0% found this document useful (0 votes)
43 views50 pages

Frequency Control Modelling Basics

Frequency control

Uploaded by

Irfan Ullah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
43 views50 pages

Frequency Control Modelling Basics

Frequency control

Uploaded by

Irfan Ullah
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 50

Downloaded from orbit.dtu.

dk on: Aug 29, 2024

Frequency control modelling - basics

Hansen, Anca Daniela; Sørensen, Poul Ejnar; Zeni, Lorenzo; Altin, Müfit

Publication date:
2016

Document Version
Publisher's PDF, also known as Version of record

Link back to DTU Orbit

Citation (APA):
Hansen, A. D., Sørensen, P. E., Zeni, L., & Altin, M. (2016). Frequency control modelling - basics. DTU Wind
Energy E Vol. 0103

General rights
Copyright and moral rights for the publications made accessible in the public portal are retained by the authors and/or other copyright
owners and it is a condition of accessing publications that users recognise and abide by the legal requirements associated with these rights.

 Users may download and print one copy of any publication from the public portal for the purpose of private study or research.
 You may not further distribute the material or use it for any profit-making activity or commercial gain
 You may freely distribute the URL identifying the publication in the public portal

If you believe that this document breaches copyright please contact us providing details, and we will remove access to the work immediately
and investigate your claim.
Frequency control modelling - basics
DTU Vindenergi
E Rapport 2016

A. D. Hansen, P. Sørensen, L. Zeni, M. Altin

DTU Wind Energy E-0103

January 2016
Forfatter(e): A. D. Hansen, P. Sørensen, L. Zeni, M. Altin
Titel: Frequency control modelling - basics 2016
Institut: DTU Wind Energy

Resume (mask. 2000 char.): ISBN 978-87-93278-59-2


The purpose of this report is to provide an introduction on how the system
balance in an island system can be maintained by controlling the frequency.
The power balance differential equation, which is fundamental in
understanding the effect on the system frequency of the unbalance between
generation and consumption, is addressed. Basic topics on the main
components of a generating unit, such generators, prime movers and
governors are presented. A simple dynamic model for an island power
system, containing realistic dynamic representations of generators, loads,
prime movers, governors, is described specifically for the assessment of the
performance of frequency droop control loop, i.e. primary control.

Danmarks Tekniske Universitet


DTU Vindenergi
Nils Koppels Allé
Bygning 403
2800 Kgs. Lyngby
Telefon

www.vindenergi.dtu.dk
Content

Introduction .....................................................................................................................................4

1. General issues on power systems .......................................................................................5

2. Generating units components ............................................................................................12

3. Generating unit characteristics ..........................................................................................18

4. Modeling representations ...................................................................................................24

5. Dynamic models in frequency control loop ........................................................................37

6. Frequency control with wind power....................................................................................45

References ...................................................................................................................................46
Introduction
An electric power system is by definition a system where power is produced, transmitted and
consumed in real time, namely contrarily to storage systems, power is intermittent and produced
as demand calls for it. This means that a balance between production of electricity and
consumption of electricity must always be maintained in a power system. A change in this
balance alters the system frequency and if this violates a strictly predefined frequency range, it
can threaten the stability and thus the security of the power system. Steady state frequency of
50Hz is thus an indication that the generation and the consumption are in balance.
As illustrated in Figure 1, on one side of the balance there are the large power plants, which
produce electrical power. Notice that besides the traditional ones, namely the thermal and hydro
plants, nowadays there are also more and more renewable generators like wind turbines and
solar cells. On the other side of the balance there are the consumers, i.e. houses, hospitals,
offices and electric vehicles. The consumers are also called loads or demand.

Figure 1: Power balance between production and consumption.

The maintenance of the power balance implies that in case of too much electricity
production (supply), the frequency will increase, while in case of too much electricity
consumption the frequency will decrease.
System balance is in general the responsibility of transmission system operators (TSOs),
who utilize some predefined large power plants existing in the system to maintain the frequency
constant at its nominal value. This balance is typically ensured through functions such as i.e.
activation of additional generation or disconnection of loads, this last action being referred to as
load shedding.
The goal of the present report is to provide an introduction on how the system balance in an
island system can be maintained by controlling the frequency.

4 DTU Wind Energy E-0103


1. General issues on power systems
In this chapter a general introduction to power systems and their frequency control is given. It is
not the intention to include the fundamentals of electrical engineering related with power
systems. However some basic terminologies will be shortly addressed from time to time, when
necessary, for the sake of completeness. The equation of motion, which is fundamental in
understanding the effect of an instantaneous imbalance between load and generation on the
system frequency, is described.

1.1 Power system frequency


Nowadays power systems are mostly based on alternating current (AC) applications [1]. An
alternating current occurs typically when the voltage source (i.e. potential energy source)
alternates around zero with nil average value over a period T. Figure 2 shows an example on
how an alternating signal oscillates between positive and negative value.

1
+ f = [ Hz ]
T

Time

-
1 period
T [s]

Figure 2: Alternating signal.

The time in seconds it takes the signal to complete one cycle is called the period
(revolution), denoted typically by T. As indicated in Figure 2, the frequency f is the term used to
describe the number of cycles of an alternative signal in a second 1.
The synchronous electrical angular speed ωe0 is defined as:

ωe0 = 2 ⋅π ⋅ f0 [rad / s ] (1)

where f0 denotes the synchronous frequency (i.e. 50 Hz or 60Hz).


1.2 Synchronous power systems
A synchronous region is a regional power system that operates at a synchronized frequency
and it is tied together during normal system operations 2.
All the grids in Europe are synchronized at 50Hz 3, while those in USA operate at 60Hz.
Figure 3 illustrates the five synchronous regions existing in the ENTSO-E association for
European Network of Transmission System Operators for Electricity [2]:
• Continental Europe 4 synchronous grid
• Ireland’s synchronous grid

1 The number of cycles per second is also called hertz (Hz).


2 Notice that small local deviations can still appear due e.g. oscillations of the synchronous machines
3 In Europe, the period (revolution) of al alternating signal with a synchronous frequency is 20ms.
4 Includes the members of UCTE (Union for the Coordination of Transmission of Electricity) system, where Western
Denmark is included.

DTU Wind Energy E-0103 5


• United Kingdom’s synchronous grid
• Nordic synchronous grid 5
• Baltic synchronous grid

Figure 3: European network of transmission operators for electricity [2]

The main task of ENTSO-E is to maintain the frequencies in all five synchronous power
systems balanced around the standard nominal value of 50Hz ensuring a safe European power
supply.
Electrical power is typically produced by central power plants connected to the system.
They convert mechanical energy into electrical energy by using synchronous generators.
These generators are normally driven by prime movers such as steam turbines, gas turbines or
hydro turbines.
Frequency in the power system is directly related to the rotating speed of the synchronous
generators connected to the system. The frequency is synchronous all over the system, but
small deviations can happen locally owing to the oscillations of the synchronous machines.
Figure 4 illustrates a mechanical equivalent for the power system, namely a tandem
configuration: the synchronous generators are running similar to a tandem, sharing the same
load through the chain [3]. Load division between power plants is dependent on their speed-
droop characteristics [1].

5 Nordic region consists of Finland, Sweden, Norway and Eastern Denmark – members of TSO association NORDEL.

6 DTU Wind Energy E-0103


Power
system
~ ~ Load

Gen1 Gen2

Tandem
equivalent

Gen1 Gen2 Load

Figure 4: Mechanical equivalent of the power system operation.

1.3 Why frequency control in power systems?


Frequency in a power system is typically maintained in a narrow band. Nevertheless changes in
frequency may occur if production or consumption exceeds its counterpart.
Figure 5 shows the legal operational states in the Nordic system. They are typically
indicated by colours similar to those used in traffic lights, namely green for normal operation,
yellow for alert operation and red for fault operation (disturbed or emergency operation). The
colours are thus indirectly reflecting the security state of the power system.
The frequency in the Nordic power system is maintained during normal operation at the
synchronous frequency 50Hz within operational limits of ±0.1Hz from the nominal value. If the
frequency starts to deviate out of this range because of faults in the system, several
consecutive warnings are activated in the power system. Notice that the system may still be in
normal operation condition even in case of small power plant faults, as long as the frequency is
maintained within the limits. However a large negative deviation can be a threat for the security
of the system, because it might lead to potential blackout. A blackout means that the whole
power system is going down due to problems in the generation of the electricity and as result
the loads in the system are disconnected or are taken out of operation. On the other hand, a
large positive deviation in frequency, due to generation exceeding the consumption, is more
easily tackled and less harmful to the security of the entire power system.

DTU Wind Energy E-0103 7


Figure 5: Operational states in the Nordic system [4].

One particular failure in the system, typically called as (n-1) dimensioning fault 6 situation,
may lead the system into an alert operation (yellow area). Notice in Figure 5 that in this
operational state, the power system should be restored in less than 15 minutes; otherwise the
system enters disturbed operation state. In this situation, many systems can be protected from
frequency collapse by importing large amounts of power from neighbouring systems to counter
balance for the lost generation 7. Beside power plants, a frequency drop in a power system is
also registered by the loads. Another way to solve an emergency situation and to prevent a
frequency collapse is therefore load shedding, where the least important loads are shed/
disconnected first. A load shedding can be performed manually or automatically as a part of
security protection system. In an emergency situation, it is preferred to shed loads in the system
to avoid a complete blackout, where all power plants in the system would disconnect. In the
extreme situation of a blackout it may take very long time to recover the frequency. Another way
to manage an emergency situation is to split up the network and isolate the part of the grid,
which has caused emergency situation.
Figure 6 indicates that in an emergency state, power actions on the HVDC (high voltage
DC) links are taken in the Nordic system.

