3.protective Relaying
3.protective Relaying
3.protective Relaying
1 Protective relaying
3. PROTECTIVE RELAYING
SYLLABUS
3.1 Requirements – relay time, related terms
OBJECTIVES
❖ To understand requirement of protective relaying in protection system.
❖ To study µP based over current relay, distance relay and directional relay.
e] Stability
f] Simplicity and
g] Economy
A] Selectivity and Discrimination:
1) Selectivity is the quality of a protective relaying by which it is able to ‘select’
(search out) correctly the faulty part of the system and isolate it from the healthy part of
the system, by tripping the nearest circuit breaker. Or
Selectivity is the ability of a relay to select the faulty part of the system and isolate
it from the remaining healthy part of the system with the help of either circuit breaker or
contactor.
2) Discrimination is the quality of relay due to which it distinguishes between the
following:
1] Normal condition and abnormal condition.
2] Abnormal condition within protective zone and abnormal condition elsewhere
Also, it should be able to distinguish whether a fault lies within its zone of protec-
tion or outside the zone. The quality, ‘Discrimination’, enables the protective relaying to
distinguish between
1] Normal and abnormal condition
2] Abnormal condition within its zone of protection
3] Abnormal condition outside its zone of protection.
Bus bar
Bus bar
CB-1 CB-2
G
The relay should also be able to discriminate between a fault and a transient condi-
tion like power surges of magnetising inrush current of a transformer. The magnetising in-
rush current of a transformer may be 5 to 7 times the full load current and hence for a large
transforms it is comparable with a fault current.
If fault occurs at point F as shown in fig 3.1, the short circuit current (ISC) will flow
through the circuit breakers CB-l, CB-2 and CB-3. So only circuit breaker CB-3 should
operate. Then we say that the protective relaying is having selectivity.
B] Reliability:
‘It means ‘trust – worthiness’.
The protective relaying should be reliable in its operation i.e. it should not fail to
operate in the event of faults in its protected zone. It should not operate unnecessarily.
The basic requirement of reliable protection is reliability of each component includ-
ing C.B. relays, CT’S, P.T.S, trip circuit, battery system, cables etc.
The protective relaying should operate reliably when a fault occurs in its zone of
protection. In other words, it should not fail to operate in the event of faults in its zone of
protection. The failure of protective relaying may be due to failure or fault in the compo-
nent or element of protective relay systems. Its components are the protective relay, C.T.,
P.T., battery, circuit breakers, etc. To obtain a high degree of reliability, greater care should
be given to the design, testing, installation, and maintenance of the various elements of the
protective system. The relay contact material, contact pressure is also very important as-
pect as far as, reliability is considered. A typical range of reliability of a protective system
is 98 % to 99 % in the Soviet Union and in other countries it is 80 % to 90 %.
C] Sensitivity:
Sensitivity is the ability of relay system to operate when the operating current or
fault current just exceeds its preset value called as pick-up current. Or
It is the ability of the relay to respond and operate with the low value of actuating
quantity.
It is a measure of minimum volt – ampere required for input for necessary to oper-
ate relay. The relay should not operate when the current in the relay coil is below its pick-
up value. Thus, sensitivity of a protective relaying refers to the smallest value of actuating
quantity at which the protective relay starts acting in relation with the minimum value of
fault current.
Sensitivity of a protective system is expressed by a sensitivity factor, KS.
It is required that the sensitivity factor should not be less than 1.5 to 2 in value.
D] Quickness of Action or Fastness of Operation:
Electrical Power System – II 3.5 Protective relaying
The relay system should be very quick so that the faulty section can be disconnect-
ed quickly. For this, relay time and fault clearing time should be as small as possible.
1] Relay time is the time between the instant of occurrence of fault and the instant
of closure of relay contacts, and
2] The fault clearing time is the time between the instant of fault occurrence and in-
stant of final are interruption in circuit breaker.
(Speed and Time of operation) Quick disconnection on occurrence of a short circuit
decreases the amount of damage, helps maintaining the stability of machines operating in
parallel ensures normal operating conditions in the healthy section of the system, etc. Also,
it decreases the possibility of spreading of a fault into the power system. Therefore, a pro-
tective system should be fast enough to remove the faulty element of the system as quickly
as possible. Though fast fault clearing is desirable, time lag is purposely provided in many
protective systems for the following purposes.
a] To distinguish between main and back up protection.
b] To prevent the operation of relay during transients, motor-starting currents, load
permissible fluctuations etc.
E] Stability:
It is the quality of a protective system by virtue of which the protective system re-
mains inoperative under the specified conditions such as system disturbance, through
faults, transients, momentary faults etc. or
Stability is defined as the quality of protective system due to which it will not oper-
ate under the specified conditions such as system disturbance, through faults, transients,
momentary faults etc.
i.e. It does not operate and remains stable under certain specified conditions such
as system disturbances, through faults (i.e. faults outside its zone of protection), transients
etc.
In many cases, time delay, biasing, filter circuits, etc are provided to make the pro-
tective system stable under certain disturbances
F] Simplicity:
The protective relaying system should be simple so that it can be easily maintained.
Reliability is very closely related to simplicity. If the protective system is simpler, there
will be greater reliability.
G] Economy:
The economic aspect is the most important factor in the choice of a particular pro-
tection scheme. An ideal scheme of protection is not economically justified. As a rule, the
Electrical Power System – II 3.6 Protective relaying
cost of protective scheme should be about 1% of the total cost of equipment to be protect-
ed, but should not be more than 5 % of the total cost of the equipment to be protected.
