen, user can press “CANCEL” button and go into the main Menu, also can

press the “S/(A)” button or other control buttons to operate the device as per requirements.

3.2 Control operation of main screen

In the main screen, when device is under local status, user can do the control operation
(start/stop the motor) or reset the device.
① Control operation, take Startup A as example, as below:

After pressing the S/(A) button, the LED screen will show as below:

If quitting the “start A” control operation is required at this stage, please press “Cancel”

button, the LED display returns back to main screen, the control operation is cancelled this

time.

If confirming the “start A” control operation, please press “OK” button, the LED display

returns back to main screen, the control operation is done this time.

② Reset operation

Pressing the “reset” button, the LED displays as below:

6
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)

The resetting operation is done this time.

4 Device Menu Description


In the main screen, press the “Cancel” button and return to the main Menu interface then

as below:

Via using the up/down button to choose the required function, then press “OK” to enter into

the next layer Menu. The Menu structure is as below:

7
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)

Present abn. Prot. data Unbalance


Imbalance rate
Act. report Meas. data Earth fault
Imbalance time
Di report Energy data Under load
Act mode
Abnor. rep. Phase data Block fau;t
Run report Signal data O/T startup
Ctrl. report Loop display Fault interl
Startup rep.
Over thermal
Stat. report
overload
Under power
CLR All Rep.
Fuse break
CLR Act Rep.
undervoltage
CLR DI Rep. Main menu
overvoltage
CLR Abnor.
Phase setting
CLR Run Rep. Meas.
Undervoltage
CLR Ctrl Rep. Reports restat
overflow
CLR Startup Settings
TE
Clear report
Current fuse
Gains Auto System info.
other
Prot gains System cfg.
Meas. gains other

Generate SOE See info. Controller ver

Start wave Device Debug checkcode

Do check Load time

DI check Compile time

4-20mA Display ver


password
Field Cfg. Compile time
Net1 setting
Now time
Net1 setting
Field Cfg. 4-20mA Set. Field Cfg.
DI Predefine clock Set energy
Field Cfg.
DO Predefine language Set Stat. Inf
DO Predefine
DIOpen
CT Rate DIOpen
Or Close
Or Close
PLC Logic I0CT Rate PLC Logic
Restore define
settings Wave set Com Monitor

4.1 Measured value displaying

Entering into this menu, could view all the measured values and status info as below:

8
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)

.Prot. Data 1
6
.Meas. Data

.Energy Data 3
6
.Phase Angle

.Signal Data 5
6
.Loop Display

 Protection value display: 3 phase current, 3 phase voltage, positive/negative sequence

current, zero sequence current, average current, Current unbalance rate, protection

power, over heat value(below is the screen snap of the LED display):

 Measurement value display: 3 phase current, 3 phase voltage, active power, reactive

power, power factor, average current, current unbalance rate, frequency (below is the

screen snap of the LED display):.

 Power display: active power and reactive power;

 Phase angle display: the phase angle of current and voltage:

9
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)

 Signal quantity display: showing the status of DI & DO. If DI & DO has signal, the

below check will be filled; if DI & DO does not have signal, the below check will be blank.

 Circularly display: the measurement value/protection value/power energy/phase

angle/status info, etc will be circularly displayed.

4.2 Report display

The menu could be used to check the reports of the device:

10
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)

.Present Abno 1
8
.Act. Report

.DI Report 3
8
.Abnor. Report
.Run Report 5
8
.Ctrl. Report
.Startup Rep. 7
8
.Stat. Report

 Present abnormal: display the current/present abnormality of the device, if the device is

under normal working status, then display “no abnormal”;

 Action report: display the protection action one by one, including the protection trip,

protection alarm, protection return-back.

00-01-04 1/2
22:49:53.214 ->

Block Fault ACT

Success
Ia 0.009A
Ib 0.015A

Ic 0.009A

 Position changing report: displaying the historical position-changing info, including the

status change of DI;

11
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)

00-01-11 1 / 48
22:30:28.280
DI2 0->1

 Self checking report: display the abnormal situation during self checking of the device

itself;

 Running report: display the report of the cool startup and entering debugging status, etc;

00-01-08 1 / 48
10:30:28.130
Cool startup

 Control report: display the report of the control operation;

00-01-08 1 / 39
10:30:28.130
Panel Stop

 Start/ stop report: display the start/stop report of the motor;

00-01-08 1 / 39
06:59:243.138
Stop

 Statistics report: display the system statistics info of the device program, including the

12
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)

running time of the motor; the tripping/closing times of the switch A (contacts A or CB),

the tripping/closing times of the switch B (contacts B or CB), the times of the motor, the

times of the protection action.