6 A dimensioning fault is defined in the grid codes as the situation when the biggest component in the
system falls.
7 Denmark can for example import power generation from Germany or Norway in case fault operation.

8 DTU Wind Energy E-0103


Blackout

Blackout

Figure 6: Frequency controlled actions in the Nordic system [4].

A sudden connection of a large load or disconnection of a generating unit by the protection


equipment may result in a significant distortion of the power balance in the power system. This
imbalance, which is initially covered by the release of the kinetic energy of rotating masses
connected to the system, has as result a drastic drop in the frequency - as indicated in Figure 7.
The rate at which the frequency drops, depends on the total angular momentum (rolling inertia)
in the system, calculated as the sum of the angular momenta of all generators and spinning
loads connected to the system.
The attention in the frequency control studies existing in the literature is typically drawn to
the under-frequency events, namely to the events that lead to frequency drops. Frequency
drops are also in focus in the present report.
The process of stabilization the frequency to a steady state (constant) value is typically
performed through the primary control function, while the process of restoring the frequency
back to the steady state corresponding to the nominal frequency value (i.e. 50Hz in the
European system) is known as secondary control.
Primary control is provided automatically (within typically 30 seconds after a frequency
drop) by fast generating units through a frequency droop (usually proportional) control loop. In
the case of a frequency drop, these generating units start immediately to produce more power
to avoid a further decrease of the frequency in the system. As illustrated in Figure 7, the task of
primary control is to bring the frequency back to short term acceptable frequency values. During
primary control, the frequency is thus stabilized temporarily to a lower level than the initial one,
the system being still in an alert condition (i.e. yellow area).
Secondary control, also called Load Frequency Control, is a supplementary control loop,
much slower than the primary control, which re-distributes load among the various generating
units in order to restore the frequency back to its nominal value. In secondary control, the power
setpoints of the generators are adjusted in order to compensate for the remaining frequency
error after the primary control function. In the Danish power system, the secondary response
must be delivered within 15 minutes. Secondary control is made either via automatic generation

DTU Wind Energy E-0103 9


control systems (i.e. Continental Europe synchronous grid) where available, or via manual
intervention by the system operators (i.e. in Nordic System).

f [Hz] up to 15 min

up to 30s
50.1

50 Normal operation

49.9
fault event

Alert operation

Primary Secondary time


response response

Figure 7: Frequency control in the Danish power system –


for a fault event e.g. when a generating unit trips (disconnects).

In this report, the mechanisms for primary frequency control in island power systems are
addressed and modelled. Primary control is implemented on a purely local level (on power plant
level), i.e. without any coordination between different power plants.

1.4 Equation of motion (EoM)


Before presenting the equation of motion of the power system, it is useful to visualise the
analogies between quantities and relationships associated with rotational motion with those
associated with linear motion, since the latter is more familiar and easy to understand. Table 1
summarizes these analogies.

10 DTU Wind Energy E-0103


Table 1: Analogies between linear and rotational motion. Source: [1]

Linear Motion Rotational Motion


Symbol/
Quantity SI unit Quantity Symbol/ Equation SI unit
Equation
Rotational
Length L m θ rad
angle
Moment of
Mass m kg
inertia
Angular
Velocity v m/s rad/s
velocity
Linear Angular
kg m/s
Momentum momentum
Angular
Acceleration
acceleration

Force F=m ⋅ a Torque

Power P =F ⋅v W Power W

Power plants (generating units) transform other sources of energy in the process of
producing electrical energy. For example hydraulic, heat, solar, wind sources of energy can be
used in the production of electrical energy, as illustrated in Figure 8. Notice that the generator is
driven by a prime mover, which can be for example a steam, gas or hydro turbine.
From the viewpoint of frequency control, the power system can be thought as only one
large power plant supplying one load. Two opposite torques act on the large rotating mass,
namely a mechanical torque Tmec and an electrical torque Telec, as shown in Figure 8. In case of
an imbalance between these torques, the rotating mass will experience an angular acceleration
or deceleration d ω/dt according to Newton’s Second Law for rotating systems:

Tmech − Telec = I
dt
2 2
[kg ⋅ m /s ]
(2)

where I is the moment of inertia of the rotational mass. Notice that the inertia I has a
stabilization effect, i.e. in case of an imbalance in torques, the frequency change is smaller for a
system with high inertia compared to a system with low inertia, meaning that a high inertia
system is more stable.

Production Demand

Transfer
Tmec Telec
Energy Electrical
Prime mover Generator Loads
Source energy

Heat Turbine
lights,computers,
Water (steam/water/gas/wind)
houses, motors …..
Wind Diesel Engine

Figure 8: Simplified electric power system with a single prime mover, generator and load.

DTU Wind Energy E-0103 11


The previous equation is also known as equation of motion (EoM). The equation of motion
includes generally rotating components of the power system i.e. generating units and loads.
Notice that a sudden increase in the generation, namely in the mechanical torque Tmec, implies
an increase in the rotational speed ω and thus in the frequency f in the system. Vice-versa, an
increase in the consumption, namely in the electrical torque Telec, implies a decrease in the
frequency. It is worth noticing that the larger the inertia of the rotating mass is, the smaller the
speed rate-of-change following a torque imbalance is.
The equation of motion can also be expressed in power terms by using the proportional
relationship between power and torque:

P =T ω [kg ⋅ m /s ]
2 3
(3)

By applying this relationship, the equation of motion in power terms (power balance
equation) can be expressed as:
dω dω
Pmech − Pelec = Iω =M
dt dt (4)
where Pmech is the mechanical power, Pelec is the electrical power and M is the angular
momentum of a rotating system, defined as:

M =Iω [kg ⋅ m /s]


2
(5)

2. Generating units components


The scope of this chapter is simply to provide an overview over the components of a generating
unit, addressing shortly the role and the inputs/outputs of each component in a generating unit.
Basic topics on generators, prime movers and governors are presented. No models are
presented in this chapter, since this is the topic of a subsequent chapter.

The principle of the balance between production and consumption in a power system can
be best presented by considering an isolated generating unit supplying a local load, as
illustrated in Figure 9. The electrical energy is produced by a generator driven by a prime
mover, which is usually a turbine or a diesel engine. The turbine is equipped with a governor,
which controls the speed of the generating unit according to a predefined power-frequency
characteristic.

Pelec
Load
Generating unit
Pref
Pfuel Prime Pmech + – Generator ω
ωref Governor
mover (EoM)

Figure 9: Generating unit supplying isolated load.

12 DTU Wind Energy E-0103


2.1 Generator
As illustrated in Figure 10, generators have typically coils of wire mounted in a certain pattern in
a stationary housing, called stator, where the voltage is produced due to the magnetic field
provided by the spinning rotor.
The rotor, which is the rotating part of the generator, is responsible for the inducing
magnetic field of the generator. A rotor can have a permanent magnet or an electromagnet. In
the case of an electromagnet, a magnetic field is produced around the rotor windings due to the
current flowing through them, when they are connected to a stationary voltage source 8. By its
rotation, the rotor’s magnetic field, that passes the stator windings, induces voltages at the
stator’s terminals. A magnetic field is further created around stator’s windings (induced field), if
current flows in the stator windings, i.e. the generator is loaded.

Figure 10: Generator’s stator and rotor.

When the magnetic field of the stator is following the magnetic field of the rotor at the same
speed, the generator is called synchronous. Such generator is synchronized to the power
system, namely its shaft speed is the same as the frequency of the voltage in the power system.
If the magnetic fields are not following each other synchronously the generator is called
asynchronous.
The synchronous generator is the workhorse for the generation of electricity in the power
system. Synchronous generators with power rating of several hundred MW are very common.
Figure 11a) shows as an example the size of a 660MW synchronous generator. Figure 11b)
illustrates a front side visual perspective of the generator, namely the inner rotor and the outer
stator with the three-phase windings, separated by an airgap.

8 The rotor windings are connected to a stationary voltage source via electrical contacts (slip rings).

DTU Wind Energy E-0103 13


Stator

Airgap

Rotor

a) b)

Figure 11: a) Size example of a 660MW AC generator.

Source: http://emadric.blogspot.com b) Generator cross section sketch.

For synchronous generators in power plants, the current which generates the rotor’s
magnetic field is normally supplied by an exciter (DC - Direct Current voltage source).

2.1.1 Electricity generation - basic principles


It is not the task of this section to provide a detailed description of the electrical system
terminologies. However for the sake of a good understanding of how electricity in the power
system is produced, some basic concepts are quickly addressed.