However, when the equipment to be protected has got utmost importance (i.e. generators,
main transmission lines, etc), the cost of protective equipment does not matter to increase
reliability.
Nowadays micro-processor-based protective relays are used. The cost of protective
scheme with microprocessors is about 15 times more than those without microprocessors.
If the computer performs other control functions in addition to protection, then the
microprocessor based protective scheme is economical otherwise not.
3.3 IMPORTANT DEFINITIONS:
A] Relay:
A relay is an automatic device by means of which an electrical circuit (trip circuit
or alarm circuit etc) is controlled (opened or closed) with a change in the same or another
electrical circuit. Relays are the essential components of a protective relaying.
B] Protective Relay:
A protective relay is an automatic device which detects an abnormal condition (any
disturbance or fault) in an electrical circuit and initiates the operation of a circuit breaker
to isolate the faulty element of the system. In some cases, it may give an alarm or some vis-
ible indication to watchful operator.
Protective relays detect the abnormal conditions in electrical circuits by constantly
measuring the electrical quantities (e.g. current, voltage, frequency, impedance, phase an-
gle etc) which are different under normal and fault conditions. After detecting the fault, the
relay operates to close the trip circuit of the circuit breaker which results in the opening of
the circuit breaker contacts and hence in the disconnection of the faulty part of the circuit
system.
3.4 FUNCTIONS OF PROTECTIVE RELAYING:
a] To give an alarm or to close the trip circuit of circuit breaker so as to disconnect
any element of power system when it undergoes short circuit or it starts operating abnor-
mally.
b] To disconnect the faulty part as quickly as possible so as to minimise the damage
to the faulty part.
c] To disconnect the faulty part as quickly as possible so as to improve the system
stability and service continuity i.e. to prevent the total failure of the power system.
d] To disconnect the part which starts operating abnormally so as to prevent the
subsequent faults.
Electrical Power System – II 3.7 Protective relaying
The relay which operates at a pre-set value of current, which is more than the full-
load current of equipment, machine etc, this type of relays may have intentional time lag.
J] Inverse definite minimum time relay:
This is the relay which has inverse characteristic of current verses time. i.e. time of
operation is reduced when fault current increases and vice-versa. But the relays takes a
specified minimum time for its operation.
K] Directional relay:
This is a relay which operates only when the direction of current is reversed or the
phase angle of the current have a displacement more than the desired value.
L] Differential relay:
It is a relay which responds to the vector difference between two (or more) similar
quantities.
M] Impedance relay:
V
It is a relay which senses the ratio = Z and operates accordingly.
I
N] Distance relay:
In such type of relay, the operation is based on the measurement of ratio V/I. It
gives the measurement of distance between relay location and fault location.
O] Electromechanical relay:
It is a conventional relay in which movable parts perform the measurement.
P] Biased relay:
It is the relay which characteristic is modified by additional mechanical or elec-
tromagnetic provision such as a bias-coil, magnet etc.
Q] Static relay:
It is the relay in which, relay measurements or comparision is performed by sta-
tionary (static) circuit.
R] Relaying Systems:
Electrical Power System – II 3.9 Protective relaying
circuit breaker to cause the opening of the circuit breaker. Hence the faulty section is dis-
connected from the healthy system.
Most of the relays in the power system are of electro-mechanical type. They work
on the following two main operating principles.
a] Electromagnetic attraction (actuated by D.C. or A. C. quantities)
b] Electromagnetic induction (actuated by A. C. quantities only) Thus, the basic re-
lays can be classified as:
1] Electromagnetic attraction type and
2] Electromagnetic induction type
A] Electromagnetic Attraction Type Relays: These are simplest type of relays.
The important types of electromagnetic attraction type relays are:
1] Attracted armature type relays,
2] Plunger type or solenoid type relays,
3] Balanced beam type relays.
1] Attracted armature type relay:
Relay
To trip circuit
contact
Electromagnet
Coil Armature
Figure 3.2 Hinged Armature Type Relay
These types of relays have a coil or an electromagnet energised by coil. The coil is
actuated by the operating quantity which may be proportional to circuit current or voltage.
Fig. 3.2 shows a hinged armature type relay.
Electrical Power System – II 3.11 Protective relaying
Spring
Plunger
I
A.C. or D.C. current
Coil (solenoid )
When a fault occurs, the current through the solenoid becomes more than the pick
value which causes the plunger to be attracted to the solenoid, i.e., downwards. The down-
ward movement of the plunger closes the trip circuit of the circuit breaker, the circuit
breaker is operated and thus the faulty section is disconnected.
3] Balanced beam type relay:
It consists of a horizontal beam pivoted at its centre, with one armature attached
one of its sides. There are two coils as shown in fig. 3.4. Under normal operating condi-
tions, the current through the operating coil is such that the beam remains in horizontal po-
sition till the operating force becomes more than restraining force.
Compressed spring
Restraining
Operating
coil
coil
When a fault occurs, the current in the operating coil becomes more than the pick
up value required to tilt the beam. i. e. attracted to close the trip circuit of circuit breaker to
disconnect the faulty section. The current in the operating coil gives operating force while
Electrical Power System – II 3.13 Protective relaying
the current in the other coil gives restraining force. The beam is given slight mechanical
bias by means of a spring such that under normal conditions, the contacts are kept open.
In impedance balance relay, voltage and current energise the two coils.
