How to select cable size for various
loads with calculation with real life
examples?
By Bharat Ribaciya « June 07, 2017
Voltage drop in Cables
Voltage drop is a important factor to consider while selecting cable size. Every cable have
internal resistance and this resistance is directly proportional to it's length and inversely
proportional to it's diameter[R = p (L/a)]. It can be neglect in small diameter and small length
wire but it must have to consider in long cable or big diameter cable. As per standard voltage
drop between power supply terminal and installation not be increase above 2.5% of supply
voltage. i.e. If supply voltage is 220 V then voltage drop not be increase then the 5.5 V.
Voltage drop also occur in between installation point(distribution box) & sub-circuit or final
sub-circuits and this drop should be half of that allowable voltage drop. i.e. 2.75 V of 5.5 V.
Their are two method to describe voltage drop, The Si(System International and Metric
System) and FPS(Foot Pound System). In SI system voltage drop describe in A/m and in FPS
system it describe as 100 feet.
Tables for Suitable Cable & Wire Sizes
For proper size of cable or wire the selection tables are given below:
Current No. ofwire | Area Current No.of wire Area
carying andthickness. (Inmm?) — carrying andthickness__(Inmm*)
capacity of each wire capacity of each wire
(In Amp) (in Amp)
a 11.13 1 a 1/0.044 0.0015
13 11.38 15 13 3/0.029 0.002
18 W/1,78 25 16 3/0.036 0,003
24 710.85 4 2 7/0.029 0.0045
31 7/104 6 28 710.036 0.007
42 WN.35 10 34 710.044, 0.01
56 INTO 16 43 7/0.052 0.0145
73 W214 25 56 7/0.064 0.0225
hpsielecrical20a blogspot car/2017/0/suitaee-cable-sizo Hindsy, 1:21 AM Howto select cable size for various loads wih calculation wth rea life exarples?
90 19/1.53 35 66 19/0.044 0.03
145 19/1.78 50 77 19/0.052 0.04
185 19/2.14 70 105 19/0.064 0.06
230 19/2.52 95 180 19/0.83 04
Table 1 - Current rating of Cu cables at 30°C or 86F
Current No. of wire Area Current No. of wire Area
carrying and (inmm) carrying and (mm)
capacity thickness of capacity thickness of
(inamp) each wire (inamp) each wire
3 16/0.20 Os 3 14/0.0076 0.0006
6 24/0.20 0.75 6 23/0.0076 0.001
10 32/0.20 1 13 40/0.0076 0.00017
13 40/0.20 1.25 18 70/0.0076 0.003
15 48/0.20 15 24 110/0.0076 0.004
20 80/0.20 25 31 162/0.0076 0.007
Table 2 - Current rating of flexible cords Cu cables at 30°C or 86F
Temp 1.02 1 097 | 094 | O91 088 | 077 | 0.63
Factor
TempF 77 86 95 104 113 122 1131 140
Temp*C 25 30 35 40 45 50 55 60
TempK 298.15 303.15 308.15 313.15 318.15 323.15 328.15 333.15
‘Table 3 - Temperature factor
Inside Trunking & Conduit Conductor
Single phase one cable AC & | Three phase three or four No. & Cross
oc core cable Diameter of | Section Area
wires (In (in inch?)
Inch)
Current. Volt Current Volt
Rating (A) Drop/100 Rating (A) Drop/100
Feet (V) Feet (V)
i 14 9 9.8 1/0.044 0.0015
13 12 al 91 3/0.029 0.002
16 m1 14 77. 3/0.036 0.003
2 84 18 6.4 7/0.029 0.0045
28 7 23 5.3 7/0.036 0.007
34 57 28 Al 7/0.044 0.01
43 5.5 36 4 7/0.052, 0.0145
56 48 48 3.5 710.064 0.0225
66 43 56 32 71970.044 0.03
77 36 65 27 19/0.052 0.04
105 34 88 25 19/0.064 0.06.
Table 4- Cable size, Current ratings with Voltage drop (British System)
hpsielecrcal20a blogspot car/2017/0/suitate-cable-sizo Hind
29sy, 1:21 AM Howto select cable size for various loads wih calculation wth rea fe expos?
Inside Trunking & Conduit Conductor
Single phase one cable AC & | Three phase three or four No. & Cross
oc core cable Diameter of | Section Area
(in mm?)
wires (In
mm)
Current Volt Current Volt
Rating (A) | Drop/Amp- | Rating(A) | Drop/Amp-
meter(mVolt meter(mVolt
) )
ii 41 9 35, 1/1.13 1
13 28 12, 24 1/1.38, 1.5
18 7 16 15 1/1.78 25
24 ii 22 91 7/0.85 4
31 7 27 6 7/104 6
40 Al 37 3.6 7/135 10
53 26 a7 22 77.10 16
60 V7 53 1.5 F214 25
74 1.2 65 1 19/1.53 35
Table 5 - Cable size, Current ratings with Voltage drop (SI/Decimal/Metric System)
‘Steps to find out voltage drop ina cable
Step 1-Find the maximum allowable voltage drop.