There are actually two physical laws that describe how the electric power system works:
• Faraday’s Law - says that by placing a coil of wire (conductor) next to a moving/rotating
magnet, an AC (Alternating Current) voltage is induced in that coil. This principle is
graphically illustrated in Figure 12 both for single-phase and three-phase AC voltage
generation. Notice how by placing one coil of wire next to a moving magnetic field (i.e.
magnet), a voltage is induced in the coil. Each time the North pole and the South pole
passes the coil, with the layout adopted in the figure, the induced voltage in the coil has
a positive peak (denoted by N) and a negative peak (denoted by S), respectively. Figure
12 shows also that when three coils spaced physically with 120 degrees apart in a 360
degree circle are placed in the presence of a moving magnetic field, a so called three-
phase AC voltage is induced.
• Ampere’s law - says that a current flowing through a wire creates a magnetic field
around the wire. This law describes how a magnetic field can be created, when the coil
of the rotor is connected to a voltage source (e.g. battery, exciter). The induced
magnetic field in the rotor’s coil has of course a north and a south pole.

The simple combination of these two laws depicts the phenomena behind how electric
generators produce electricity. Generators, for example, use a moving magnetic field next to a
coil to produce voltage, while the magnetic field is created by applying a voltage (e.g. battery) to
a coil of wires.
A three-phase AC generator has basically three single-phase windings mounted on the
stator. The windings are physically spaced so that the angle between the magnetic fields
induced in each winding is 120 degrees – as illustrated in Figure 12.

14 DTU Wind Energy E-0103


Single-phase AC voltage generation
+
N

N
Time
S
S
-

Three-phase AC voltage generation


1
+
N1 N2 N3

N
Time
S
S1 S2 S3
-
2 3

Figure 12: Single-phase and three-phase voltage generation.

2.1.2 Rotor poles


Many synchronous generators in the power system have more than one pole-pair (i.e. more
than two poles) in the rotor. They may have four, six, eight or more poles, depending on the
desired speed of rotation. Figure 13 illustrates the effect of increasing the number of poles in the
generator rotor, namely higher number of poles implies slower rotational speed.

0 5 10 15 20

N S
ωe 0
N ωe 0 2

N
S S

Two poles Four poles

a) b)

Figure 13: Three phase generators with different rotor poles:


a) Generator with two poles (one pole-pair Npp=1)
b) Generator with four poles (two pole-pairs Npp=2)

DTU Wind Energy E-0103 15


In a synchronous generator the generated frequency is determined by the rotational speed
and the number of poles in the generator. Synchronous generators, even with differing number
of poles, can thus operate in parallel at the same synchronous frequency, due to their different
rotational speeds.
The synchronous rotor speed ωgen0 of a generator with two poles (Npp = 1) is equal to the
synchronous electrical angular speed ωe0, namely it corresponds to the synchronous frequency
of the AC (Alternating Current) voltage on the terminals. This means that the rotor speed of a
synchronous generator with one pole pair can be provided by a measurement of the frequency
of the voltage:
N pp = 1 → ω gen 0 = ω e 0 = 2 ⋅ π ⋅ f 0 [rad / s ] (6)

Figure 13 shows that for a generator with two pole-pairs, the windings in the coil for each
phase of the stator are rearranged according to the increased number of poles in the rotor. In
this case, one cycle of voltage corresponds to only half rotation compared to that for a
generation with one pole-pair, namely:
ωe0 2 ⋅ π ⋅ f 0 (7)
N pp = 2 → ω gen 0 = = [rad / s ]
2 2
Increasing the number of magnetic poles on the rotor enables thus the generator’s rotor
speed to be slower and still maintain the same electrical output frequency f0.
For a certain number of pole-pairs Npp, the rotor speed of the synchronous generator ωgen0
can be expressed as follows:

ωe0 2 ⋅π ⋅ f0 (8)
N pp → ω gen 0 = = [rad / s ]
N pp N pp
Its expression in rotations per minute [rpm] is:

f0
[rpm]
(9)
n gen 0 = 60 ⋅
N pp
The electrical power Pgen produced by a synchronous generator is depending on its
rotational speed ωgen0 and torque Tgen as follows:

Pgen = Tgen ω gen 0 [W ] (10)

Notice that slower rotational speed implies higher torque to get the same electrical power,
i.e. if a 2-poles and a 4-poles synchronous generator provide same electrical power, then the
torque of the 4-poles generator is two times bigger the torque of the 2-poles generator.

2.2 Prime mover


As illustrated in Figure 9, the production of electrical energy by mechanical means always
requires a prime mover to drive a generator.
A prime mover is mainly a turbine or a diesel engine, used to convert an energy source
(i.e. steam, hydro, wind) into mechanical rotational movement of the rotor of a generator. A
prime mover has typically a throttle valve, which position (open/close) is adjusted continuously
by a control device called governor.

16 DTU Wind Energy E-0103


The input of the prime mover is a power flow related with the position of the throttle valve,
while its output is the mechanical power, which drives the generator.
A simple model for a prime mover is presented in Section 5.3.

2.3 Governor
Each prime mover is equipped with a governor that senses the speed changes of the turbine
and controls it to a predefined setpoint value. Governor is thus a mechanism, which controls the
unit speed by adjusting (increasing or decreasing) the power flow into the prime mover to
change the mechanical power output to compensate for load changes and thus to maintain
frequency (speed) at a desired value.
For many years governors were of mechanical-hydraulic type, which was based on the
widely used Watt flyballs centrifugal mechanism, shown in Figure 14, as the speed responsive
device. Depending on turbine speed, the flyballs actuate a mechanical-hydraulic system to open
or close the throttle valve of the prime mover and adjust (i.e. increase or decrease) the energy
input to the prime mover. In this way, the governor manages to maintain the frequency (speed)
at a desired value. As illustrated in Figure 14b), an increase in the speed ω causes the flyballs
to move away from the rotating shaft, which forces the throttle valve to close a little. This action
implies that the power flow through the prime mover is reduced and the frequency (speed) is
controlled back to its setpoint.

ω
valve

a) b)

Figure 14: James Watt flyballs governor: a) in repose b) in action

Nowadays, electronic governors are more frequently applied. They measure the frequency and
actuate hydraulic devices to control gate or throttle position without the use of flyballs [5].
There are two types of governors:
• The isochronous governor 9, which is the simplest type governor, controls and
maintains the frequency regardless of the generator loading. It adjusts the prime
mover’s valve to bring the frequency back to its setpoint value. This governor mode is
also referred to as frequency control operation mode. Such governor works
satisfactorily when only one generator in the system has to respond to changes in load.
This type of governor is problematic to use when several generators, connected to run

9
Isochronous means constant speed.

DTU Wind Energy E-0103 17


in parallel, have to share the load in the system, because they can work against each
other, trying to control the frequency to their own settings [6].
• The speed-droop governor controls the frequency taking the generator loading into
account. It provides the primary control function, described in Section 1.3. It is utilized
when two or more generating units connected to the power system have to share a
load change.

3. Generating unit characteristics


The scope of this chapter is to explain the basic characteristics of a generating unit, like droop,
power setpoint, nominal power, frequency bias and how multiple generating units can share
load changes in the system.

3.1.1 Droop characteristic


The droop characteristic of a generating unit is a steady-state power-speed characteristic, as
illustrated in Figure 15. It reflects an idealized relation between the system frequency and the
power, which can be delivered by a generating unit into the system during its operation. Notice
that the power of the unit slides back and forth along the droop characteristic in the attempt to
stabilize supply and demand regardless of the frequency. According to the droop curve a
decrease in frequency yields to a higher power production and vice-versa.
By definition:
• The power setpoint Pref of a unit is the power, which is delivered by the unit at the
nominal frequency fn.
• The nominal power Pn of the unit is the maximum power, which can be continuously
produced by the unit, and as illustrated in Figure 15, it corresponds to full load
condition.

f [Hz]

fn

P [MW]
Pre f Pn
no-load full-load

Figure 15: Steady-state droop characteristic.

Besides providing a graphical definition of droop, Figure 16 also illustrates the effect of
changing the droop of a generating unit. The droop R of a unit is defined as the percentage of

18 DTU Wind Energy E-0103


the frequency change required for a governor to move a unit from no-load to full-load or vice-
versa 10. Notice that by definition the droop is a non-negative value.

f [Hz]
R = 0%
f n = 50
R = 2% ∆f = 2% ⋅ f n
49 ∆f = 4% ⋅ f n
R = 4%
48

0
0% 25 % 50 % 75 % 100 %
Generator loading (% full load)

Figure 16: Graphical signification of droop.

Figure 17 indicates graphically different characteristics related to a generating unit: the


droop R, the nominal power Pn, the frequency bias B, the change in power ∆P from power
setpoint and the frequency deviation ∆f from the initial steady state. By writing the proportional
relations sketched in Figure 17, the mathematical expression of the droop can easily be
obtained as follows:

∆f ∆P ∆f / f n
[%]
(11)
=− ⇒ R=−
R ⋅ fn Pn ∆P / Pn

Pn
f [Hz]
B

fn R ⋅ fn
1 Hz ∆f

∆P

0 Pref Pn P [MW]
Figure 17: Droop R and frequency bias B graphically illustration.

This is the mathematical expression of the power balance between generation and
demand, when the system is in steady state.

10 For example, a 4% droop means that a 4% frequency deviation causes 100% change in the power output of the
generating unit.