Operating Principle:
The net torque is given by,
0 = K1 I12 − K 2 I 22
K1 I12 = K 2 I 22
2
I K2
i. e. 1 =
I2 K1
I1 K2
i. e. =
I2 K1
= constant
Fig. 3.5 shows the operating characteristic of the relay. It is an approximate straight
line. It is slightly curved for low currents due to the effect of spring.
Balanced beam relay is difficult to design over a wide range. It is so because the
force is proportional to I2.The relay is fast and instantaneous. The relay is largely replaced
by permanent magnet moving coil relay having better accuracy and lower VA burden. The
VA burden is of the order of 0.2, 0.4, 0.6 VA for 0.1 - 0.6 ampere range.
Electrical Power System – II 3.14 Protective relaying
I1
Negative torque
Operating region
current
Operating
characteristics (thick)
duced currents cause the flux in the flux in the portion of the iron surrounded by the shad-
ing rings to lag in phase by (40 to 50) behind the flux in the unshaded portion of the
shaded poles. The interaction of the two fluxes differing in phase produces the necessary
torque to rotate the disc. The torque is proportional to the product of the two fluxes.
Shaded pole
I
Shaded portion
S U Unshaded portion
N Actuating
Disc (Aluminium) current
S
i.e. T S u sin
If S and u are assumed to be proportional to the current, I in relay coil, then,
T I2 sin
Fig. 3.7 shows the construction which is actually used in practice.
Disc P
Relay coil
N
Disc N
S
Upper magnet
I1
Primary winding
I2
To trip circuit
Aluminium disc
Lower magnet
The current, I1, in the primary winding induces e.m.f. (by transformer action) in the
secondary. Due to this, e.m.f. induced in the secondary, a current I2 is circulated in it. The
currents I1 and I2 produce alternating fluxes 1 and 2 respectively. Each flux cuts the alu-
minium disc. The two fluxes 1 and 2 differ in phase by an angle. The two fluxes pro-
duce the driving torque in the disc which is proportional to 12 sin.
An important feature of watt-hour - meter type relay is that opening or closing the
secondary winding circuit can control its operation. If the circuit of secondary winding is
opened, the primary winding cannot set up flux and hence no torque will be produced and
thus the relay can be made inoperative.
3] Induction cup relay:
Electrical Power System – II 3.17 Protective relaying
Fig. 3.9 shows induction cup relay. It closely resembles an induction motor, except
that the rotor iron is stationary, only the rotor conductor (cylindrical) portion being free to
rotate.
To trip
circuit
Stationary Rotor
iron core cup
A stationary iron core is placed inside the hollow cylindrical rotor called cup to de-
crease the air gap without increasing inertia. The rotating magnetic field is produced by
two pairs of coils wound on four poles placed radially around the outside of the cup as
shown in the fig. 3.9. If 1 and 2 be the fluxes produced by the two pair of poles, torque
produced is proportional to 1 2 sin, where is the phase displacement between the two
fluxes. This type of construction can be of single winding or double winding type and is
used for high-speed induction relay because the moment of inertia can be kept much small-
er than induction disc relays.
Theory of induction relay torque:
In induction relays, torque is produced when one alternating flux reacts with eddy
currents induced in a rotor (say, disc) by another alternating flux of the same frequency but
displaced in time and phase.
Fig. 3.10 Production of (force) torque in an induction relay
Electrical Power System – II 3.18 Protective relaying
2
I2 I1
F2 F1 i2
i1
The two fluxes 1 and 2 are produced in a disc type shaded pole relay by shading
technique. In watthour-meter type, 1 is produced by the upper magnet and 2 by the lower
magnet. In case of the cup type construction, 1 and 2 are produced by pairs of coils.
The theory given below is applicable for both disc type and cup type induction re-
lays.
The fluxes are A. C. quantities and therefore can be expressed as under.
1 = 1 m sin t
2 = 2 m sin (t + )
where is the phase displacement between 1 and 2 . The flux 2 leads 1 by , e.m.f.’s
induced in the disc or cup are:
d1
e1
dt
d ( 1m sin ωt )
e1
dt
e1 1m cost …[1]
d2
Similarly e2
dt
d ( 2m sin ( ωt + ) )
e
dt
As the paths to eddy currents in the disc have negligible self-inductance, it may be
assumed that the induced eddy currents in the disc/cup are in phase with their e.m.f’s.
i2 2m cos ( ωt + )
The eddy current produced by one flux reacts with the other flux and vice-versa.
Therefore, the forces are:
F1 1 i 2
and F2 2m i1
Since these forces are in opposition as shown in fig. 3.10 the resultant force is giv-
en by,
F = (F2 – F1)
or F 1 2 sin or T 1 2 sin
F I1 I 2 sin
Thus the induction relay is a sine comparator. The torque expression, T 1 2 sin
shows that the maximum torque is developed when is 90 or 270 and zero torque when
is 0 or 180
3.7 MOVING COIL RELAYS:
Electrical Power System – II 3.20 Protective relaying
Fig. 3.11 shows a permanent magnet moving coil relay. It responds to D.C. quanti-
ties only. It can be used with A.C. quantities in combination with rectifiers. These relays
are most sensitive type electromagnetic relays. These are costlier than induction cup or
moving iron type relays. These are used as slave relays.
In this relay the coil is free to rotate in the magnetic field between poles of a per-
manent magnet. The torque is produced by the interaction between the magnetic field due
to the magnet and the field produced by operating current in the relay coil.
Fixed contact
Moving
contact
N S
Coil
Permanent magnet
tors, power equipments and distribution lines. The induction disc type relay is commonly
used.
