Mpq1000 Ds Us
Mpq1000 Ds Us
Mpq1000 Ds Us
Automatic CT recognition
Automatic connection verification
On-board data analysis
SD card and USB stick support
1000 V ac and 1000 V dc range
Scope and DMM modes
CATIV @ 600 V
IEC61000-4-30 Class A compliant
APPLICATIONS Environmental
Operating: -20° C to 50° C (-4° F to 122° F)
Using experience gained from supplying a multitude of
Storage: -30° C to 60° C (-22° F to +140° F)
analyzers to a large number of utilities, industries and Relative humidity: 0-95% non-condensing
service providers, Megger has designed the most versatile Altitude <2000 m: 1000V CAT III / 600 V CAT IV
unit available today. Some of the applications include the Altitude 2000 m - 5000 m: 600 V CAT III / 300 V CAT IV
following:
Case
Compliance testing to any PQ standard IP54 enclosure
Kensington lock
Power factor studies
Display
Load studies and load balancing Backlit 11.5 cm x 8.5 cm color VGA
Resolution 5.56 pixels per mm (640 x 480 pixels, 115.2 x 86.4 mm)
Billing verification Refresh rate: 1-3 sec
Substation monitoring
PQ Events
Capacitor bank sizing Dips / sags: Triggers off of voltage and current. IEC61000-4-30
compliant.
Transformer analysis and de-rating Swells: Triggers off of voltage and current. IEC61000-4-30 Compliant
Sub-cycle distortions: Triggers off of voltage and current. IEC61000-4-
Motor troubleshooting and inrush testing 30 compliant.
Transient detection: 1 μsecond. Triggers off of first 3 voltage channels.
Switchgear and component failure IEC61000-4-30 compliant.
THD: Triggers off of voltage and current. IEC61000-4-30 Compliant
Tripping breakers
Rapid Voltage Change (RVC): Triggers off of first 3 voltage channels.
Equipment tripping offline IEC61000-4-30 compliant.
Phase shifts: Trigger event when a phase shift occurs between the
Dimming/surging lighting voltage channels. Record date and time, duration and waveforms of all
enabled channels. Phase shift user selectable down to 1 degree.
Lamp flicker analysis Waveform capture of events: Capture waveforms on all enabled
channels when an out of limits event occurs. Waveforms
Neutral overheating programmable with up to 9 pre-trigger cycles and 99 post-trigger
Solar (PV) analysis cycles.
Timed waveform capture: Captures waveforms periodically on all
enabled channels. Waveform capture interval programmable down
to 1 cycle. Programmable number of cycles to be captured up to 99
SPECIFICATIONS cycles.
Input Power Event triggered waveforms and timed triggered waveforms
120/240 V, 50/60 Hz simultaneously.
International power adapter supports US, UK, EU and Australian plugs Mains signaling events: Two selectable frequencies and amplitudes.
Selectable time interval. Measured per IEC61000-4-30.
Battery Captures waveforms on all enabled channels when a mains signaling
NiMH battery pack (field replaceable) event occurs. Waveform programmable with up to 9 pre-trigger cycles
Discharge time – up to 8 hours and 99 post-trigger cycles.
Recharge time – 3 hours Event Flagging: Measured per IEC61000-4-30.
Sampling
Resolution: 16 bit analog to digital converter on 8 channels
Max sampling speed: 1 MHz max
Max RMS sampling: 17,664 per channel max
PLL synchronization: 42.5 Hz to 69 Hz
Trended Parameters
Voltage
4 voltage channels
Voltage range: 0 to 1000 V range AC RMS DC
Measures AC & DC simultaneously (common neutral required)
Voltage accuracy: 0.1% per IEC61000-4-30
Voltage ratios: Adjustable voltage ratios for measuring
secondaries. (.0001 through 9999)
Resolution: 16 bit
Crest factor: 1.5
Max pk voltage: 1628 V / 2500 V
Voltage lead set: 5 voltage leads, 6 ft (2 m) in length. Safety banana
leads. Removable alligator clips. Optional plunger
clips. Set of color bands for customizing color
codes. Safety green/yellow ground lead included.
Fused adapter: In line with voltage leads to provide fuse
protection (optional).