DTU Wind Energy E-0103 19


If the generating units in a power system do not have the same droops, an equivalent
droop RPS for the whole power system can be calculated according to the following expression:
N units
Pn ,i
1
∑R
i =1
= N units
i
(12)
RPS
∑P
i =1
n ,i

where Ri and Pn,i denote the droop and the nominal power of unit i, respectively. Nunits is the
number of generating units in the system. Notice that if the individual droops are equal, the total
droop of the system is equal with one individual droop.

3.2 Frequency bias


Another characteristic of a unit, illustrated graphically in Figure 17, is the frequency bias B.
Frequency bias reflects the power ability (reserve) of the unit in [MW] to compensate for a
frequency deviation of 1Hz, as following 11:

ΔP (13)
B=− [MW/Hz]
Δf
Notice that the frequency bias is per definition a positive value and can further be
expressed as:
Pn
B= [MW/Hz] (14)
R ⋅ fn
This formula can also be used to calculate the bias of a whole power system BPS, when it is
assumed that all units existing in a power system are sharing the same nominal frequency fn
and droop R:

Pn , PS
BPS = [MW/Hz] (15)
R ⋅ fn

where Pn,PS is the nominal power of the whole power system. Otherwise the total bias of the
power system BPS has to be calculated by simply adding the biases of the individuals generating
units Bi, as follows:
N units
BPS = ∑B
i =1
i [MW/Hz] (16)

Notice that the larger the number of generating units running in a power system is, the
larger the frequency bias may be. The droop characteristic of a system with a very large number
of units tends to be almost horizontal. This means that frequency deviation in a system with a

11 For example, if the bias of a unit is B=100 [MW/Hz], it means that for a decreasing in frequency of 1Hz, the unit is
able to increase its power production with 100MW.

20 DTU Wind Energy E-0103


very large number of units due to a change in power may be very small even for a large power
change.
Once the frequency bias BPS of a power system is determined, the steady state deviation in
frequency from the initial steady state produced by a changing in power ∆P can be calculated
as follows:
ΔP (17)
Δf = − [Hz]
BPS
It is worth noticing that frequency deviation ∆f refers to the new steady state (i.e. new
constant value) the system frequency has reached after a transient change in power ΔP, as
depicted in Figure 19. During the first seconds of the transient change ΔP, the frequency
deviation typically gets higher values.

3.3 Result of changing the droop or the power setpoint of a unit


Figure 18 illustrates the implication of changing the droop or the power setpoint of a unit.

f [Hz] f [Hz]

R2 >R1 R2 =R1

fn fn
∆f 1 2
1
2
∆P1

∆P2 ∆Pref

0 Pref P [MW] 0 Pref1 Pref2 P [MW


a) b)

Figure 18: Implication of changing the droop or the power setpoint of a unit.

Notice in Figure 18a), that the higher the droop R, the less responsive the generating unit
is to changes ∆f in frequency, namely the change in production ∆P of a unit with a droop
characteristic with a higher droop R2 is smaller than that for a unit with a droop characteristic
with a smaller droop R1, i.e. ∆P2 < ∆P1. The change in production ∆P of a unit refers here to the
new steady state power the unit should reach in order to compensate for the frequency change
in the system.
Figure 18b) illustrates that a change in the power setpoint Pref of a unit implies that the unit
runs on a parallel droop characteristic (i.e. R1=R2).
It has already been mentioned in the abstract that the attention of this report, as the frame
of the present course, is directed specially towards primary control action of generating units,
namely the frequency droop control loop.
Generating units providing primary control in the power system are characterised by a fixed
power setpoint Pref , namely they are producing power only according to one droop
characteristic. This means that in primary control ∆Pref=0.
In Section 1.3, it has been illustrated that during primary control, following a change in load,
the frequency in the system does not return to its initial steady state. In order to force the
frequency to return to the initial steady state, the power setpoint and thus the droop
characteristic of the unit must be shifted (as for example illustrated in Figure 18b), from position
1 to 2. It is said that a generating unit having this ability participates in the secondary control of
the system. In secondary control a unit has to produce more at the same frequency. This means

DTU Wind Energy E-0103 21


that the power setpoint of the unit has to be changed, i.e. ∆Pref ≠0, and that the droop
characteristic of the unit has to be moved upward, as shown in Figure 18b. Notice that no
change in power setpoints can force a unit to exceed its nominal power. As a conclusion, the
power output of a generating unit at a given frequency can be modified by adjusting its power
setpoint Pref, which has as result the shifting of the droop characteristic.
Remark that both terminologies described in this section, i.e. droop R and power setpoint
Pref, are essential for describing precisely the operation of a generating unit. It is thus not
sufficient to have given the droop value only for a generating unit, but also its power setpoint
value Pref, i.e. to know how much the unit has to produce at the nominal frequency.

3.4 Unit response to changes in frequency in an infinite power system


If a unit is connected to a large interconnected system, it can be modelled, as it is connected to
an infinite power system. In such system the outputs of the unit are locked to the system values
and they cannot be changed by any action on the unit. Hence the infinite power system dictates
the frequency, while the unit only controls its power (not also the frequency).
Figure 19 illustrates the time response of a generating unit, when the frequency decreases
suddenly in the infinite power system due to e.g. an increase in load. The turbine governor
opens the main control valves to increase the flow of working fluid through the valve to the
prime mover (turbine) and so it increases the turbine mechanical power output. The unit
increases thus its production, as result of the decrease in the frequency. Notice that the system
reaches another steady state lower than the nominal one, after the power output of the
generating unit has been increased with ∆P.

fn
∆f

Pm

∆P
Pm0

time

Figure 19: Time response of a unit when the system frequency drops.

Figure 20 illustrates how the generator output slides back and forth along the droop
characteristic in the attempt to stabilise supply and demand, when changes in frequency occur
in the system, i.e. generator production is reduced when the frequency in the system is
increasing and vice-versa.

22 DTU Wind Energy E-0103


f f

A
fA
fn
∆f N fn N
∆f C C
fC
∆f D
fD D

∆PA ∆PC
P P
PA Pref Pn Pref PC Pn
a) b)

Figure 20: Unit response to frequency changing:


a) increase in frequency b) decrease in frequency

Notice in Figure 20b), that if the frequency decreases even lower than the frequency value
corresponding to full load operation, the generating unit comes in a limited power production
situation (as it is for example the operation case D). In point D the unit is operating at its upper
power limit and has therefore no ability to further compensate for deviations in frequency. The
frequency bias of the generating unit in this situation is equal to zero. Notice thus that the
frequency bias of the whole system is dependent on the number of units, which are not
operating at full load.

3.5 Load sharing in island power system


All generating units connected to a power system operate at the same frequency. They share
and supply any load change in the power system according to their droop characteristic. Figure
21 illustrates a load share example between two units for a sudden increase in load.

f [Hz] f [Hz]
Unit1 Unit2

fn
∆f
f’

∆P1 ∆P2

P [MW] P [MW]
0 Pref ,1 P1 0 Pref , 2 P2

Figure 21: Load sharing example between two parallel generating units.

The two generating units are initially at nominal frequency fn, with power outputs
corresponding to their power setpoints Pref,1 and Pref,2, respectively. Notice that an increase in
load causes both units to slow down (as the frequency decreases) and to increase their power
output according to their droop characteristic. A new steady state operating frequency f’ is
established by both units corresponding to a new balance between generation and demand.
The change in generated power of the two units is then:

∆P1 = P1 − Pref ,1 = − B1 ⋅ ∆f
(18)
∆P2 = P2 − Pref , 2 = − B2 ⋅ ∆f

Notice that the change in the generated power of the two units is, as expected, proportional
with their frequency bias, namely their ability to react and compensate for frequency deviations:

DTU Wind Energy E-0103 23


∆P1 B1 Pn ,1 R2
= = ⋅
∆P2 B2 R1 Pn , 2 (19)

This expression shows that the change in the generated power of two units with equal
nominal powers (Pn,1=Pn,2) is inverse proportional to their droops. This implies also that when
the generators have equal droops, the generators share the total load in proportion to their
nominal powers:
∆P1 Pn1
=
∆P2 Pn 2 (20)

In a power system with Nunits generating units:


• The overall change in the total generated power in the system ∆PgenPS caused by a
deviation in frequency ∆f, can be calculated as the sum of changes in power in all units,
as follows:
N units N units N units N units
∆PgenPS = ∑ ∆Pi =
i =1
∑ ( Pi − Pref ,i ) =
i =1
∑ Pi −
i =1
∑P
i =1
ref ,i (21)
N units
= −∆f ⋅ ∑ Bi
i =1

• The total generated power PgenPS can be expressed as follows:

N units N units N units N units


PgenPS = ∑ Pi =
i =1
∑ ( Pref ,i +∆Pi ) =
i =1
∑ Pref ,i +
i =1
∑ ∆P
i =1
i (22)
N units N units
= ∑ Pref ,i − ∆f ⋅ ∑ Bi
i =1 i =1

The system frequency reaches steady-state at a value that corresponds to the situation
when power production (sum of power for on-line units MW) is equal to the system load
(demand MW):

PgenPS = PloadPS (23)

4. Modeling representations
In this chapter different modeling representations, typically used in the electric power system
literature, are described. Per-units and delta models are presented and exemplified. Some
basics of Laplace transform are reviewed and an overview of its use in dynamic system analysis
is given.