The operating time of all over current relays tends to become asymptotic to a defi-
nite minimum value with increase in the value of operating current. This is due to satura-
tion of the magnetic circuit. So by varying the point of saturation, different characteristics
can be obtained. The different characteristics are:
1] Definite time
2] Inverse definite minimum time (IDMT)
3] Very inverse
4] Extremely inverse
These are obtained with induction disc and induction cup relays.
IDMT
Definite time
Operating time in second
10
Very inverse
Extremely inverse
In induction relays, if both fluxes are produced by the same quantity, say current
below saturation, the torque is proportional to I2, (the current in the relay coil). By shifting
saturation point, above different characteristics are obtained. Out of all these characteris-
tics, IDMT is the only characteristics which is specified by Indian standards - IS: 3231-
1965.
The time current characteristics are conveniently plotted on a log-log scale.
Electrical Power System – II 3.22 Protective relaying
Two basic adjustable settings on all inverse time relays are as:
1] Time multiplier setting (TMS)
2] Current setting known as the plug setting multiplier (PSM)
B] Important Terms:
Following are some important terms used with relays.
1] Pickup current:
It is the minimum current in the relay coil at which the relay starts to operate.
From CT
Plug setting
Relay coil
Brake
magnet
2] Current setting:
In disc type relays, there are a number of tappings provided on the relay coil to ad-
just the pick up current to any defined value. These tappings on the relay coil are shown in
fig. 3.13.
Electrical Power System – II 3.23 Protective relaying
An over current relay which is used for phase to phase fault protection can be set at
50% to 200% of the rated current in steps of 25%, the settings are marked as shown in fig.
3.14
Plug bridge
Operating current
50% 75% 100% 125% 150% 175% 200%
To relay coil
Current setting is usually achieved by the use of tappings on the relay coil. The taps
are brought out to a plug bridge as shown in fig. 3.14. The number of turns on the relay
coil is changed by changing position of the plug bridge. It changes the torque on the disc
and hence the pick up value also.
The relay used for protection against earth-faults (called earth fault relay) has
settings from 20% to 80% of the rated current in steps of 10 %. The current rating of an
earth-fault relay is 1 A while that of over current relay (used for phase to phase protection)
is 5 A.
3] Plug setting multiplier (PSM):
It is defined as the ratio of fault current in relay coil to the pick - up current. PSM
can be expressed as,
Electrical Power System – II 3.24 Protective relaying
10
Operating time in second
1 2 3 4 5 10 20
Current as multiple of setting (PSM)
Suppose that at a particular value of the current or plug setting multiplier(PSM), the
operating time is 4.0 seconds with TMS = 1. The operating time for the same current with
TMS = 0.1 will be 4.0 × 0.1 = 0.4 second. In other wards, if the time from the curve is 4.0
Electrical Power System – II 3.25 Protective relaying
seconds (Tm) and the operating time required is 0.4 second (T) the TMS must be,
TMS = T/TM = 0.4 / 4.0 = 0.1.
T
TMS =
Tm
Where T = the required time of operation and Tm = the time obtained from the
relay characteristic curve at TMS =1.0 and employing the PSM equivalent to maximum
fault current.
Current setting is adjusted by means of a tapped plug bridge shown in fig. 3.14,
hence known as plug settings multiplier (PSM)
PSM 2 4 8 10 20
Solution:
Relay current setting = 150% i.e., the pick up current will be more by 50 % than 5 A
i.e. 5 × 1.5 = 7.5 A
400
C. T. ratio =
5
= 80
Electrical Power System – II 3.26 Protective relaying
2400
=
7.5 80
= 4
P.S.M. = 4
Operating time from, the given for PSM = 4 is 5 seconds. This time is for TMS = 1.
The operating time for TMS = 0.4,
T = 5 × 0.4
= 2.0 seconds
B) Indirect Heated Thermal Relay:
Fig.3.16 represents the schematic arrangement of this type of relay.
Current proportional to system current is made to flow through the heating coil of
the relay. The bimetallic strip gets heated by means of heat produced by heating coil. A
moving contact is fixed to an insulated, pivoted arm. The spring ‘S’ makes the contact of
insulated arm with the bimetallic strip. The tension of spring ‘S’ can be changed by move-
ment of the sector shaped plate ‘A’. In other words, with the help of sector A, the current
setting of relay can be changed. At room temperature, the strip is straight but when current
flows through heating coil, it bends due to which the tension of the spring is reduced at the
set value of current. The bending of strip is sufficient to close the relay contacts against the
force of spring ‘S’ Thus trip circuit of circuit breaker gets signal for operation.
Such type of over current relay is mostly used for protection of motor.
Electrical Power System – II 3.27 Protective relaying
Relay contacts
Bimetallic strip
Heating coil
To C.T.
To trip
circuit
Calibration
setting
S A
Spring
2
IO
1
Fig. 3.18 Phasor Dia. for Induction Type Overcurrent Relay
Electrical Power System – II 3.28 Protective relaying
1
2
Fig. 3.18 represents the vector diagram of the circuit. IO is exciting current of the
relay. IS is secondary current referred to primary and I represents total primary current. The
phase angle between 1 and 2 is α. When the current I is more than required set value, the
disc rotates to close the trip circuit terminals.
D] Shaded Pole Structure:
The arrangement of a shaded pole induction type over current relay is represented
in fig. 3.19 It consists of a pivoted aluminium disc, which is free to rotate in the air gap of
the electromagnet. Some portion of the poles (which is nearly ⅓ of pole area) is surround-
ed by copper bands known as shading rings.
