ANew Power Swing Detection Schemefor
ANew Power Swing Detection Schemefor
net/publication/235697990
CITATIONS READS
5 869
3 authors:
Hussain Shareef
United Arab Emirates University
397 PUBLICATIONS 5,183 CITATIONS
SEE PROFILE
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Hussain Shareef on 11 June 2014.
θ = sin −1 (X T P2 E1 E2 ) (8)
Assuming that Pline << Qline equation (22) then is written as,
By using the Kirchoff Voltage Law , the voltage Vs can be
written as;
S s = jQline + Pload + jQload (23)
V s = Vline + Vload (17)
During a power swing, the load impedance is significantly
larger than the line impedance, that is,
Substituting (17) into (16), we get;
2
Z line << jZ load (24)
S s = Vline + Vload (Z line + Z load ) (18)
The simplified apparent power at the sending end, S s ' can be
written as
Then, the line impedance, Z line of the power system is be
represented as, 2
Ss ' = Vload Zload = Pload + jQload (25)
Z line = Rline + jX line (19)
Based on the above equation, the corresponding power system
The resistive component, Rline at transmission lines is very model during power swing is further simplified as shown in
Fig. 5.
small and hence it is neglected. Thus, equation (19) becomes,
2
Vline + Vload
Ss = (21)
jX line + Z load
where,
jQline = 0 (26)
2
Ss = Vline jX line (27)
V. TEST RESULTS
Fig. 6 The IEEE 39 bust test system
Large figures and tables may span both columns. Place The IEEE 39 bus test data are constructed based on PSS/E
figure captions below the figures; place table titles above the format raw data. The 39-bus system has 10 generators
tables. If your figure has two parts, include the labels “(a)” and GENROE and 10 exciter, ESDC1A type. The parameters of
“(b)” as part of the artwork. This section describes the generators GENROE and exciter, ESDC1A type are tabulated
simulations and tests that have been performed in order to in as shown Tables 1 and 2, respectively.
study the behavior of the proposed detector under power swing
conditions. The proposed detector is studied on the IEEE 39 TABLE 1
bus test system by using the commercial PSS/E software THE PARAMETERS OF GENERATORS GENROE
version 31. The test system consists of 10 generators 18 loads Parameter Value
and 36 lines as shown in Fig. 6.
T'do (> 0) 10.2
T''do (> 0) 0.03
T'qo (> 0) 1.5
T''qo (> 0) 0.04
Inertia H 4.2
Speed Damping D 0
Xd 1
Xq 0.69
X'd 0.31
X'q 0.31
X''d = X''q 0.2
Xl 0.125
S(1.0) 0
S(1.2) 0
version of the file IEEE39bus_converted.sav is used for
TABLE 2 performing dynamic stability studies.
THE PARAMETERS OF EXCITER, ESDC1A TYPE
Parameter Value TABLE 3
SET OF PSS/E FILES TO CARRY OUT LOAD FLOW AND DYNAMIC
TR 0
SIMULATION
KA 5
File Name Description
TA 0.06
Base case
TB 0
IEEE39bus.raw input data
TC 0 file
VRMAX or zero 5
Main load
VRMIN -5
IEEE39bus_unconverted.sav flow solved
KE or zero -0.05 case
TE (> 0) 0.25
KF 0.04 Single line
diagram
TF1 (> 0) 1 IEEE39bus.sld
drawing
0. Switch 0 datafile
E1 1.7
Base case
SE(E1) 0.5
IEEE39_stability.dyr Dynamic
E2 3 data file
SE(E2) 2
Converted
saved case
file with
A. Simulation Procedure IEEE39_converted.sav
loads and
The dynamic simulation of a power system s using PSS/E generators
software has three basic steps: converted
B. Results of ldθ/dtl
One of the fast detectors used to discriminate a fault and a
power swing employs the use of negative sequence current
magnitude and the magnitude of derivative of current angle,
ldθ/dtl [4]. However, identical values of ldθ/dtl may appear
during fault and fault clearance as the increment of current
angle is very substantial in both situations. The results in Fig. 9
and 10 show clearly the ldθ/dtl values of the affected relay
during fault, fault clearance and power swing for the case.
From Fig. 7, it is clearly observed that the first fault has been
created at 1 second until 1.15 second which causes a power
swing to appear after the fault clearance. Subsequently, a
second fault which is located at 200% away of the relay
boundary has been created at 3 second. During the simulation,
the apparent impedance, Za seen by the distance relay at bus 6
is very low during the fault and power swing conditions. The
apparent impedance or impedance trajectory enters the relay
operating zone at both situations as shown in Fig. 8.
Once the apparent impedance, Za enters the relay operating Fig. 9 Result of ldθ/dtl
zone, the distance relay may send the trip signals to the
breaker to clear the fault. However, during power swing, the
trip signals should be blocked to avoid false tripping. The As can be seen from Fig. 9, the range of ldθ/dtl is
proposed additional detection criteria is then introduced in approximately between 2,100 degree/second to 9,500 degree/
distance relay in order to avoid such undesirable relay second during the fault. The results of ldθ/dtl values during
operation. power swing are depicted in Fig. 10, where the value of ldθ/dtl
is between 9 degree/second to 45 degree/second.