4.1 Per-unit representation


The per-unit system, mostly used in the electric power systems literature, is a scaling
procedure, which normalizes the value of a variable with a corresponding base value.

24 DTU Wind Energy E-0103


Essentially, the idea of per-unit system is to express the value of a physical variable as
percentage of its corresponding base value [1].
The per-unit value xpu of a certain quantity x can be calculated as follows:
x
x pu = (24)
xbase
where xbase is the base value and x is the value in physical units. The base value is a
normalization factor. For a principal variable the base value is typically chosen so that its per-
unit value is equal to one under rated conditions. In other words this means that in the per-unit
system, 1pu corresponds to 100%.
The base value has always the same unit as the physical value and therefore the per-unit
value is dimensionless. For the variables where the base values are chosen independently (i.e.
power, frequency), the per-unit value xpu is typically in the interval 0 ≤ xpu ≤ 1 (e.g. for power
varying from 0 to 100 %) or close to 1 (e.g. for frequency or rotational speed). For other
variables like inertia and angular momentum, where the base values are calculated based on
interrelated quantities, per-unit values can be much bigger than 1. Furthermore some other
variables are typically maintained in the physical units, e.g. phase angle (rad).
Table 2 provides an overview on the typical base value and on the calculation of per-unit
value for different common quantities like: power, frequency, speed, torque, angular
momentum, moment of inertia and damping. Notice that some base values in Table 2 are
chosen independently (e.g. power and frequency), while other are defined directly based on
relationships between interrelated quantities (e.g. torque, angular momentum, moment of
inertia) 12.
As shown in Table 2, the base value for the torque is calculated in the similar way as the
base value for the angular momentum:
Pbase
Tbase =
ωbase
(25)
Pbase P
M base = = base as sbase = 1
sbase ⋅ ωbase ωbase
eventhough their units are different, namely [kg m2/s2] for torque and [kg m2/s] for angular
momentum. The reason for this is that the unit for the base value of Laplace frequency operator
s is [s-1].

12
A selection of two independent base values is typically enough to determine the base values of the others.

DTU Wind Energy E-0103 25


Table 2: Base and per-unit values.

Variable name Base value Per-unit value


Power P
P Pbase = nominal power Ppu =
Pbase
[W=kg m2/s3]
Frequency
50Hz in Europe
f
f f base = f 0 =  f pu =
60Hz in USA f base
[Hz]
Speed ω
ω ωbase = 2 ⋅ π ⋅ f base ω pu =
ωbase
[rad/s]
Torque Pbase T
Tbase = T pu =
T ωbase Tbase
[kg m2/s2]
Time t
t pu = =t
t tbase = 1 tbase
[s]
Laplace frequency
s
(operator) sbase = 1 s pu = =s
s sbase
[s-1]
Angular momentum Pbase M
M base = M pu =
M ωbase ⋅ sbase M base
[kg m2/s]
Moment of inertia M base Pbase I
I base = = I pu =
I ωbase (ωbase ) 2 ⋅ sbase I base
[kg m2]
Inertia constant H
H pu = =H
H H base = 1 H base
[s]
Damping Pbase D
Dbase = = Tbase D pu =
D ωbase Dbase
[kg m2/s2]

Table 3 contains basic formulas for power and angular momentum, used in physical, base and
per-unit calculations.

Table 3: Examples of physical, base and per-unit relations.


Physical relations Base relations Per-unit relations

P = T ⋅ω Pbase = Tbase ⋅ ωbase Ppu = T pu ⋅ ω pu


M = I ⋅ω M base = I base ⋅ ωbase M pu = I pu ⋅ ω pu

Notice that each generation unit in a power system may have its own individual base
corresponding to its own technology. The summation of the power generated by all the units in

26 DTU Wind Energy E-0103


the system is typically performed using a common base 13. A power system base is usually used
as common base. By definition, in this report, the power system base is considered to be the
power capacity of the whole system.
As mentioned previosly, a per-unit value can be in general calculated referred to an
individual (local) base or to a global base. The calculation of a per-unit value for a quantity (like
power, torque or inertia) in a new base x new
pu
_ base
, based on its per-unit value in an old base

x old
pu
_ base
, can be calculated according to:

x Pold _ base
x new
pu
_ base
= = x old
pu
_ base
⋅ (26)
xnew _ base Pnew _ base

where Pold _ base and Pnew _ base are the old and the new considered power bases, respectively.

In spite of its abstractness, per-unit system offers some advantages like:


• Computational simplicity for both manual and automatic calculations, by
eliminating units and expressing quantities as dimensionless ratios.
• Quick evaluation and understanding of the system condition, i.e. the per-unit or
percentage value of a certain variable contains more information than its
corresponding physical value. For example, if a power plant unit is set to produce
0.8pu, it means that the power plant unit has to produce 80% of its nominal/base
value. The per-unit value may also convey a message whether the value is or is
not an acceptable value.
• Easy comparison between power plants with different ratings or speeds of
generators with different number of pole-pairs.

In the following, some examples are given on how to calculate per-unit values for different
quantities.

4.1.1 Calculation of power in per-unit


The power in per-unit is calculated as:
P
Ppu =
Pbase (27)

where P is the power expressed in physical units (W), while Pbase is the power base which is
typically defined equal to the nominal power (i.e. maximum possible continuous power). This
means that the power per-unit value is equal to one at rated conditions (Ppu=1 when P=Pn).
As mentioned previously, a per-unit value can be in general calculated referred to an
individual (local) base, or to a global (common) base, as for example the power system base.
The power base Pbase,i of an individual unit i is typically defined as: Pbase ,i = Pn ,i , namely
equal with the nominal power Pn,i of the individual unit i, while the power base for the whole
power system PbasePS is typically defined as the total sum of the individual nominal powers of all
units in the system, i.e. the system installed capacity:
N units N units
PbasePS = ∑P
i =1
n ,i = ∑P
i =1
base ,i (28)

13
Individual machines can be typically treated using their own base system. However, the quantities of all components
in the system are scaled to a common new base when the whole power system has to be analysed.

DTU Wind Energy E-0103 27


4.1.2 Calculation of speed in per-unit
The electrical speed in per-unit is calculated as:
ω (29)
ω pu =
ω base
where ω is the speed expressed in physical units, while ωbase is the speed base, which is
typically defined thus that the per-unit value is equal to one under normal conditions, namely
ωpu=1, when the speed is equal to the synchronous electrical angular speed ω=ωe0=2⋅π⋅f0.
The speed base for the whole power system is typically defined as illustrated in Table 2:
ω base, PS = 2 ⋅ π ⋅ f 0 (30)

Notice that speed in per-units is equal with frequency in per-units:


ω 2 ⋅π ⋅ f
ω pu = = = f pu
ω base 2 ⋅ π ⋅ f 0 (31)

In order to calculate the base and the per-unit value of a generator speed, it is necessary to
use the expression used in Section 2.1.2 for the generator speed, which expresses the
generator speed depending on the electrical angular speed ωe0 and on the number of pole-pairs
NPP. The base and the per-unit value of a generator speed can be thus calculated as follows,
respectively:
ω base, PS 2 ⋅π ⋅ f0
ω gen,base = = (32)
N PP N PP
ω gen
ω gen, pu =
ω gen,base

4.1.3 Calculation of torque in per-unit


The torque in per-units is calculated as:
T
T pu =
Tbase (33)

where T is the torque expressed in physical units, while Tbase is the torque base defined based
on relationship between the interrelated quantities power and speed:
Pbase
Tbase =
ω base (34)

The torque in per-units can be then calculated as:


T P ω Ppu
T pu = = ⋅ base =
Tbase ω Pbase ω pu (35)

The torque base of a unit i using the individual unit base or the power system base,
respectively, is calculated as:

28 DTU Wind Energy E-0103


Pbase,i
Tbase,i =
ωbase,i
(36)
PbasePS
TbasePS ,i =
ωbase,i
Similarly, the generator torque base and per-unit value can be expressed as:
Pgen ,base Pn
Tgen ,base = = ⋅ N pp
ω gen ,base ω base ,PS (37)

Tgen
Tgen , pu =
Tgen ,base

where Pn is the nominal power of the generator.

4.1.4 Calculation of moment of inertia in per-unit


Inertia is a very important parameter for the frequency control in the power system. The larger
system inertia is, the smaller the frequency rate-of-change following a power imbalance is.
The moment of inertia in per-units is calculated as:
I
I pu =
I base (38)

where I is the inertia expressed in physical units, while Ibase is the inertia base defined as:

M base Tbase T P
I base = = = base = base 2 (39)
ω base sbase ⋅ ω base ω base (ω base )
where sbase=1 [s-1], as shown in Table 2.
The inertia base of a unit i using the individual unit base or the power system base,
respectively, is calculated as:
Pbase,i
I base,i =
(ωbase,i ) 2 (40)

PbasePS
I basePS ,i =
(ωbase,i ) 2

Similarly, the generator inertia base and per-unit value can be expressed as:
M gen ,base Pgen ,base Pn
I gen ,base = = = ⋅ ( N pp ) 2
ω gen ,base ( ω gen ,base ) 2
( ω base ,PS ) 2

I gen
I gen , pu =
I gen ,base
where Pn is the nominal power of the generator.