Electrical Power System – II 3.29 Protective relaying
2
2
Shading 1 Disc
band To trip circuit
I
Alternating flux 1 in the unshaded portion will cause induced currents in shading
ring and set up flux 2, fluxes 1 and 2 are displaced from each other, causing induced ed-
dy currents i1 and i2 in the disc. The action is to set up a torque on the disc, which will ro-
tate at set value of current I.
E] Overload Inverse Time Relay:
Fig. 3.20 represents the details of a overload inverse time relay. It essentially con-
sists of the mechanism as that of the over current relay, but it is modified to give the in-
verse time characteristic.
On the upper ‘E’ type electromagnet, two windings are provided. One is primary
and other is secondary. The primary is connected to C.T. secondary of the power transmis-
sion line, which is under protection. It is provided with tappings, which are connected to a
plug setting bridge. It is used for setting of operating current of relay. The secondary wind-
ing is wound on the lower part of ‘E’ upper magnet and it is spread over the two limbs of
the lower ‘U’ type magnet. By this method, the flux from the upper magnet entering the
disc is displaced from the flux of the lower magnet entering the disc. The interaction pro-
duces torque on the disc. The spindle of the disc carries the moving contacts, which bridges
two fixed contacts after the disc has rotated through a certain angle. The angle may vary
from 0 to 360°C.
The speed of disc is dependent upon the current. When the current flowing through
the primary winding is more for same setting, speed of rotation increases, and operating
time is reduced, the reverse is also true. Thus, the time current characteristic of the relay
follows the inverse-square law. The definite minimum time characteristic of the relay is
obtained by use of saturated upper magnet i.e. at a particular value of primary current the
core becomes saturated, and further increase in value of this current will not increase flux
and therefore speed of disc does not increase. Hence, it takes specified minimum time for
Electrical Power System – II 3.30 Protective relaying
the operation of the relay. That is why it is also called as inverse definite minimum time lag
(IDMT) relay.
T T
Trip circuit
terminals
Trip contact
Disc
Plug
setting
bridge
Permanent
magnet N S
Coil
Figure 3.21
4.11Permanent Magnet Moving Coil Type Relay
Trip
S N circuit
contacts
Axially supported
coil
Figure 4.12
3.22 PMMC Relay
Fig. 3.22 represents another type of moving coil P.M. relay. The coil is supported
axially and moves horizontally when current is passed through it. These relays are faster
than moving coil, because of small travel and light parts. The operating time of the order of
30 m sec can be obtained, the VA burden is low, and the sensitivity can be as low as 0.1
milli-watt. They are very delicate for use.
The current rating of a protective relay is generally 5A or 1A. But, the primary cir-
cuit currents are of higher magnitudes. It is quite obvious that these heavy currents in an
element of a power system must be reduced to lower values suitable for relay operation.
This is achieved with the help of ‘Current Transformers’. C. T’s are also used for instru-
mentation i.e. in measurement. The C. T’s used for protection are known as protective or
protection C. T’s.
A.C.T. isolates the secondary circuit (the relay circuit) from the primary circuits
(power circuit) and provides currents in the relay, which are proportional to these in power
circuits. The primary winding of the C.T. is connected in series with the load and therefore,
it carries the actual power system currents (normal or fault).
The secondary circuit of a C.T. must on no account be opened while its primary is
carrying a current, since all the primary ampere-turns would then be available to produce
flux. The iron loss due to the high flux density would cause excessive heating of the core
and the windings. A high e.m.f. could be induced in the secondary winding. Hence if it is
desired to remove the ammeter or protective relay from the secondary circuit, the second-
ary winding must first be short-circuited.
1] C. T. construction:
There are two types of construction of C.T. and hence classified as:
i] Bar Primary C.T. and ii] Wound Primary C.T.
2] Requirements of C.T.’s for protection:
Electrical Power System – II 3.33 Protective relaying
The requirements of protection C.T.s are quite different from those of measuring
C.T.s. The C.T.s used with measuring instruments are required to be accurate over the
I1
To Load
P
Laminated Secondary
core winding
Wound
primary
Secondary P
S
Bar as primary
winding
I2
Laminated iron core
Relay Relay
Figure 3.16 (a) Wound primary C.T. Figure 3.16 (b) Bar C. T.
P1 P2
Secondary
Primary
(Line conductor)
Ring type
core
S2
S1
Figure 3.16 (c) Symbol of a C.T. Figure 3.16 (d) Outdoor high voltage C. T.
normal working range of currents, whereas the C.T.s used for protection purpose are re-
quired to give a correct ratio upto many times the rated primary currents, since the relay
has to work reliably at normal currents as well as fault currents. Its accuracy is not im-
portant for many applications, at currents less than the rated value.
3] Core material:
The C.T. is similar in operation to any other transformer, and therefore its primary
current also consists of two components, namely the exciting (magnetising current) which
magnetises the core and the secondary current which is transformed in the inverse ratio of
the turns ratio. The exciting current is not transformed and, therefore, is the cause of the
transformer errors. Because of this reason, certain values of secondary currents could never
Electrical Power System – II 3.34 Protective relaying
be produced whatever the value of primary current. This happens when the C.T. core satu-
rates.
The general shape of a C.T. magnetisation curve is shown in fig. 3.23. The shape of
the characteristic is different for different core materials. The curve is divided into three
regions, by the ankle point and the knee point as shown in the fig.3.24.
The knee point marks the boundary between the saturated and unsaturated regions.
