PVC Insulated Single Core Internal Sales


35mm2 PVC Building Wire Black 100m Phone: 1300 CABLES
[email protected]

Nexans Ref.: BAAC18A1001AABK


Country Ref.: BAAC18A1001AABK
EAN 13: 9319215263805

35mm2 PVC Building Wire Black

DESCRIPTION
Single Core Building Wires

• Single core,
• 0.6/1kV V-90 insulated,
• to AS/NZS 5000.1 (unsheathed),
• Copper conductors, 90°C.
STANDARDS
National AS/NZS 1125; AS/
NZS 5000.1

Conductor flexibility Rated Voltage Uo/U (Um) Cable flexibility


Class 2 0,6/1 kV Rigid

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 22/8/24 www.nexans.com.au Page 1 / 3
Contact
PVC Insulated Single Core Internal Sales
35mm2 PVC Building Wire Black 100m Phone: 1300 CABLES
[email protected]

CHARACTERISTICS
Construction characteristics
Colour Black
Conductor flexibility Class 2
Conductor material Copper
Conductor shape Circular
Insulation V-90
Type of conductor Compact copper
With Green/Yellow core No
Dimensional characteristics
Approximate weight 35.0 kg/100m
Cable length 100 m
Conductor cross-section 35 mm²
Neutral conductor section (when smaller) - mm²
Nominal insulation thickness 1.2 mm
Nominal overall diameter 9.4 mm
Number of cores 1
Electrical characteristics
Conductor AC resistance at 50 Hz 0.638 Ohm/km
Inductive reactance at 50Hz - flat touching 0.117 Ohm/km
Inductive reactance at 50Hz - trefoil 0.101 Ohm/km
Insulation resistance at 20°C 5.2 MOhm.km
Max. DC resistance of the conductor at 20°C 0.524 Ohm/km
Rated Voltage Uo/U (Um) 0,6/1 kV
Mechanical characteristics
Cable flexibility Rigid
Maximum Pulling Tension 2.5 kN
Usage characteristics
Minimum Bend Radius - During Installation (under 110 mm
Tension)
Minimum Bend Radius - Installed 75 mm

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 22/8/24 www.nexans.com.au Page 2 / 3
Contact
PVC Insulated Single Core Internal Sales
35mm2 PVC Building Wire Black 100m Phone: 1300 CABLES
[email protected]

PVC INSULATED - CURRENT CARRYING CAPACITY TABLE SINGLE PHASE (IN


AMPS)
Copper Conductor Insulation PVC Maximum Conductor Temperature 75C

Conductor cross-section
[mm²] Cu Cu Cu Cu Cu Cu Cu Cu
35 153 145 119 112 90 59 139 155

Unenclosed spaced Unenclosed spaced from surface Unenclosed touching

Thermal insulation, partially Thermal Insulation, completely


Enclosed conduit in air
surrounded by thermal insulation surrounded by thermal insulation

Underground ducts A - Underground ducts B - Individual


Undergound Wiring Enclosure Wiring Enclosure

PVC INSULATED - CURRENT CARRYING CAPACITY TABLE THREE PHASE (IN


AMPS)
Copper Conductor Insulation PVC Maximum Conductor Temperature 75C

Conductor cross-section
[mm²] Cu Cu Cu Cu Cu Cu Cu Cu
35 148 127 119 100 80 59 122 140

Unenclosed spaced Unenclosed spaced from surface Unenclosed touching

Thermal insulation, partially Thermal Insulation, completely


Enclosed conduit in air
surrounded by thermal insulation surrounded by thermal insulation

Underground ducts A - Underground ducts B - Individual


Undergound Wiring Enclosure Wiring Enclosure

All drawings, designs, specifications, plans and particulars of weights, size and dimensions contained in the technical or commercial documentation of Nexans is
indicative only and shall not be binding on Nexans or be treated as constituting a representation on the part of Nexans.
Generated 22/8/24 www.nexans.com.au Page 3 / 3