DTU Wind Energy E-0103 29


4.1.5 Calculation of angular momentum in per-unit
The angular momentum in per-units is calculated as:
M
M pu =
M base (41)

where M is the angular momentum expressed in physical units, while Mbase is the base of
the angular momentum. The expression can be further extended as follows:
M I ⋅ω
M pu = = = I pu ⋅ ω pu
M base I base ⋅ ω base (42)

Notice that the angular momentum is variable with speed, while inertia is a constant
variable. Assuming now small variations in speed (to make possible the linearization of
differential equation of EoM), as it is the case for synchronous generators in conventional power
plants, it means that:
ω ≈ ω e 0 = const → ω pu ≈ 1 → M pu ≈ I pu (43)

The per-unit expression of the angular momentum can be approximated to be equal with
the per-unit value of the inertia.

4.1.6 Calculation of inertia constant in per-unit


Inertia constant H is defined as the ratio of stored kinetic energy at rated (nominal) speed
to the rated power:

1 2
Iω n
[sec]
2 (44)
H=
Pn
Notice that the inertia constant is expressed in seconds. An inertia constant of 4 seconds
means that the energy stored in the rotating part could supply the nominal load during 4
seconds.

The inertia constant in per-units is calculated as:

H
H pu = =H
H base (45)

where H is the inertia constant expressed in physical units, while Hbase is the inertia base and it
is equal to 1. The expression of the inertia constant in per unit can be further expressed as:
1 Iω
2
1 I 1 1
H pu =H = ⋅ n = ⋅ = ⋅ I pu = ⋅ M pu (46)
2 Pn 2 I base 2 2
The angular momentum in per-unit Mpu can be then expressed as:

M pu = 2 ⋅ H pu (47)

30 DTU Wind Energy E-0103


4.2 Delta representation
Delta representation is another modelling approach often applied together with per-unit
representation in electrical systems literature. It is typically used to describe deviations of
quantities from initial steady-state values [6].
The idea of delta representation is that any variable x can be expressed at any moment t
as the sum of its initial value denoted by x0=x(0) and a small deviation ∆x(t) from its initial value,
as follows:
x( t ) = xo + ∆x( t ) (48)
with the condition of course that in the steady state initial condition the deviation is zero, i.e.
∆x( 0 ) = 0 .
The delta model can then be expressed as:
∆x( t ) = x( t ) − xo and ∆x( 0 ) = 0 (49)
Notice that delta models are very convenient to use, as their states do not need to be
initialised, since they start automatically in zero.

In the following a small example is given on how to calculate the delta model for the equation of
motion (EoM), described in Section 1.4.

4.2.1 Equation of motion – delta representation example


Consider the equation of motion (EoM) expressed in power, as described in Section 1.4:
dω dω
Pmech − Pelec = Iω =M
dt dt (50)

Suppose that the variables of EoM can be expressed as the sum of their initial value (i.e.
Pmech0 for Pmech) and a small variation (i.e. Pmech for ∆Pmech), as follows:
Pmech = Pmech 0 + ∆Pmech (51)
Pelec = Pelec 0 + ∆Pelec
ω = ω 0 + ∆ω
By applying the superposition principle, the equation can be then rewritten like:
d
∆Pmech − ∆Pelec + ( Pmech 0 − Pelec 0 ) = I (ω 0 + ∆ω ) (ω 0 + ∆ω )
dt (52)

Notice that the steady state quantities can be factored out, since:
Pmech 0 = Pelec 0
dω 0 (53)
=0
dt
and further assuming small deviations in speed, the terms involving products of ∆ω with
d
(∆ω ) can be neglected. The power balance equation can then be approximated as:
dt

d d
∆Pmech − ∆Pelec ≈ Iω 0 ∆ω = M 0 ∆ω
dt dt (54)

DTU Wind Energy E-0103 31


This delta representation of EoM is going to be used in Section 5.1 as the basic
formulation of a generator model.

4.3 Dynamic modelling in frequency domain (Laplace transform)


Understanding dynamic systems in Laplace and time domains is extremely important in the
study of process dynamics and control. Dynamic system modelling in frequency domain, using
Laplace transform, is often used in the analysis of continuous time dynamical systems. It is not
the scope here to describe Laplace transform in details, as it can be found in relevant literature.
The chapter focuses on the application of Laplace transform in analysis of process dynamics.
The transfer function of a dynamic system is also addressed.

4.3.1 Linear time domain modelling


Any dynamic linear system can be completely characterized in time domain by its impulse
response. This means that for any input function x(t) of the system, the output function y(t) of
the system can be calculated in terms of the input x(t) and the impulse response h(t).
The impulse response h(t) of a dynamic system is defined as the output of the system,
when it has as input an impulse δ(t). The impulse δ(t) can be modeled as a Dirac delta function
for continuous time, as follows:
0 for t ≠ 0 ∞ (55)
δ (t ) = 
∞ for t = 0
and ∫−∞
δ (t )dt = 1

The Dirac delta function δ(t) is roughly speaking, a pulse of unbounded amplitude and zero
duration.
The output of the system y(t) is then determined by the input x(t) according to the
convolution defined as follows:
t
y (t ) = y (t 0 ) + ∫ h(t − τ ) x(τ )dτ (56)
0

Notice thus that output y(t) of a linear system in time domain requires the convolution of the
input x(t) with the impulse response function h(t). The convolution technique,
described in more details in [7], is based on a decomposition of the input signal x(t) into
impulses, while the output y(t) is expressed as a sum of the responses resulting from the
individual impulses.
The calculation of the output of the system in time domain is quite difficult and it requires
the use of integrals. The calculation is much easier to perform in Laplace domain, where the
convolution turns into a simple multiplication of two algebraic functions.

4.3.2 Formal definition and characteristics of Laplace transform


The Laplace transform of a function f(t) is represented by a continuous sum of exponential
functions of the form e-st, where the operator ‘s’ is defined as a complex frequency 14, namely:

F ( s ) = L{ f (t )} = ∫ f (t ) e − st dt (57)
0

14
The Laplace operator s, already mentioned in Table 2, is a complex variable. It is defined as s≡ơ+jɷ. For the analyse
of the frequency response in steady state, s≡jɷ is used.

32 DTU Wind Energy E-0103


where L{.} is used to denote Laplace transformation. The function f(t) is a function of time, s is
the Laplace operator, and F(s) is the transformed function. Notice that the Laplace transform
converts functions with a time dependent variable into functions with a complex dependent
variable, such as frequency (known as Laplace frequency), represented by operator ‘s’.
Table 4 contains the most fundamental properties of Laplace Transforms. More
comprehensive lists of Laplace transforms may be found in numerous control literatures e.g. [7].

Table 4: Some Laplace properties and transforms.

Time domain Laplace domain


f (t ) F (s)
x(t ) + y (t ) X (s) + Y (s)
k f (t ) k F (s)
df (t ) / dt s F ( s ) − f (0)
d n f (t ) / dt n s n F ( s ) − s n −1 f (0) − s n − 2 f 1 (0) −  − f n −1
(0)
t

∫ f (t )dt
0
F (s) / s

1 ( step ) 1/ s
t 1/ s2
e − at 1 /( s + a )
f (t − a ) e − as F ( s )

Notice that operation such as differentiation and integration in time domain can also be
replaced by simple algebraic operations in Laplace domain.
Laplace transform is used extensively in electrical engineering. Laplace transform is for
example a strong technique to solve linear differential equations, as it overcomes some of the
complexities encountered in the time domain solution of differential equation. Laplace transform
is used to transform time domain relationships to a set of equations expressed in terms of the
Laplace operator ‘s’. Thereafter, the solution of an original problem can be found by simple
algebraic manipulations in the Laplace domain rather than the time domain. To return to the
time domain from the Laplace domain, the inverse Laplace Transform L-1 is used [7].

Example of solving differential equation using Laplace transform


Consider the linear differential equation to be solved:
f( t ) + 8 f ( t ) + 15 f ( t ) = 1
with initial conditions f ( 0 ) = f ( 0 ) = 0

Applying Laplace transform:

{ }
L f( t ) + 8 f ( t ) + 15 f ( t ) = 1 ⇒ s 2 L{ f ( t )} + 8sL{ f ( t )} + 15 L{ f ( t )} = 1

DTU Wind Energy E-0103 33


as L{ f ( t )} = F ( s ) then the equation can be written as:

s 2 F ( s ) + 8 s F ( s ) + 15 F ( s ) = 1
This can be further written and decomposed as:

1 0.5 0.5
F( s ) = = −
s + 8s + 15 s + 3 s + 5
2

Applying the inverse Laplace transformation, the solution of the differential equation can be then
found as follows:

f ( t ) = 0.5e −3t − 0.5e −5t


Notice that the condition f(0)=0 is also satisfied.