10% Increment
Secondary voltage
50% Increment
Knee point
Ankle point
Figure3.24
3.17 C. T. Magnetising Characteristics
4] Knee point:
The knee point is defined as the point on the magnetisation curve at which a 10%
increase in secondary voltage produces a 50% increase in exciting current. The working
range of a protection C.T. extends over the full range between the ankle point and the knee
point and beyond that. The measuring C.T. usually operates in the region of the ankle
point. This is because of the radical difference in their basic functions. Measuring CT. re-
quires comparatively high accuracy over the range of 10% to 120% rated current, and it is
an advantage if the measuring C.T. saturates for currents above this range in order to pro-
tect the measuring instruments.
Protection C.T. on the other hand, requires linear characteristic upto the secondary
voltage corresponding to maximum fault current in the connected burden.
Fig. 3.25 shows the characteristics for protection C.T. and measuring C.T. for the
same rated burden.
Electrical Power System – II 3.35 Protective relaying
Measuring C.T.
It is obvious that a core of longer cross sectional area would be required for protec-
tion C.T. if the material has to be the same. Grain oriented steels having high saturation
levels are used as core materials for protection C.T.’s and nickel-iron alloys having low
exciting amp-turns per unit length of the core are used for the CT.’s for measurement and
the knee point occurs at a relatively low flux densities.
5] C.T. burden:
The burden on the C.T. is defined as the load connected across its secondary termi-
nals, expressed in volt-amperes (VA). It can also be expressed in terms of impedance at the
rated secondary current at a given power factor. Rated burdens of C.T.’s refer to the maxi-
mum load in volt-amperes (VA) which can be applied across the secondary terminals,
without the ratio and phase angle errors exceeding the permissible limits.
6] Accuracy class:
It is the accuracy class assigned to the current transformer with the specified limits
of the ratio error and phase angle error.
The accuracy classes are as under.
5P 1 60 5
Electrical Power System – II 3.36 Protective relaying
10 P 3 - 10
15 P 5 - 15
The C.T.’s are marked, for example, as 30/5P 10, where first number indicates out-
put in VA (e.g. 30), second number indicates accuracy class (e.g. 5P) and last number indi-
cates composite error (e.g. 10).
7] Linear coupler:
An iron-cored C.T. has the limitation of magnetic saturation and owing to D.C. off-
set transient component present in the fault current, the stability on heavy through faults
may be difficult to obtain.
If the C.T. core is made of non-ferrous material, usually air or plastic, the problem
of saturation and D.C. offset transients are overcome. An air cored C.T. has a linear charac-
teristic and is called a linear coupler. Such C.T.s have no saturation limits and hence no ra-
tio and phase angle errors which arise due to saturation.
A C.T. with a small air gap in its iron core is also having linear characteristic, and
no errors such a C.T. is called as transactor.
B ] Potential or Voltage Transformers for Protection:
The voltage rating of a protective relay is 110 V. It is not possible to connect the
voltage coils of the protective devices directly to high voltage systems. It is therefore nec-
essary to reduce/ step down the voltage and to insulate the protective equipment from the
power circuit. This is achieved with the help of a potential transformer (PT). It is also
called as voltage transformer (VT). Thus, potential transformers are used to reduce the
power system voltage to lower values which suit the ratings of protective relays.
Ideally, a PT should produce a secondary voltage exactly proportional to the prima-
ry voltage and exactly in phase opposition. Practically, this is not achieved due to the volt-
age drops in the primary and secondary coils. Therefore, ratio error and phase angle errors
are introduced.
A] P.T. construction:
There are two types of construction for P.T.’s as: Conventional wound type PT and
the capacitor PT.
1] Wound type or electromagnetic type:
In this, primary and secondary are wound on magnetic core similar to usual trans-
former. The wound type P.T. is conveniently used for system voltages upto or below 132
kV for economic reasons.
Electrical Power System – II 3.37 Protective relaying
VC1 C1
Line voltage
VC2 V Output
C2
Bus-Bar S/S A
C.B.
1
CT1 IC1
2
Relay
1
CT2 IC2
2
C.B. Ir = IC1-IC2
Bus-Bar S/S B
Figure 4.15
3.28 Voltage Differential Relay
Two C. T.’ S. of same current ratio are connected across two ends of the alternator
winding. A relay R is connected in series with the two C. T.’ S when the load current at two
ends of the circuit being protected is same, and then there will be no voltage drop across
the relay to cause any current to flow in the relay. When the fault occurs voltage balance is
disturbed and current flows through relay R, causing closing of trip circuit contacts of C.B.
C] Biased Beam Or Percentage Differential Relay:
The relays explained uptill now have disadvantage that a small difference in the
C.T. ratio of the two C. T.’ s may cause erroneous operation of relay when their primaries
carry through heavy fault currents. The faulty operation can be avoided by using percent-
age differential relay.
Fig, 3.29(a) represents the general scheme of this type of relay, the operating coil of
I + I2
this relay carry current I1 - I2 and restraining coil carries current 1 . The restraining
2
CT1 Alternator winding CT2
I
Trip
Restraining coil circuit
Operating
coil
Figure 4.16
3.29 (a) Percentage Differential Relay
Electrical Power System – II 3.40 Protective relaying
coil does not allow the relay to operate when primary carries large through fault currents. A
mechanical biasing is provided with the help of beam for obtaining a certain current setting
for operation, when there is a current only in one C.T.
Fig. 3.29 (b) represents a simplified circuit of this type of relay.