[4] M. Jonsson and J. Daalder, A New Protection Scheme to Prevent Mal-
Trips Due to Power Swings, IEEE/PES Transmission and Distrib. Conf.
and Expo., Vol. 2, 2001, pp. 724 – 729.
[5] X.Lin, Y. Gao and P.Liu, , A Fast Unblocking Scheme for Distance
Protection to Identify Symmetrical Fault Occurring During Power
Swings, IEEE Trans. on Power Del., Vol 1, 2008, pp. 73-77.
[6] B. Su,. X. Z. .Dong, Z.Q.Bo, Y.Z.Sun, B.R.J Caunce, D.Tholomier and
A.Apostolov, Fast Detector of Symmetrical Fault During Power Swing
for Distance Relay, IEEE Power Eng. Soc. Gen. Meet., Vol. 2, 2005,
pp.1836 – 1841.
[7] L.Xiangning, Z.Qing, L.Wenjun, W.Kecheng and W. Hanli, A Fast
Unblocking Scheme for Distance Protection to Identify Symmetrical
Fault Occurring During Power Swings, IEEE Power Eng. Soc. Gen.
Meet., 2006, pp.1-8.
[8] H. K. Zadeh and Z. Li, A Novel Power Swing Blocking Scheme Using
Adaptive Neuro-Fuzzy Inference System, Electr. Power Syst. Research
J., 2008, vol. 78, pp. 1138-1146.
[9] P. M. Fonte and J. C. Quadrado, Stability Modelling of WECS for
Power Generation, WSEAS Trans. on Circuit and Syst., 2005, vol. 3, pp.
1591-1596.
[10] S. Jalilzadeh and S.Jadid, Improvement of transient stability by
variation generator parameters and high speed fault clearing, WSEAS
Fig. 10 Result of ldθ/dtl (enlarge)
Trans. on Syst., 2005, vol. 4, pp. 609-616
[11] V.G. Parkash, C. P. Singh and R. Dahiya, Transient Stability
The results from both figures prove that the ldθ/dtl is very Improvement of SMIB With Unified Power Flow Controller, 2nd
promising in distinguishing between a fault and a power swing. WSEAS Int. Conf. on Circuits, Systs., Signal and Telecommun.
(CISST'08), 2008, pp. 1155-1149.
However, it can be noted that the ldθ/dtl values are not suitable [12] N. M. Hanoon, B.P.Kartik and O.M.Ahtiwash, A Neuro-Control
to differentiate between fault and fault clearance as shown in Approach for Flexible AC Transmission Systems, , WSEAS Trans. on
Fig. 9. From the figure, it can be deduced that, the value of Syst., 2004, vol. 3, pp. 964-968
ldθ/dtl is apparently in similar range for fault and fault
Ahmad Farid Bin Abidin received the B.E.E.S degree from University
clearance. The distance relay installed in these lines may send Kebangsaan Malaysia (UKM), Malaysia, in 2000 and M.S.E.E. from
false trip signals during fault clearance operation. Universiti Teknologi MARA (UiTM), Malaysia, in 2005. He is currently a
PhD student at the Department of Electrical, Electronic and System, UKM.
His research interests are in power system stability and power quality. He is a
student member of IEEE.
VI. CONCLUSION
The use of dQLine/dt has been proposed as a new detection
.Professor Azah Mohamed received her B.Sc from University of London in
technique to block the distance relay trip signals during power 1978 and M.Sc and Ph.D from Universiti Malaya in 1988 and 1995,
swing. Time domain simulations were first carried out under respectively. She is a professor at the Department of Electrical, Electronic and
the conditions of fault and power swing. The proposed Systems Engineering, Universiti Kebangsaan Malaysia. Her main research
interests are in power system security, power quality, artificial intelligence
detector has been tested to evaluate its effectiveness in and distributed generation. She is a senior member of IEEE
differentiating between a fault, power swing and fault
clearance. The results show that the dQLine/dt can effectively
.Hussain Shareef received his BSc with honours from IIT, Bangladesh, MS
differentiate the fault, fault clearance and power swing unlike
degree from METU, Turkey, and PhD degree from UTM, Malaysia, in 1999,
the use of ldθ/dtl. 2002 and 2007, respectively. He is currently a lecturer in the Department of
Electrical, Electronics, and Systems Engineering, Universiti Kebangsaan
Malaysia. His current research interests are power system deregulation, power
quality and power system distribution automation.
ACKNOWLEDGMENT
The authors gratefully acknowledge the Universiti
Teknologi MARA for financial support in terms of scholarship
and Universiti Kebangsaan Malaysia for financial support on
the project.
REFERENCES