4.3.3 Transfer function of a linear system


In system analysis, the Laplace transform is seen as a transformation from the time domain, in
which inputs and outputs are functions of time, to the frequency domain, where the same inputs
and outputs are functions of operator ‘s’ (complex frequency). Laplace transform provides thus
an alternative functional description that simplifies the process of analysing the behaviour of the
system.
Figure 22 sketches graphically how the Laplace transform can be used to transfer a time
domain modeling into frequency domain modeling and back again.

x(t) y(t)
Time domain h(t)

∆x(t ) = x(t ) − x(t 0 ) y (t ) = ∆y (t ) + y (t 0 )

Δ x(t) Δy(t)
h(t)

∆X ( s ) = L{∆x( t )} ∆y( t ) = L-1 {∆Y ( s )}

Δ X(s) Δ Y(s)
Laplace domain H(s)

Figure 22: Application of Laplace transform.

Notice that in order to make the transformation from time domain in frequency domain, it is
preferable to work with delta values, i.e. ∆x(t), because in this way the initial value of the
variable x is automatically included in the analysis. The dynamic of variable x is the same as
the dynamic of ∆x, if of course initial condition is zero, i.e. x(0)=0.

34 DTU Wind Energy E-0103


As illustrated in Figure 22, the corresponding variables in frequency domain are:
• Input Laplace transform ∆X(s)

• Output Laplace transform ∆Y ( s ) = H ( s ) ⋅ ∆X ( s )


• Transfer function H(s), which fully describes the system dynamic through the relation
between the input ∆X(s) and the output ∆Y(s), as follows:
∆Y ( s )
H( s ) =
∆X ( s ) (58)
The transfer function H(s) is thus the Laplace transform of the impulse response function
h(t). It is a linear function and ratio of polynomials in ‘s’. The Laplace transform of a system’s
output can thus be determined by the multiplication of the transfer function with the input
function the Laplace domain. The output function in time domain may be then calculated by
applying the inverse Laplace transform.
As illustrated in Figure 22, the transfer function shows the flow of signal through a system,
from the input to the output, describing thus the dynamics in operational sense.
The general procedure to find the transfer function from input to output of a system
modeled by a linear differential equation is to apply the Laplace transform on both sides of the
differential equation and to solve for the ratio of the output Laplace over the input Laplace.
Transfer functions play a central role in the analysis of a dynamic system, because it is
usually easier to analyze systems using transfer functions instead of impulse response
functions.

Example of first order differential system


Consider a linear system characterized by the following differential equation:
d y (t )
x(t ) = a + b y (t )
dt
0 for t < 0
where the input signal is x(t ) = 
1 for t ≥ 0
The output y(t) of the system to the input x(t) is determined by applying Laplace transformation.
Based on formulas presented in Table 4, the differential equation can be expressed in Laplace
domain as follows:

∆X ( s ) = a s ∆Y ( s ) + b ∆Y ( s )
The transfer function of the system is then given by:
∆Y ( s ) 1
H( s ) = =
∆X ( s ) a s + b

By using further the notation k=1/b and τ=a/b, the transfer function can also be expressed as:
k
H( s ) =
τ s +1

DTU Wind Energy E-0103 35


k is the final value, while τ denotes typically the time constant. Based on Table 4, the output y(t)
of the system in time domain can be then expressed and illustrated as in Figure 23.
4.3.4 Block diagram of a system

τ y(t)
  t 
y (t ) = k 1 − exp −   x(t)
  τ 

Figure 23: Output of a first order system at a step input.


Using block diagram is another way to represent dynamic systems pictorially. Each block
represents a transfer function, while the signal flow between the blocks is illustrated by the block
connections.
Dynamic systems can thus be easily visualized through block diagrams. Figure 24
illustrates examples for three basic arrangements of transfer functions and their respective
equivalent transfer functions. Notice that transfer functions can consist of combinations of other
transfer functions.

Block diagram Equivalent transfer function

∆X(s) ∆Y(s) ∆Y ( s )
H(s) G(s) F( s ) = = H ( s )G( s ) a)
∆X ( s )
F(s)

H(s)
∆X(s) + ∆Y ( s )
∆Y(s)
F( s ) = = H ( s ) + G( s ) b)
+ ∆X ( s )
G(s)
F(s)

∆X(s) + ∆Y(s) ∆Y ( s )
H(s) F( s ) =
- ∆X ( s )
c)
H( s )
=
G(s) F(s) 1 + H ( s )G( s )

Figure 24: Three basic arrangements of transfer functions:


a) in series b) in parallel c) in feedback form

4.3.5 Initial and final value theorems


Initial and final value theorems, illustrated in Figure 25, permits one to calculate the output of a
dynamic system approached at time t=0, i.e. y(0), and after very long time t, i.e. y(∞),
respectively, for a certain input x(t), directly from the transfer function H(s), without the need of
applying inverse Laplace transform.

36 DTU Wind Energy E-0103


Initial Value Theorem Final Value Theorem

y( 0 ) = lim y( t ) = lim s ∆Y ( s ) y( ∞ ) = lim y( t ) = lim s ∆Y ( s )


t →0 s→∞ t →∞ s→0

Figure 25: Initial and final theorems.

Example for initial and final value theorem of first order differential system
Consider a dynamic system with the following transfer function:
1
H( s ) =
2s + 1

If the input ∆X(s) into the system is a step function, the output of the system ∆Y(s) can be then
calculated as:
1 1 1
∆Y ( s ) = ⋅ ∆X ( s ) = ⋅
2s + 1 2s + 1 s
Applying now the initial and final value theorem the value of the output y(t) in time domain in the
initial and final moment is as follows:

This result means that by applying a step signal as input to this dynamic system, the output will
start from zero and it will converge to one after a while.

5. Dynamic models in frequency control loop


In this chapter, a basic dynamic frequency model for island power systems is introduced. It is
based on simple models for the equation of motion, prime mover, governor and load. The
frequency dependent loads, which have a stabilizing effect on the frequency, are also modelled.

Having so far described the fundamentals of the frequency control, it is now possible to model
the frequency control loop. Such a model can be used to simulate the response of an island
power system to a power imbalance caused, for example, by the tripping of a large generating
unit.
Figure 26 sketches the block diagram of the frequency control loop. Models for the
following components are considered:
• Equation of motion 15
• Load

15 Equation of motion (EoM) includes in general both generators and rotating load. However, in an island power
system, it can be assumed that all the inertia is given by the generators.

DTU Wind Energy E-0103 37


• Prime mover
• Governor

Notice that the model illustrated in Figure 26 is in per-unit and delta representation. Therefore
all the models described from now on are going to be in per-unit and delta representation.
∆Pelec
Load

∆Pref ∆Pfuel Prime ∆Pmech + – Equation of ∆ω


Governor
mover motion

Figure 26: Frequency control loop model (delta and per-unit).

5.1 Generator model (equation of motion EoM)


As already mentioned, the equation of motion (EoM) is expressed as follows [1]:

Tmech − Telec = I
dt (59)
Any change in the load of the system is instantaneously reflected in the electrical torque
Telec. This generates an imbalance between the mechanical torque Tmech and the electrical
torque Telec, which results further in speed/frequency changes according to the dynamics of the
equation of motion. As shown in Section 1.4, the equation of motion can be expressed in terms
of mechanical and electrical power, as follows:

Pmech − Pelec = M
dt (60)

As presented in Section 4.2.1, assuming very small variations in frequency, i.e. frequency
almost constant (ω=ω0), the generator model can be simple expressed as:
d
∆Pmech − ∆Pelec = M ∆ω
dt (61)

This can be further rewritten in the Laplace domain as:

∆Pmech − ∆Pelec = M s ∆ω (62)

where ‘s’ is the Laplace operator. The equation of motion can be further expressed as:

1
∆ω = ( ∆Pmech − ∆Pelec ) (63)
Ms

This expression is graphically sketched in Figure 27.

38 DTU Wind Energy E-0103


∆ Pelec

+ 1 ∆ω
∆ Pmech Ms

Figure 27: Generator model (delta and per-unit).

where ∆Pmech is the mechanical power from the prime mover, while ∆Pelec is the electrical power
consumed by the loads in the system.

5.2 Load model


In general, the loads in a power system consist of different types of devices. They can be:
• frequency-dependent loads, as i.e. motors, fans, pumps
• frequency-independent loads, as i.e. lights, heaters, computers.

The total load in a power system can therefore be modelled as follows:

∆Pelec = ∆PL + D ⋅ ∆ω (64)

where:
• ∆PL represents the frequency-independent load
• D⋅∆ω represents the frequency-dependent load
• D is known as the damping constant and in a per-unit model it is expressed as a
percent change in load for one percent change in frequency 16.

It is worth noticing that the frequency dependent loads, as i.e. motors in the power system,
have a beneficial influence on the power system [1]. They have a stabilizing effect on the power
system during a frequency drop 17.

The block diagram for a dynamic model of a load is presented in Figure 28.

∆ω + ∆ Pelec
D
+

∆ PL
Figure 28: Load model (delta and per-unit).

By combining now the generator model (EoM), shown in Figure 27, and the load model,
presented in Figure 28, the following expression of the system frequency can be obtained:

16
For example a value of D=2, means that a 1% change in frequency implies a 2% change in load.
17
A frequency drop means that the frequency dependent load also decreases. This load reaction adjusts the
momentary unbalance between production and consumption and transforms it into a new balanced situation, where the
frequency is stabilised at a new value.