Step 2Find load current and according to load current, select a proper cable from table
(which current rating nearest to the load current).
‘Step 3-Find the voltage drop in meter or 100feet according it's rated current from table 1
Step 4-Calculate the voltage drop for the actual length of wiring circuit according to it’s rated
current by using these formulas.
Voltage drop (In per meter) = (Actual length of circuit * voltage drop for 1m) /100
Voltage drop (In 100feet) = (Actual length of circuit * volt drop for 100ft) /100
‘Step Now, find out voltage drop by using load factor
Load factor = Load current of cable/ Rated current of cable
Find out the rated current of cable from table and this value of load factor is voltage drop in
the cables when the current is passing through it. If this value of voltage drop is less then the
maximum allowable voltage drop which calculated in step 1, then the selected size of cable is
hipsielectrcal24x Hog spe cr/2017/0/eittle-cable-sizelind 39sv, 1:21 AM Howto sleet able size for srcs load wth clean wh el fe antes?
proper but if it is greater then the step 1 max. allowable voltage drop then calculate the
voltage drop greater size until it value becomes less then the step 1 voltage drop.
Examples - Find out proper cable size for given load
To determine cable size keep in mind these rules of voltage drop.
+ For a given load, there should be 20% extra scope of current for additional, emergency
or future needs (except the known value of current).
‘+ From Energy meter to DB, voltage drop should be 1.25% and 2.5% for final sub-circuit
should not exceed 2.5% of Supply voltage.
‘+ Use temperature factor for considering change in temperature from table 3 and consider
load factor while finding cable size.
+ Selecting cable size consider the wiring system (Temperature is low in open wiring
system then the conduit wiring)
+ Consider diversity factor in wiring installation
‘Solved examples for cable size selection
Example 1 - For Electrical wiring installation in a building, Total load is 4.5kW and total length
of cable from energy meter to sub circuit distribution board is 35 feet. Supply voltages are
220V and temperature is 40°C (104°F). Find the most suitable size of cable from energy meter
to sub circuit if wiring is installed in conduits.
Solutior-(British System)
Total Load = 4.5 kW = 4.5 x 1000 W = 4500 W and 20% additional loa
w
=Total Load = 4500 W + 900 W = 5400 W
4500 x (20/100)
Total Current = | = P/V = 5400 W /220 V =24.5.A
For the load current the size of cable is 7/0.036(28 A) from table. Now, check the temperature
factor from table 3, it is 0.94 at 40°C and current carrying capacity of cable size 7/0.036 is 28
A. So,
Current rating for 40°C = 28 x 0.94 = 26.32. A
It is less then the current carrying capacity of selected cable which is 28 A, therefore it is
also suitable with respect to temperature.
hpsielecrical20a blogspot car/2017/0/suilate.cable-sizo Hindsy, 1:21 AM Howto select cable size for various loads wih calculation wth rea fe earrples?
Now find the voltage drop for 100 feet for this (7/0.036) cable from Table 4 which is 7 V, But in
our case, the length of cable is 35 feet. Therefore, the voltage drop for 35 feet cable would be;
Actual Voltage drop for 35 feet = (7 x 35/100) x (24.5/28) = 21 V
And Allowable voltage drop = (2.5 x 220)/100 = 5.5 V
Here, The actual voltage drop (2.1 V) is less than that of maximum allowable voltage drop of
5.5 V. Therefore, the cable size (7/0.036) is suitable for that given load
Example 2- What type and size of cable suits for given situation
Load = 5.8 kW
Volts = 230 V
Length of Circuit = 35 meter
‘Temperature = 35°C (95°F)
SI/ Metric / Decimal System )
Load
Voltage = 230 V
5.8 KW = 5800 W
Current = | = P/V = 5800 / 230 = 25.2.4
20% additional load current = (20/100) x5.2A=5A
Total Load Current = 25.2 A+ 5A =30.2A
From the table 1, size of cable is 7/1.04 for 31 A and temperature factor is 0.97 for 35°C from
table 3.
Current rating for 35°C = 31 x 0.97 = 30,
It is less then the current carrying capacity of selected cable which is 31 A, therefore it is
also suitable with respect to temperature.
Now find the voltage drop for per ampere meter for this (7/1.04) cable from Table 5 which is 7
mV, But in our case, the length of cable is 35 meter. Therefore, the voltage drop for 35 meter
cable would be;
Actual Voltage drop for 35 meter = mV x I x L = (7/1000) x 30x35 = 7.6 V
Allowable voltage drop = (2.5 x 230)/100 = 5.75 V
Here, the actual voltage drop is greater than then the maximum allowable voltage drop of 5.75
\V Therefore the cable size (7/1 0a) is not suitahle for that aivan lnad Naw find aut valtane
hpsielecrcal26a blogspot car/2017/06/suiate-cable-sizo irl 59sy, 1:21 AM Howto select cable size for various loads wih calculation wth rea life exarples?
drop again by selecting higher cable size. Let's select 7/1.35 and calculate again.