CT1 CT2
I Alternator
winding
Operating
coil
Restraining coil
Figure 4.16
3.29 (b) Simplified Diagram for Percentage Differential Relay
A A’
1 1’
3 2 2’
3 3’ 3’
C C’
Disc
4’
4
P
B
B’
P’
Pilot wires
Figure 4.17
3.30 Translay Relay
Electrical Power System – II 3.41 Protective relaying
There are two types of distance relays in use for the protection of power supply sys-
tem, namely.
a] Definite distance relay.
b] Time distance relay.
A ] Definite Distance Relay:
Beam
Relay
contacts
F
To trip circuit
Armature
V I
Figure3.31
4.18 Distance Relay
Fig. 3.31 represents the schematic arrangement of a definite distance type impedance relay.
It consists of a pivoted beam, pivoted at F; two electromagnets, which are
energised respectively by a current, and voltage transformer in the protected circuit i.e. cur-
rent proportional to circuit current flows through coil of one magnet and current propor-
tional to voltage of circuit flows through coil of other magnet. The armatures of the two
electromagnets are mechanically coupled to the beam on the opposite sides of the fulcrum.
To the beam is fixed bridging piece for closing the trip contacts. The torque produced by
the two coils act in opposite direction.
At normal working condition, the force due to voltage coil on its armature (plunger)
is greater than that of the current coil. Hence, the relay contacts remain open. When fault
occurs voltage applied to the relay decreases3.32 where as current flowing through the other
coil increases the ratio of voltage to current falls below the set value, hence the force of the
current coil on its plunger becomes more than the pull of voltage coil on its plunger the
result is that beam tilts, closing the trip circuit contacts of the C.B.
The pull of the current element is proportional to I2, and that of voltage element to
V2, hence the relay will operate, when
Electrical Power System – II 3.43 Protective relaying
K1 V 2 < K 2 I2
V2 K2
or 2 <
I K1
V K2
or <
I K1
K2
i.e. Z <
K1
The value of constants K1 and K2 depends up on the turns of coils. Hence, the set-
ting of such relays can be changed by using suitable taps on the two coils.
These relays work on electromagnetic action.
B] Time Distance Impedance Relay (Induction Type):
The time distance relay is a relay which works on the principle of electromagnetic
induction and adjusts its operating time according to the distance of the relay from the fault
point.
Fig. 3.32 represents the schematic arrangement of a typical induction type, time
distance impedance relay. It consists of a double- winding type induction over current ele-
ment.
The spindle of this relay which carries the disc, is connected by means of a spiral
spring, coupled to a second spindle, which carries the bridging strip of the relay contacts.
The bridge is normally held in open position by an armature held against the pole
face of an electromagnet excited by the voltage of the circuit to be protected.
To trip circuit
From P.T.
Voltage
excited Spiral
Electrical Power System – II 3.44 Protective relaying
Under normal conditions, the pull of the armature is more than that of the induction
element, keeping the trip circuit contacts open. On the occurrence of fault, the disc of in-
duction over current relay starts to rotate at a speed depending upon the operating current.
As the rotation of the disc continues, the spiral spring is wound up until the tension of the
spring is sufficient to pull the armature away from the pole face of the voltage excited
magnet. Immediately the spindle carrying the armature and bridging piece moves rapidly
in response to the tension of the spring and closes the trip contacts of the circuit breaker.
Electrical Power System – II 3.45 Protective relaying
The time of operation of the relay is directly proportional to the pull of the voltage
excited magnet, and the speed depends upon the operating current, hence time of V opera-
tion of the relay varies as V/I i.e. as Z or distance.
3.13 OTHER RELAYS
In study of other relays, we will briefly study the construction and working princi-
ple of following relays
a] Directional power relay b] Directional overcurrent and earth fault relay.
c] Negative phase sequence relay.
Potential coil
3.33
1
Disc
Current coil
2
From C.T.
Figure3.33
4.20 (i) Induction Type Directional Power Relay
V
2
1
Figure3.33
4.20 (ii) Phasor Diagram
2, produced by it will be almost in phase with it, as shown in vector diagram. The driving
torque T on the disc will be given by
T 1 2 sin
or T V I sin(90 – )
When the phase angle, becomes more than 90°C, the power reverses, and the relay
closes the trip circuit contacts of circuit breaker.
These relays are used for controlling the reverse power of synchronous machines,
they are not used as directional protective relays under short-circuit conditions, because
under such conditions the voltage drops and the sensitivity of the relay drops.
B ] Directional Over current and Earth Fault Relay:
Fig. 3.34 represents schematic arrangement of a directional over current and earth
fault relay. It essentially consists of a combination of over current relay (non-directional
type) and a directional power relay.
In normal working condition the disc of the directional power relay does not move,
but the moment there takes place a reversal of current or power the disc of the directional
power relay will start rotating, which closes the contacts of the secondary winding of the
over current relay or earth fault element due to over current a torque is produced in the
disc, causing its rotation, which closes the contacts of the trip circuit of C.B., enabling the
circuit breaker to operate and isolate the supply.
Electrical Power System – II 3.47 Protective relaying
Directional
element
Voltage
Current
Disc
R Y B
IR IR’
1
2
IY 3
Disc To trip
circuit
IB
IY
30
30 30
IY IR IR’ IR’
(A)
Current in R and Y
phases in the secondary
side of C.Ts.
Figure 4.23
3.36 Positive Phase Sequence Currents
The currents IR and IY flow in opposite direction through the primary winding of
‘E’ type magnet due to auxiliary transformer construction, they are made equal in
magnitude hence as represented in fig. 3.36 the magnitude of current in the winding is
zero, hence the relay will not operate.