MPQ1000
Handheld Power Quality Analyzer
OPTIONAL ACCESSORIES Split Core Current Clamp Split Core Current Clamp
1000 A Available options:
CP-1000WCE-ID 1000 A split core CT (CP-1000WCE-ID)
100 A (CP-100CE-ID)
20 A (CP-100CE-ID)
CP-100CE-ID 100 A split core CT 5 A (CP-5CE-ID)
These flexible rain tight CTs have four current ranges that are all
self-identifying.
The current clamps are powered from the MPQ1000 Analyzer and
come in three different diameters (18 cm, 27 cm, and 37 cm). Hall Effect Current Clamp
600 A dc and 400 A ac
Ranges include 60 A, 600 A, 3000 A and 6000 A. (CP-600DC-ID)
Includes: 5 voltage leads and 1 ground lead. MCCV Rain Tight Flexible
Current Clamps
Range = 0 to 1000 V ac/dc Available diameters:
18 cm (MCCV6000-18)
Multiple colar straps. Configure your voltage leads for the required 27 cm (MCCV6000-27)
color code. 37 cm (MCCV6000-37)
CAT IV @ 600 V
ACCESSORY KITS
ORDERING INFORMATION
Item (Qty) Cat. No. Item (Qty) Cat. No.
MPQ1000 8 channel 3-phase power MPQ1000 Optional Accessories
quality analyzer
Fused adapter kit (3 adapters and fuses) 1008-645
*MPQ1000 basic kit MPQ1000-BASIC
Kit of 4 plunger clips 1008-756
*MPQ1000 silver kit MPQ1000-S-KIT
Instrument strap 2009-205
*MPQ1000 silver plus kit MPQ1000-S-KIT-PLUS
Power quality simulator MPQ-SIM-01
*MPQ1000 gold kit MPQ1000-G-KIT
Current Clamps
*MPQ1000 gold plus kit MPQ1000-G-KIT-PLUS
Four range 6000 A AC rain tight, MCCV6000-18
*MPQ1000 platinum kit MPQ1000-P-KIT self-identifying, flexible rope current
*MPQ1000 platinum plus kit MPQ1000-P-KIT-PLUS clamps (18 cm ID)
Four range 6000 A AC rain tight, MCCV6000-27
*See description of Kit contents on
self-identifying, flexible rope current
previous pages
clamps (27 cm ID)
Included Accessories
Four range 6000 A AC rain tight, MCCV6000-37
Unfused voltage lead kit 2007-259 self-identifying, flexible rope current
32 GB SD card 90023-619 clamps (37 cm ID)
USB memory stick: contains MPQ user 1009-697 1000 A AC split core current, self- CP-1000WCE-ID
guide, Megger PQ PC software and identifying current clamps (50 mm ID)
Megger PQ PC software user guide 1-100 A AC split core current, self- MCP-100CE-ID
USB communications cable CA-USB identifying mini current clamps (20
mm ID)
Ethernet communications cable 36798
20 A AC split core current, self- CP-20CE-ID
Soft sided case 2007-626-1 identifying current clamps (20 mm ID)
Universal 24 Vdc power adapter 90011-992 5 A AC split core current self- CP-5CE-ID
Battery pack 2008-369 identifying current clamps (20 mm ID)
AC/DC 600 A hall effect current self- CP-600DC-ID
identifying wide band current clamps
(50 mm ID)
DC 100A / 1000 A hall effect current MCP-1000DC-ID
self-identifying current clamps (50 mm
ID) No batteries required.
**Kit of 4 split core self ID 1000A PQ CP-1000WCE-ID-KIT
CT
**Kit of 4 split core self ID 20A PQ CT CP-20CE-ID-KIT
**Kit of 4 split core self ID 5A PQ CT CP-5CE-ID-KIT
**Kit of 4 split core self ID 1-100A MCP-100CE-ID-KIT
Mini CT’s
**Kit of 3 split core self ID 600A (AC/ CP-600DC-ID-KIT
DC)PQ CT
**Kit of 4 hall effect self ID MCP-1000DC-ID-KIT
100 / 1000A (DC) PQ CT
**See description of Kit contents on
previous pages