From table 5, cable rating for selected cable size is 40 A and voltage drop is 4.1 mV. So,
actual voltage drop for 35 meter is
Actual Voltage drop for 35 meter =(4.1/1000) x 40x35 = 7.35 V = 5.74V
Now, The actual voltage drop is less than that of maximum allowable voltage drop. Therefore,
the cable size (7/1.04) is suitable for that given load
Example 3- Following Loads are connected in a building:
For Sub-Circuit 1
2 lamps each 0 1000 W and
4 fans each of 80 W
2 TV each of 120 W
For Sub-Circuit 2
6 Lamps each of 80 W and
5 sockets each of 100 W
lamps each of 800 W
If supply voltages are 230 V then calculate circuit current and Cable size for each Sub-Circuit?
Solution:
Total load of Sub-Circuit 1 = (2 x 1000) + (4 x 80) + (2x120) = 2000 W + 320 W + 240 W = 2560
w
Current for Sub-Circuit
P/V = 2560/230 = 11.1 A
Total load of Sub-Circuit 2 = (6 x 80) + (5 x 100) + (4 x 800) = 480 W + 500 W + 3200 W= 4180
Ww
Current for Sub-Circuit
= PV = 4180/230 = 18.1A
From the table, cable size for sub circuit 1 is 3/.029° (13 A) or 1/1.38 mm (13 A) and for sub-
circuit 2 is 7/.029" (21 A) or 7/0.85 mm (24 A).
Total Current drawn by both Sub-Circuits = 11.1 A+ 18.1 A= 29.27 A
So, cable size for main-circuit is 7/.044" (34 A)
hpsielecrical20a blogspot car/2017/0/suilate.cable-sizo Hind 69sy, 1:21 AM Howto select cable size for various loads wih calculation wth rea fe expos?
Example 4-A 10 H.P (7.46 kW) three phase squirrel cage induction motor of continuous rating
using StarDelta starting is connected through 400 V supply by three single core PVC cables
run in conduit from 250 feet (76.2 m) away from multi-way distribution fuse board. Its full load
current is 19 A. Average summer temperature in Electrical installation wiring is 35°C (95°F).
Calculate the size of the cable for motor?
Solution:
Motor load = 10 HP = 10 x 746 = 7460 W (-
Supply Voltage = 400 V (3-Phase)
Length of cable = 250 feet (76.2 m)
Motor full load Current = 19 A
‘Temperature factor for 35°C (95°F) = 0.97 (From Table 3)
HP = 746 W)
Size of cable for 19 A full load current is 7/0.36" (For 23 A) in the table, Here, 3-phase system
and voltage drop is 5.3 V fro 100 feet. According to table 4 cable size 7/0.036 can be use.
From the table 3, the temperature factor is 0.97 at 35°C and current carrying capacity of
selected wire is 23 A. So,
Current rating for 40°C (104"F) = 23 x 0.97 = 22.31 A
It is less then the current carrying capacity of selected cable which is 23 A, therefore it is
also suitable with respect to temperature.
Load factor = 19/23 = 0.826
From the table 4, voltage drop is 5.3 V for selected cable at 100 feet and here, length of cable
is 250 feet. therefore,
Actual voltage drop (250 feet) = (5.3 x 250/100) x 0.826 = 10.94 V
‘And maximum Allowable voltage drop = (2.5/100) x 400 V= 10 V
Here, the actual voltage drop is greater than then the maximum allowable voltage drop of 10
V. Therefore, the cable size (7/0.036) is not suitable for that given load. Now, find out voltage
drop again by selecting higher cable size. Let's select 7/0.044 cable size and calculate again.
Actual voltage drop (250 feet) = (4.1/100) x 250 x 0.826 = 8.46V
‘And Maximum allowable voltage drop = (2.5/100) x 400V= 10V
Now, The actual voltage drop is less than that of maximum allowable voltage drop. Therefore,
the cable size (7/0 04d is suitable for that civen nad
hpsielecrical26a blog spe car/2017/06/suilaee-cable-sizo ind 79192, 1121 AM Howto select cable size for various loads wih calculation wth rea fe earrples?
"~ housewiring installation wiring
Popular posts from this blog
Three phase electrical wiring system for home & multi-floor
building
jiya = June 08, 2017
In this article you will learn about how to do three phase wiring in home.
Generally, the elctrical supply provider company install single phase energy
meter for where requirements is 7.5 kW load in domestic area
READ MORE
How to control One Lamp from three/six different places and
working principle of intermediate switch?
= June 07, 2017
In this article we learn about how to control a lamp with 3 different switches
at different places. This is very useful. For doing this we required two 2-way
switch, 1 intermediate switch and a lamp. Connect all these at
READ MORE