4.3 Value settings

Setting the protection values as per protection requirements.

.Unbalance 1
18
.Earth Fault

Unbalance Rate
60%

Unbalance Time
30.00 s

Act Mode
off

4.4 Clearing the report

Clearing the report by category, including clear all the report, clear the action report, clear
the position changing report, clear abnormal report, clear the running report, clear the
control report, clear the starting report. After selecting the wanted clear option, then
confirm via press the “OK” button, input the required password, then clearing the report
will be done.

4.5 System info

Including the software version of the main module and display module, check code,

13
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)

compiling time, loading time and current time.

4.6 System settings

Setting the system parameters of the device:

 Use password

1
.Password 9
.Net1 Setting

User Password
[ 0~ 9999]
0000

New Password
[ 0~ 9999]
0000

 Communication setting: setting the communication protocol, address, baud rate.

.Password 2
9
. Net1 Setting

Com. Protocol
MODBUS

Com. Address
99

BaudRate
485 - 19200

Communication protocol: modbus, IEC103,IEC103(special).

Communication address: 1-255;

Baud rate: settable values 485-4800bps,485-9600bps,485-19200bps,485-38400bps,

485-57600bps,485-115200bps,CAN-50k,CAN-80k,CAN-100k,CAN-125k.The Baud

Rate of PROFIBUS is not required to be set in the device.

14
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)

 Analog quantity output setting: set the signal quantity related to 4-20mA output.

“4-20mA output” is used for the setting the signal quantity related to 4-20mA output,

settable as: NA,(Not available),IA, IB, IC, Iav, Uab, Ubc, Uca, Uav, f. “AO1 Ratio”

means the multiple of the full range of the signal quantity related to 4-20mA. If setting

“Ia” as the signal quantity, and the ratio is set as “1.0”, the rated current of device is 5A,

then 20mA means 5A, if the ratio is set as “1.2”, then 20mA means 5A*1.2=6A, the

range of the ratio is 0.8-1.2.

4
.Net2 Setting 9
.4-20mA Output

4-20mA Output1
IA

AO1 Ratio
1.0

 Clock setting: set the time of the device, year/month/day/hour/mins/secs.

 Language selection: Choose Chinese or English;

6
.Clock 9
.Language

Language
English

 CT ratio and Zero sequence CT ratio: if the device CT is taken as the secondary CT, one

primary CT shall be equipped outside. The outside CT ratio and the outside zero

sequence CT ratio could be set. After setting the ratio, the measurement values will

multiple this ratio.

15
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)

 Wave record settings

The info of the recorded wave could be set.”Wave data send” is for the setting of

whether actively send the wave record to main control. “wave date time” is for the

setting of the wave length.

9
.Wave Set 9

WaveData Send
Disable?

WaveDate Time
5.00s

4.7 Other settings

For setting the energy and statistics info.

 Energy settings: could set the active power and reactive power separately;

1
.Set Energy 2
.Set Stat. Inf

PE
782366.61KWH

 Statistics info settings: could set the statistics info by category;

16
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)

2
.Set Energy 2
.Set Stat. Inf

Run time (day)


206

4.8 View menu

This menu is used for viewing the engineering selection, DI predefinition, DO predefinition,

I/O normal open or normal close, PLC logic and communication supervision. These info could

be viewed and revised when entering into “Device debugging” menu. For the stable running of

the load, when motor is under startup or running status, the “debugging menu” could not be

entered.

The engineering selection, DI predefinition, DO predefinition, I/O normal open or normal

close, PLC logic will be described in device debugging later.

“Communication supervision” including NET1 statistics data, NET2 statistics data, DBG

statistics data, GPS statistics data, take NET1 statistics data as an example:

4.9 Device debugging

Device has two status: debugging status and running status. When entering in to the
“debugging” menu, the device is under debugging status.
Exiting the “debugging” status, the device will be restarted and back to running status.
There are below sub menu under device debugging: measurement accuracy-automatic,
protection accuracy-manual, measurement accuracy-manual, generating SOE, initiating the wave
record, DO checking, 4-20mA output, engineering configuration.

