Installation and Startup Guide
This document covers the installation of TK6070iQ Series HMI, for the detailed
specifications and operation, please refer to Datasheet and EasyBuilder 8000 User
Manual.
Install Environment:
NEMA Rating TK6070iQ Series HMI is NEMA 4 rated.
The TK6070iQ Series has been tested to conform to European CE
requirements. This means that the circuitry is designed to resist the
Electrical
effects of electrical noise. This does not guarantee noise immunity in
Environment
severe cases. Proper wire routing and grounding will insure proper
operation.
1. Make sure that the displays are installed correctly and that the
operating limits are followed. Avoid installing units in environments
where severe mechanical vibration or shocks are present.
4. This device should be mounted in the vertical position and for use
on the flat surface enclosure.
Unpack and check the delivery. If damage is found, notify the supplier.
1. Installation Instruction, 2-sided A4 *1
3. Power Connector *1
NOTE:
Place the operator panel on a stable surface during installation. Dropping it or letting it
fall may cause damage.
Installation Instructions
Secure the operator panel in position, using all the fastening holes and the provided
brackets and screws:
Type A(mm) B(mm)
TK6070iQ 192 138
Power Connections
NOTE:
1. Connect positive DC line to the '+' terminal and the DC ground to the '-' terminal.
2. Please do not connect HMI with PLC and PC simultaneously to prevent potential
difference from destroying USB ports of HMI and PC.
To make a connection, strip about 3/8" of insulation off the end of the wire, turn the
connector screw counterclockwise until the gap is wide open, insert the wire all the
way in, and turn the screw clockwise until it's tight.
System Settings
When HMI powered up and displays image, click the system setting button. (Default
System Password: 111111)
Go to the Security tab, the default password is 111111, click the button to set your own
password.
Select USB cable > Click Download to download this project file to HMI.
( Please refer to EasyBuilder 8000 User Manual for software operation details )
Calibration Mode
Launch Project Manager, select TK6000/8000 iQ Series in Type field, select USB
cable, and then click Calibrate Touch
Communication Connections
NOTE:
Com2 [RS485 2W] supports MPI 187.5K.
COM1 COM2 COM2
PIN# Symbol
[RS232] [RS485]4W [RS485]2W
1 Rx- Rx- Data-
2 Rx+ Rx+ Data+
3 Tx- Tx-
4 Tx+ Tx+
5 GND GND
6 TxD TxD
7 RTS RTS
8 CTS CTS
9 RxD RxD
Cable Requirement
Different cables are required for various devices.
Restrict cable length to less than 500' (150m) for RS485/422 devices and 50' (15m) for
RS232 devices to avoid communications problems. Shielded cable must be used for
long lengths or cables run in an electrically noisy environment. Do not run cables next to
AC power lines or near sources of electrical noise. Be sure that the cable ends have
been inserted all of the way into mating connectors and are secure.