3.14 NEGATIVE PHASE SEQUENCE CURRENT:
When the as symmetrical fault occurs, unbalanced currents in phases are resulting
into negative phase sequence component. The vector diagram of current under such asym-
metrical fault condition is shown in figure 3.37
Electrical Power System – II 3.49 Protective relaying
IY
IR IR’ IR’ IY
C. T. secondary Auxiliary transformer Current in the primary
currents output currents winding of relay
From the vector diagram, it is clear that there will be a resultant current through the
winding and when its magnitude is more than the relay setting, the relay will operate and
close the trip circuit of the circuit breaker.
3.15 STATIC RELAY:
The static relay is a relay without any moving parts except in the slave device. It is
a combination of various devices. Its out put device can be electric, semiconductor or even
electromagnetic. The out put device is a tripping mechanism. The trip coil of circuit
breaker can be directly corrected to out put device.
Following is the block diagram of a static relay.
D. C. supply
Transducer or Trip
secondary of CT circuit
The rectifier receives A.C. signal from transducer or secondary of C.T. It rectifies
A. C. signal into D.C. and feeds it to relay measuring unit. Relay measuring unit consists
of :
Electrical Power System – II 3.50 Protective relaying
a] Comparator
b] Level detector
c] Filter and
d] Voltage stabilizer.
The output of the relay measuring unit is amplified by amplifier. The amplified
output is feed to output device which actuates the trip circuit.
Since all devices except output device are of either semiconductor type, their
speeds of operation are fast. Hence static relays are faster in operation than electromagnetic
relays.
Comparison between static relay and electro magnetic relay.
Advantages
3 Various characteristics for static relay can Relatively less number of characteristics
be obtained. Hence, selectivity, stability are obtained in electromagnetic relays.
and adequateness can be achieved.
4 Resetting time and overshoots time are Resulting time of electromagnet is still
very small for static relays very small. However, overshoots time is
relatively large.
5 Static relays are compact and hence they Electromagnetic relays need compara-
need less space. tively more space.
7 Its operation is also almost free from vi- Its operation can be badly affected by
brations and shocks. vibrations and shocks.
Disadvantages
Electrical Power System – II 3.51 Protective relaying
2 Static relays are more sensitive to voltage Electromagnetic relays are less sensitive
transients than electromagnetic relays to voltage transients.
3 The characteristics of static relay are bad- These relays are less sensitive to varia-
ly affected by variation in ambient tem- tion in ambient temperature
peratures.
4 Static relays are costlier than equivalent Electromagnetic relays are cheaper than
electromagnetic relays. equivalent static relays
R Y B
To trip D
circuit Micro- A
processor T
C. B. A
R
CT E
A/D con- Q
verter U
CT Signal
E
Processing
S
T
and
display
Time mul-
tiplier
Plug set-
ting
Data log-
ger
➢ Electromagnetic relay
➢ Thermal relay
➢ µP based and static relay
➢ Induction type relay
❖ Static relay
The static relay is a relay without any moving parts except in the slave device. It is a com-
bination of various devices. Its out put device can be electric, semiconductor or even elec-
tromagnetic. The out put device is a tripping mechanism. The trip coil of circuit breaker
can be directly corrected to out put device.
Following is the block diagram of a static relay.
D. C. supply
Transducer or Trip
secondary of CT circuit
QUESTIONS
Q.1 What do you understand by time multiplier setting?
Q.4 Describe the construction and principle of operation of an induction type disc relay.
Electrical Power System – II 3.55 Protective relaying
Q.5 The current rating of an over current relay is 5A, current setting is at 200 %, TSM =
0.4 C.T ratio = 400/5, fault current = 4000A.
Determine the operating time of the relay. Use the following table of operating at various
PSM at TMS =1
PSM 2 4 8 20
1] Relay
2] Pick-up value
3] Protective relay
Q.10 Describe with the help of neat diagram the construction and operation of induction
type over current relay.
Q.11 What is the difference between an over current relay and an earth fault relay?
Electrical Power System – II 3.56 Protective relaying
Q.13 Explain the basic difference between a C.T. used for protection and a C.T. used for
measurement.
Q.20 State the various accuracy classes of current transformers as per IS.
Q.21 What are the markings on primary and secondary terminals of C.T.s?
Q.25 Define:
1] Sensitivity
2] Selectivity
Electrical Power System – II 3.57 Protective relaying
3] Stability
4] Discrimination
5] Reliability
Q.26 Define
1] Pick-up value
3] Instantaneous relay.
4] Distance relay.
5] Impedance relay.
Q.27 Draw neat sketch and explain working principle of an induction type overcurrent re-
lay.
Q.29 Explain how an inverse definite minimum time characteristic is obtained in case of
over load relay.
Q.30 What are the advantages and disadvantages of a moving coil permanent magnet type
relay over a plunger type relay?
Q.31 Draw a neat sketch and explain the working of a biased beam percentage differential
relay.
Electrical Power System – II 3.58 Protective relaying
Q.32 On what principle does the Translay relay work? Draw a neat sketch and explain its
working.
Q.33 What is the meaning of distance relay? Explain the working principle of balanced
beam type distance relay.
Q.34 Draw neat sketch and explain working principle of induction type impedance relay.
Q.36 Draw a neat sketch and explain the directional overcurrent and earth fault relay.
Q.38 Draw a neat sketch of microprocessor based inverse time overcurrent relay. Explain
its working.