 Protection accuracy-automatic: automatically check the protection accuracy. Apply the

rated voltage and rated current, then press “OK” button to check as below screen snap

shows:

17
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)

.Gains Auto 1
8
.Prot. Gains

.Meas. Gains 1
3

.Prot. Gains

operating ……

Operate success

 Measurement accuracy-automatic: automatically check the measurement accuracy. The

checking method is the same to protection accuracy-automatic.

 Protection accuracy-manual: manually check the measurement accuracy. Apply the rated

voltage and rated current, check the measurement accuracy of each channel one by one.
2
.Prot. Auto 8
.Prot. Gains

IA
0.000 A
1.000

 Measurement accuracy-manual: automatically check the measurement accuracy. The

checking method is the same to protection accuracy-manual.

 Generating SOE: can simulate and generate kinds of SOE, including position-change

report, abnormal report, action report, running report, control report, start/stop report.

Take the position change message/report as an example (DI 1 change from 0 to 1) as

below:

18
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)

.Meas. Gains 4
8
.Generate SOE

.DI Report 1
6

.Abnor. Rrport

.DI 1 1
34

1->0

Operate success

 Start the wave record: manually start the wave record once, the duration of the wave

record is set in the debugging wave record.

5
.Start Wave 8
.Do Check

Operate success

 DO check: testing the DO relay. Doing the close/open testing in the sequence of

DO1-DO7. Take DO1 as an example:

19
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)

.Start Wave 6
8

.Do Check

DO1 0->1

DO1 1->0

DO2 0->1

 DI check: testing the DI, give signal to each DI channel and see the check is color filled

or not. If no signal, the check will be blank, if there is signal, then the related check will

be color filled.

7
.Di Check 8
.4~20mA Output

1 2 3 4 5 6 7 8 9A B C
DI

 Analogue output test: for testing the 4-20mA output. After entering the menu, edit the

required 4-20mA value, press “OK”, then the device will output the related DC quantity.

Note: when doing this test, please set the “related quantity” in the “analogue output” of

“system setting” as “NA-not available”.

 Engineering configuration: including engineering selection, PLC logic, DI definition,

DO definition, Normal open/normal close setting, and default setting.

① Engineering selection configuration (showed after input the password), see below table:

Thoese parameters/configuration required to be matched with hardware shall be rectified

20
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)

with hardware before delivery out of factory.

Items Values Required to be

matched with

hardware or not?

Rated voltage 57.74V,100V,220V,380V Yes

Rated current 1A,5A,25A,100A,150A,250A,400A Yes

Control limit of Two status(Local, remote) No

authorities Three status(Local, remote, communication)

Self zero sequence(zero sequence current is calculated from 3 Yes

phase currents)

Selection equipped of Outside zero sequence(zero sequence current is provided by

outside zero sequence outsider zero sequence CT)

Rated zero sequence 1A, 5A Yes

current

Control mode See the manual in details No

DI/DO definition Not allowed, allowed No

DI NO/NC selection Not allowed, allowed No

5-200ms, DI debounce time, the default value is 20ms No


Debounce time
Current phase sequence NO switch, CA switch, BC switch, AB switch No

switching

Earthing protection Trip contacts, trip CB No

output

Contacts position signal YES, NO

② DI predefinition

Choose the “allowed” of the “DI/DO definition”, then it is possible to make the DI

predefinition.

③ DO predefinition

Choose the “allowed” of the “DI/DO definition”, then it is possible to make the DO

predefinition.

21
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)

④ DI NO/NC settings

Set for the NO/NC of DI1-DI12 channels. Setting “NC” means negating the DI. Note: choose

the “allowed” in the “selection of DI NO/NC” of “engineering configuration” before setting

the DI NO/NC.

