ATEX Detectors Control Distribution Units Zone 1 Zone 2 Heat Detector Ex D Ex em Ex Ia - Eaton HD1 Hazardous Area Control Distribution Units

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

HD1 Range - HEAT DETECTOR

EExd, EExem & Intrinsically Safe (Ex ia)

Features
4 Zone 0, Zone 1 and Zone 2 use.
4 ATEX certified.
EExd IIB T3/T6.
Exd IIC T6.
EExem II T4/T6.
Ex ia IIC T4/T6.
4 IECEx certified.
Ex ia IIC T4/T6 Ga.
4 UL listed for USA and Canada:
Class I, Div 2, Groups A-D.
4 CUTR certified.
4 Chinese (CQST) certified
4 Brazilian (Inmetro) certified.
4 SIL 2 certified.
4 IP66 & IP67.
4 Certified temperature: –20ºC to +125ºC (Exd)*.
–20ºC to +55ºC (Exem/UL).
–55ºC to +55ºC (Exia).
4 Stainless steel probe.
4 Detector temperature settings: 60ºC to 385ºC,
Introduction (140ºF to 725ºF).

The MEDC heat detector has been designed for use in hazardous 4 Marine grade alloy or GRP enclosure.
environments. These units are suitable for fire alarm and/or suppression 4 Optional Stainless Steel guard.
systems in offshore and onshore applications including paint spray booths,
flammable material stores, turbine rooms, extract ductwork and other
*Model dependent.
hazardous areas throughout the oil & gas, petrochemical and process
industries.

Comprising a Fenwal rate-compensated detector with all-stainless steel


external construction, mounted to either a type SM87 marine grade alloy
enclosure (Exd version) or JB10 corrosion-free GRP enclosure (Exia, Exem/
UL versions). The contact in the detector CLOSES at alarm
temperature.

To select appropriate temperature setting see specification on reverse.

Head Office. Head Office (USA)


Unit B, Sutton Parkway, Oddicroft Lane, Sutton in Ashfield 3413 North Sam Houston Parkway West,
NG17 5FB, UK. Suite 212, Houston, TX 77086, USA
Sales Enq. UK: +44 (0)1623 444 445 Sales Enq. USA: +1 (713) 937- 9772 E-Mail: [email protected] Web: www.medc.com
158
Certification and Specification
ATEX EEx d IIB: Cert. no. Baseefa03ATEX0447. Exd VERSION
Certified to: EN50014, EN50018, EN50281-1-1. CERTIFICATION
EXTERNAL EARTH
7.5±1 LABEL
Ex II 2 GD, EEx d IIB T6 (T3 @ 125ºC). OPTIONAL
GUARD

ATEX Ex d IIC: Cert. no. Baseefa08ATEX0320.


Certified to: EN60079-0, EN60079-1, EN61241-0, EN61241-1.

FIXING CENTRES
Ex II 2 GD, Ex d IIC T6, Ex tD A21 T85ºC (-20ºC to + 55ºC).

105.5±0.5
122±2
ATEX EEx em: Cert. no. Baseefa03ATEX0428.
Certified to: EN50014, EN50019, EN50028.
Ex II 2G, EEx em II T6 (-20ºC to + 55ºC).
ATEX Ex ia: Cert. no. Baseefa03ATEX0427.
Certified to: EN60079-0, EN60079-11. 37±2 FIXING HOLES
Ø9±0.5 - 4 POS.
105.5±0.5
FIXING CENTRES

Ex II 1G, Ex ia IIC T6 Ga (-55ºC to + 55ºC). (T4 with diodes/resistors). 87±1 110±2


122±2

IECEx Ex ia: Cert. no. BAS 13.0010.


Certified to: IEC60079-0, IEC60079-11. 225.5±3

Ex ia IIC T6 Ga (-55ºC to + 55ºC). (T4 with diodes/resistors).


UL: Listing no. E252920 – versions up to 450ºF. Exia / Exem / UL VERSIONS
Listing no. E254077 – versions from 600ºF to 725ºF.
UL for USA and Canada, listed to Class 1, Div 2. Groups A – D. 130±2
88.5±2

CUTR: 1Ex d IIB T3/T6.


