Electrical Load Calculation
Electrical Load Calculation
Electrical Load Calculation
5 Refuge Floor / Stilt Park 0.2 1 0.2 1.5 0.1 0.1 0.1
10 Pressurization load Lift well 0.0 0.0 0.0 0.0 0.0 0.0
5 Refuge Floor / Stilt Park 0.3 1 0.3 1.5 0.2 0.2 0.2
10 Pressurization load Lift well 0.0 0.0 0.0 0.0 0.0 0.0
5 Refuge Floor / Stilt Park 0.3 1 0.3 1.5 0.2 0.2 0.2
10 Pressurization load Lift well 0.0 0.0 0.0 0.0 0.0 0.0
5 Refuge Floor / Stilt Park 0.3 1 0.3 1.5 0.2 0.2 0.2
10 Pressurization load Lift well 0.0 0.0 0.0 0.0 0.0 0.0
TOTAL COMMON AREA LOAD ( KW ) 21.6 14.4 14.4 8.7
5 Refuge Floor / Stilt Park 0.3 1 0.3 1.5 0.2 0.2 0.2
10 Pressurization load Lift well 0.0 0.0 0.0 0.0 0.0 0.0
5 Refuge Floor / Stilt Park 0.3 0.0 1.5 0.0 0.0 0.0
10 Pressurization load Lift well 0.0 0.0 0.0 0.0 0.0 0.0
5 Refuge Floor / Stilt Park 0.3 1 0.3 1.5 0.2 0.2 0.2
5 Refuge Floor / Stilt Park 0.3 1 0.3 1.5 0.2 0.2 0.2
10 Pressurization load Lift well 0.0 0.0 0.0 0.0 0.0 0.0
5 Refuge Floor / Stilt Park 0.3 1 0.3 1.5 0.2 0.2 0.2
10 Pressurization load Lift well 0.0 0.0 0.0 0.0 0.0 0.0
5 Refuge Floor / Stilt Park 0.6 1 0.6 1.5 0.4 0.4 0.4
10 Pressurization load Lift well 0.0 0.0 0.0 0.0 0.0 0.0
5 Refuge Floor / Stilt Park 0.3 1 0.3 1.5 0.2 0.2 0.2
10 Pressurization load Lift well 0.0 0.0 0.0 0.0 0.0 0.0
4 Club House - Swimming Pool 20.00 1 20.0 1.50 13.33 0.0 0.0
9 STP Transfer Pump test 10.00 1 10.0 1.50 6.67 6.7 0.0
13 External,Facade & Landscape lighting load 25.00 1 25.0 1.50 16.67 8.3 5.0
TOTAL LOAD OF COMMON INFRA UTILITY FOR BUILDINGS 237.5 158.3 124.2 36.7
BUILDCROWN MEP SERVICES CONSULTANT LLP.
B - 202, VIGHNAHARTA CHS.,
SECTOR 1, PLOT 7, KHANDESHWAR,
NEW PANVEL- 410206.
Report No: 1
Client: Evernest Developers
Date: 25/01/22
Architect: 07 Architects
Project: Taloje
1 Energy saving using LED light for Lift Lobby & Staircase
Diff Between 12W LED and 20W CFL Lighting Fixt 8 W which comes to 40 %
Diff Between 18W LED and 30W CFL Lighting Fixt 12 W which comes to 40 %
40 % of saving by using LED light as compare to
40%
CFL light
Energy saving using VFD for pumps, Basement
20%
2 ventilation and Lift with High Efficiency Motors
Energy saving using Automatic Timer operation Against Manual operation for External,Facade & Landscape &
3 Common Area Lighting
25% lights will be off for 8 hours 25%
25% lights will be off for 4 hours 25%
4 Energy saving using Low Loss Transformer as per ECBC Against Conventional Transformer
Low Loss 630kVA Transformer losses are 5.8kW
as per ECBC norms compare to Conventional 5%
Transformer whose losses are 6.1kW
5 Use of Solar Water Heater for -----Flats 100%
A Energy Saving Due to LED Lamp
1 Typical floor Passage Area Lighting & Power Load 95 40 57.1 38
2 Staircase Lighting Load 26 40 15.4 10
3 Terrace Lighting Load 1 40 0.8 1
4 Refuge Floor / Stilt 13 40 7.7 5
Common area Lighting & Power Load (80%
180 40 108.0 72
5 Lighting Load)_
6 External,Facade & Landscape lighting 100 40 60.0 40
D Energy saving due to Low Loss Transformer as per ECBC Against Conventional Transformer
1 04 nos.630 kVA transformer 4 5 3.8 0.2
Average KWH/Day saving 374
Average KWH/Annual saving 136346.48
Report: 01
Client: Evernest Developers Date : 25/01/22
Architect: 07 Architects
Project: Taloje
Total % of Average KWH/ Day Energy generated from Solar Water Heater with Actual Average
KWH/ Day Energy consumption of Geyser 100%
B. Energy Saving summary using Solar PV cells
Estimated Average KWH/ Day Energy consumption Without using Energy Saving Measures 943
Estimated Average KWH/day saving by using Energy Saving Measures 374
Actual Average KWH/ Day Energy consumption 569
Total no. of Solar PV Panel fit on Terrace area (Considering 325Wp each) 45
Total kWp from Solar PV Panel (Considering 325Wp each) 15
Total area required for Solar PV Panel on Terrace area in sq. Metres ( Considering 10 sq. Meter space for 1 145
kWp requirement )
Total Average KWH/ Day Energy generated from Solar PV Panel (As per Ministry of New & Renewable
73
Energy Solar Rooftop Calculator.)
Total % of Average KWH/ Day Energy generated from Solar PV Panel with Actual Average KWH/
Day Energy consumption 3%
SUMMARY FOR RENEWABLE ENERGY REQUIREMENT
Total no. of Solar Water Heater Panel required on Terrace area(Considering 100 liter panel ) 348
Total kWp from Solar PV Panel (Considering 250Wp each) 15
Total area required for Solar Water Heater & PV Panel on Terrace area in sq. Metres 1503
Total usable area available on Terrace area in sq. Mtrs