⑤ PLC logic

Could do the logic setting for logic 1/2/3/4/5, see below:

22
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)

Logic 1 1
5
Logic 2
Press “confirm” key

Formula
A
Enter editable status
after pressing
“confirm”key,choose
Press “down” key
formula type:A,A&B.etc

Variable A
...
Input variable edit
interface
Press “confirm” key

Type
Enter editable status after

DI
pressing “confirm”key,swtich
input type by pressing “up” and
“down” key:DI,DO.etc;confirm by
Press “down” key pressing “confirm” key

Reverse
NO
Enter editable status after
pressing “confirm”key,swtich
input reverse weather or not by
pressing “up” and “down”

Variable
Press “down” keyconfirm by pressing “confirm”

Cont.A Status
key
Enter editable status after
pressing “confirm”key,swtich
variable define by pressing
Enter first interface by
“up” and “down”, confirm by
pressing “return”key,
pressing “confirm” key
enter next interface by

Input delay
pressing “down” interface

3000ms
Enter editable status after
pressing “confirm”key,it can be
editted from 0s to 3000ms
Press “down” key

output Enter editable status after

DO_LOGIC_1
pressing “confirm”key,it can be
editted from DO_logic1 to
DO_logic5
Press “down” key

Output mode
High level
Enter editable status after
pressing “confirm”key

23
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)

⑥ recovering the default setting: make the device values, system settings, engineering

configurations, accuracy factors, etc to be the default values.

5 Device self checking information


The device has complete self-check function, when fault happens during self-checking, the

device will automatically indicate the related abnormal status, record the fault message, send

“device fault” signal, and do the interlock protection as per abnormal situations. Below is the

definition of the common abnormal status/situations.

Type Definition Interlock

protection

EEPROM EEPROM is abnormal during self check Yes

RAM RAM is abnormal during self check Yes

Clock Clock is abnormal during self check No

Value settings Value settings is abnormal during self check Yes

Protection Protection accuracy factor is abnormally during self check Yes

accuracy factor

Measurement measurement accuracy factor is abnormally during self No

accuracy factor check

System settings System settings is abnormal during self check Yes

Engineering Self check function shall be equipped with engineering Yes

configuration configuration.

I/O definition O/I is abnormal during self check Yes

Power of output Power of output is abnormal during self check No

ExeCode CPU executive program is abnormal during self check No

Programmable Programmable Logic is abnormal during self check. No

Logic

6 Device debugging and commissioning


6.1 Common fault and treatment measure

1. Display module indicates “Communication fault, check the connection”, which means there is

communication fault between main module and display module. The reasons and treatment

24
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)

measures are:

1) Check the wiring connection between main module and display module, confirming the

wiring connection is fixed and not loosened.

2) Check whether there is fault with the main module, if there are below faults (the running

lamp of main module does not blink, the field bus communication does not work, the

device cannot work properly, please contact the manufacturer.

2. LPC-3597 device “alarm” lamp lighting:

1) There is protection trip or protection alarm, please refer to “action report” for details, if

required, please contact the manufacturer.

3. LPC-3597 device “fault” lamp lighting:

1) There is the self check fault, please refer to “abnormal report” for details, if required,

please contact the manufacturer.

4. LPC-3598 device “fault” lamp lighting:

1) There is protection trip or protection alarm or device self checking fault, please refer to

“action report” or “abnormal report” for details, if required, please contact the

manufacturer.

5. LPC-3599 device “alarm” lamp lighting:

1) There is protection action or protection alarm, please refer to “action report” for details,

if required, please contact the manufacturer.

6. LPC-3599 device “fault” lamp lighting:

1) There is the self check fault, please refer to “abnormal report” for details, if required,

please contact the manufacturer.

7. The device power-on clock cannot be saved:

1) The button battery for clock chip is not installed or with a low battery, please changes a

new button battery.

2) The clock chip is destroyed, please contact the manufacturer.

8. The time showed in the device clock is inaccurate:

1) Wrongly set the clock time, please reset the clock time correctly;

2) The button battery for clock chip is with a low battery, please changes a new button

battery.

25
Appendix2 LPC-3500 series protection, measurement and control device Manual (V1.00)

3) The device communication or GPS clock time is inaccurate;

9. “Clock” abnormal:

1) The device clock has not done the initiating settings, please set the current clock

correctly;

2) After setting the clock correctly, the device lose voltage and restart again, if still indicates

that “clock” is abnormal, it may be the problem with the clock chip, please contact the

manufacturer.

26