65±1
44.5±1

2Ex de IIC T4/T6. A


165±3 9.5±1

0Ex ia IIC T4/T6. 136±2


Russian Fire Approved.
CQST: Certified Ex ia. 94±2
110±2 FIXING
Inmetro: Certified EEx d, EEx ia & EEx em. CENTRES

ABS: American Bureau of Shipping type approval for HD1BBD & HD1B1 only. OPTIONAL
CERTIFICATION
SIL: SIL2 certified. Cert no. Sira FSP 12007/02. LABEL GUARD

Material: Detector: stainless steel. B


4 OFF
FIXING HOLES
Ø7±1
Enclosures: Exd – LM25 marine grade alloy. 114±2
GLAND
FIXING CENTRES
Exia/Exem/UL – GRP (anti-static).
Stainless steel cover screws. M20 CABLE ENTRIES IN POSITIONS A & B

Optional Guard: 316 stainless steel.


Finish: Detector: Sand blasted. ALL DIMENSIONS IN MILLIMETRES

Enclosures: Exia/Exem/UL - Natural black or painted to customer’s


specification.
Listed Temperature Settings:
Exd painted to customers specification.
To select appropriate temperature settings, choose detector at 100ºF (38ºC) above maximum
Certified Temp: -20ºC to 55ºC (T6) Exem, UL, Exd IIC, CQST Exd IIB. ambient temperature.
-20ºC to 55ºC (T6) -20ºC to 125ºC (T3) Exd IIB (Not CQST).
-55ºC to 55ºC (T6) Exia. Temperature Setting Tolerance Colour Code of
Weight: Exd, 2kg. (ºF) (ºC) (ºF) (ºC) Text on Probe
Exia/Exem/UL, 1.1kg. 140 60 +7/-8 ±4 Black
Ingress Protection: IP66 & IP67. 160 71 +7/-8 ±4 Black
Operation: The detector contact is normally open and CLOSES at alarm 190 88 +7/-8 ±4 White
temperature. 210 99 +7/-8 ±4 White
Contact Rating: Ex d, EEx em, UL: 125V a.c.-5A, 125V d.c.-0.5A, 48V d.c.-1A, 24V d.c.-2A. 225 107 +7/-8 ±4 White
Ex ia: 30V - 300mA 275 135 ±10 ±6 Blue
Entries: 2 x M20 ISO (ATEX/Exd/Exe/Exi versions). 325 163 ±10 ±6 Red
2 x ½” NPT via adaptors (UL version). 360 182 ±10 ±6 Red
Terminals: 6 x 4mm2 (BK6). 450 232 ±15 ±8 Green
Resistor: Series & EOL resistor (maximum total 2) minimum value (each) 470Ω. 500 260 ±15 ±8 Orange
Diodes: Up to 2 off available in Exd IIB and Exia versions - contact sales office. 600 316 ±20 ±11 Orange
Labels: Optional stainless steel tag and duty labels. 725 385 ±25 ±14 Orange

Ordering Requirements The following code is designed to help in selection of the correct unit. Build up the reference number
by inserting the code for each component into the appropriate box.

Model Certification Type Temp Settings Options Finish


HD1

Certification Code Type Code TempºF Code Option Code Finish Code
ATEX B Exd IIB BD 140 140 Duty Label D* Natural Black N
IECEx J Exd IIC CD* 160 160 Tag Label T* (Exe/Exia/UL only)
ATEX/IECEx dual listed AJ Exe E† 190 190 Guard G Grey G
UL listed UL Exia I‡ 210 210 Resistor EOL E* Red R
ATEX/UL dual listed AU UL U 225 225 Resistor series S* Blue B
CUTR G* 275 275 Diode(s) I*† Yellow Y
Chinese (CQST) Q† * Exd IIC only available in ATEX. 325 325 Blanking Plug P Special S*
† ATEX/UL dual listed Exe 360 360
Inmetro M None N
version only.
450 450 * Please specify.
* Russian Fire Approved as standard. ‡ IECEx and ATEX/IECEx dual
listed only available Exia.
500 500 * Please specify
† Only available Ex ia certified. † Only available in ATEX Exd IIB
Not for use in China on fire alarm 600 600
725 725 or Exia versions (specify value).
systems.

All specifications, dimensions, weights and tolerances are nominal (typical) and MEDC reserve the right to vary all data without prior notice.
No liability is accepted for any consequence of use.

6DS116/R 10/14

159