Application of Standard Solutions For Mesh Corner Delayed Auto-Reclose and Autoswitching With Numerical Relay
Application of Standard Solutions For Mesh Corner Delayed Auto-Reclose and Autoswitching With Numerical Relay
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY WARANGAL. Downloaded on September 26,2024 at 09:00:47 UTC from IEEE Xplore. Restrictions apply.
• Any associated circuit breaker DAR initiated
reclosure to re-energise non-faulted plant shall not These modules are designed to be loosely coupled within the
take place until isolation of associated disconnectors relay unit and connections between the modules are made
of feeder, transformers and other plant is completed. using the Programmable Scheme Logic (PSL). This method
• All Mesh HV circuit breaker reclosures shall be provides the flexibility to couple modules within the same
separated by a minimum inter-switch delay time. unit. With the GOOSE mapping and communications, it is
• If a mesh HV DAR sequence that is ready to reclose possible to add additional MCDAR to meet the switching
cannot proceed because of an inhibit condition then requirements of different mesh corner topologies. This
reclosure of any other ready HV CB shall be flexibility of the MCDAR application has been demonstrated
attempted. up to an eight-switch mesh.
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY WARANGAL. Downloaded on September 26,2024 at 09:00:47 UTC from IEEE Xplore. Restrictions apply.
with GOOSE communications was engineered. The Micom
P842 relay standard scheme solution was offered and
implemented by AREVA T&D Substation Automation
Solutions to perform DAR and ASW at Torness. Eight relays
were required to perform DAR and ASW at this site. The
relays were mounted in cubicles in two separate relay rooms,
100 meters apart. Fibre optic cables were installed in a ring
configuration between the two relay rooms providing
connection between the P842 MCDAR relays via two
Ethernet switches.
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY WARANGAL. Downloaded on September 26,2024 at 09:00:47 UTC from IEEE Xplore. Restrictions apply.
• Transformer Function Disconnector Open/ Close each mesh corner more easily controlled, increases flexibility
Status and intelligence.
• Transformer Function Autoswitching Inhibit
• Mesh corner CB Function CB Open / Close Status 4 Conclusions
• Mesh corner CB Function DAR Inhibit
• Mesh corner CB Function DAR Lockout The implementation of the MCDAR scheme with GOOSE
communication to the mesh corner DAR and Autoswitching
• Mesh corner CB Function Manual Check Synch
demonstrates a real application with the following benefits in
Initiation
comparison with old hardwired relay solutions:
• DAR Global Lockout
• DAR Corner Lockout
• Without compromising the performance of the
system, physical I/O and associated scheme wiring
Relay logic outputs:
requirements are reduced.
• DAR CB Close
• As each MCDAR unit is only physically wired to
• Manual Synch CB Close
plant items and protection associated with the local
• Feeder Line Disconnector open corner, the complexity of the old relay
• Transformer Disconnector open interconnections is also reduced.
• LV DAR Start • With application of fast peer-peer GOOSE message
• LV DAR Inhibit communication implementation, and consideration
• LV DAR Lockout of system failure interlock in the relay logic design
• Trip Relay Reset Inhibit and GOOSE mapping, it makes DAR and ASW
• Various alarms outputs operations more stable and secure.
• With less hardwiring, it makes site commissioning
GOOSE Inputs: and maintenance easier and reduces cost.
• MC DAR In
• MC DAR Start Acknowledgements
• MC DAR Inhibit
• MC DAR Lockout We thank AREVA T&D Substation Automation Solutions
• CB Token Request and ScottishPower Group for the support and facilities offered
• CB In Service for the development of the present paper.
• CB In Progress
• CB Reclaim Timer Running References
• CB Fail
[1] NGTS 3.24.63, Issue 1, May 2001 – “Mesh Station
• Other MC Receive Token DAR and Plant Isolation “
• MC CB Remote Live
• CB Fault Detected
GOOSE Outputs:
• DAR In
• DAR Start
• DAR Inhibit
• DAR Lockout
• CB Request Token
• CB In Service
• CB In Progress
• CB Fail
• CB Fault Detected
• MC Protection Operated
• CB Remote Live
Authorized licensed use limited to: NATIONAL INSTITUTE OF TECHNOLOGY WARANGAL. Downloaded on September 26,2024 at 09:00:47 UTC from IEEE Xplore. Restrictions apply.