DTU Wind Energy E-0103 39


1
∆ω = (∆Pmec − ∆PL )
Ms + D (65)

This represents the integrated EoM and load model. Notice that, in the absence of the
governor to control the speed ∆ω, the system response ∆ω to any change in load ∆PL is
dependent only on the total angular momentum M and the damping constant D existing in the
system.
The integrated EoM and load model is shown in the cascade form in Figure 29a. This form
can be further rearranged in the equivalent transfer function form shown in Figure 29b.

∆ PL
+ +
D ∆ Pmech +
1 Δω
∆ Pelec -
Ms + D

+ 1 ∆ω ∆ PL
∆ Pmech Ms

a) b)

Figure 29: Integrated EoM & load model (delta and per-unit).

Typically more than one generator and load are connected to a power system. The
collective performance of all generators in the system is in general analysed by assuming that
they all operate synchronously at the same constant frequency. Using this assumption, all
generators can be then represented by an equivalent lumped generator driven by the sum of all
individual prime mover mechanical outputs [6], as illustrated in Figure 30.
The equivalent angular momentum Msys of the system is then equal to the sum of the
angular momenta of all generators (rolling inertia) and spinning loads connected to the system.
It is worth noticing that, besides frequency dependent loads 18, in a power system there are
different devices, which through their control system contribute actively and largely to the total
damping in the power system Dsys.

∆Pmech1
+
∆Pmech2 + 1 Δω
 + - M sys s + Dsys
∆PmechN

∆ PL
Figure 30: System equivalent with lumped angular momentum and lumped damping constant
(delta and per-unit).

18
Frequency dependent loads are not controllable, namely their damping contribution is passive.

40 DTU Wind Energy E-0103


Example of system parameter calculation
A power system consists of two generating units and each of them has a nominal capacity of
100MW. The system has a total load of 105 MW at 50Hz. Each generating unit has an inertia
constant 19 of 1 p.u. calculated in 100 MW base. For every 1% change in frequency the
corresponding variation of the load is 1.2%. If there is a sudden drop in load by 5 MW:
(a) Build the block diagram of the system expressed on 200 MW base
(b) Calculate the corresponding frequency variation

The power system calculations in per-unit are typically done using the total system power base,
which is defined as the total nominal capacity of all generating units installed in the system. In
this exercise the total system power base is therefore 200MW.
The calculation of the per-unit value for the inertia constant on the 200MW base can be done
based on its per-unit value on the 100MW base, using the formula indicated in equation 26:
100 100
200 MW base
H unit = H unit
100 MW base
× = 1× = 0.5
200 200
The per-unit value on 200MW base of the inertia constant for the power system consisting of
the two generating units can be then calculated as follows:

H = 2 × H unit
200 MW base
= 2 × 0.5 = 1
The angular momentum in per-unit on 200MW base can be then expressed as:

M = 2×H = 2
For the load after the change (105-5=100 MW) on 200 MW base,
100
D =1.2 × =0.6
200

The block diagram would be:

And expressed in standard transfer function form (see also section 4.3.3):

The parameters (gain and time constant) can be calculated according to the following:

19
Definition in equation 44, page 28.

DTU Wind Energy E-0103 41


1 1
=
k = = 1.67
D 0.6
M 2
τ = = 3.33
=
D 0.6

The load deviation is:


5
∆PL =−5MW =− =−0.025 pu
200

For the reduction in the load, the Laplace transformation of the change is (see also section 4.3):
0.025
∆PL ( s ) =

s

Therefore,
 −0.025  k  ℑ
−1

∆ω ( s ) =
−  ⇒
 s  τ s + 1 
t

∆ω ( t ) =
−0.025ke τ
+ 0.025k
t

=
−0.025 × 1.67e 3.33
+ 0.025 × 1.67
= 0.0418e −0.3t + 0.0418

The pu deviation in the speed is qualitatively shown here:

∆ω
τ = 3.33s

∆ωss =
0.0418

t (sec)

The time constant is 3.33 s and the steady-state speed deviation is

∆P
∆ωss =− L = 0.0418 pu
D
= 0.0418 × 50
= 2.09 Hz

42 DTU Wind Energy E-0103


5.3 Prime mover model
As mentioned in Section 2.2, a prime mover is a turbine, which converts steam energy,
produced by burning some kind of fuel, into mechanical energy. Each turbine consists typically
of a number of stages, where the steam can be reheated. The fuel is supplied through the
governor valve, which controls the frequency by adjusting the fuel infeed flow.
Figure 29 illustrates the simplest dynamic model of a prime mover, corresponding to a non-
reheat turbine (i.e. one turbine stage). It is a first order model with a time constant TCH, known
also as the charging time constant.

∆Pfuel 1 ∆Pmech
1 + sTCH
Figure 31: Prime mover model (delta and per-unit).

The model of a prime mover relates thus the power generated by burning fuel to the output
mechanical power:
1
∆Pmech = ⋅ ∆Pfuel
1 + sTCH (66)

5.4 Governor model


Figure 32 depicts the droop characteristic models for the two types of governors explained in
Section 2.3, i.e. isochronous governor and speed droop governor.

f [Hz] f [Hz]

fn fn

P [MW] P [MW]
0 0
a) b)
Figure 32: Droop characteristic of: a) isochronous governor; b) speed droop governor.

5.4.1 Isochronous governor model


As shown in Figure 32a), an isochronous governor keeps the frequency constant independent
of the generator loading (zero droop).
The model of an isochronous governor is shown in Figure 33:

∆ω  K  ∆ Pfuel
−  KP + I 
 s 
Figure 33: Model for an isochronous governor (delta and per-unit).

DTU Wind Energy E-0103 43


where Kp and KI are the proportional and integral parameters of the controller, respectively.
Notice that the isochronous generator has only as input signal the deviation of the speed ∆ω,
between the measured speed ω and the reference synchronous electrical speed ωe0. This
speed deviation is amplified and integrated to produce the control signal ∆Pfuel, which actuates
the throttle valve of the prime mover. Notice in Figure 34a) that the steady state operation for an
isochronous governor is defined by the condition ∆ω=0.

ω ω
∆ω = 0
ωn ωn
∆ω = − R ⋅ ∆Pfuel

a) b)
Figure 34: Frequency response of a generating unit equipped with:
a) Isochronous governor b) Speed droop governor

5.4.2 Speed droop governor model


As illustrated in Figure 32b), a speed droop governor has a characteristic with a negative slope.
It reacts to load variations by changing its speed, namely it controls the relation between power
and frequency. This means that a higher (lower) power output is established when the
frequency drops (rises).
The model of a speed droop governor is shown in Figure 35.

∆ Pref ─
+
+  K  ∆ Pfuel
R −  KP + I 
+  s 
∆ω
Figure 35: Model for a speed droop governor (delta and per-unit).

where R represents the droop of the characteristic. Notice that the speed droop governor has
two input signals, namely deviation of the speed ∆ω and the deviation of the power setpoint
∆Pref.
The steady state operation for a speed droop governor is defined by the condition:
(67)
∆Pref = 0 ⇒ ∆ω + R ⋅ ∆Pfuel = 0 ⇒ ∆ω = − R ⋅ ∆Pfuel
If frequency drops due to e.g. an increased load, the speed droop governor will yield to an
increased ∆Pfuel which will be order to the prime mover.
Speed droop governors are utilized when multiple generators have to share changes in
load in the power system. For this sharing to be equal the speed droop governors need to have
same droop characteristic.

44 DTU Wind Energy E-0103


5.5 Frequency control loop model
Figure 36 illustrates a simplified model of the frequency control loop in an island power system.
It consists of models for speed droop governor, prime mover and integrated equation of motion
and load model.

Speed Droop Governor Prime mover EoM & Load

∆Pref - + +  K  ∆ Pfuel 1 ∆ Pmech + 1 Δω


R −  KP + I 
 s  1 + sTCH - Ms + D
+
Δω ∆ PL

Figure 36: Frequency control loop model (delta and per-unit).

This model can be used to analyze the response of the frequency control loop to deviations
in speed (frequency) caused by i.e. a sudden disconnection of a large generating unit from the
system or by connecting a large load into the system.

6. Frequency control with wind power


In this chapter, the frequency control loop of an island power system, presented in the previous
chapter, is extended with a simple model of a wind turbine.

Figure 37 shows an overview block diagram of an island power system including speed droop
governor, prime mover, and equation of motion, load and wind turbine model. All generating
units in the system are lumped together as a unique generator (equation of motion), as
explained in Chapter 5.

Speed Droop Governor Prime mover EoM & Load

∆Pref - + +  K  ∆ Pfuel 1 ∆ Pmech 1 Δω


R −  KP + I  Konline +
 s  1 + sTCH ∆ Pwt Ms + D
+ +
∆ PL
Δω -

Δω
Pwtphysical + ∆Pwtphysical wt
vwind Wind turbine K physical 2 pu

-
∆ PL
Pwtphysical
0

Figure 37: Overview of frequency control loop model including wind turbine model
(delta and per-unit).

Notice that, the output of the wind turbine model is added to the mechanical power
produced by the others prime movers in the system. This is because wind turbines are seen as
negative loads, i.e. they produce power and reduce thus the load (demand) in the system,
independently of the system conditions and of the actions of governors and prime movers of the
conventional power stations.
wt
The additional amplification blocks Konline and K physical 2 pu are defined as follows:

DTU Wind Energy E-0103 45


N units

∑k i ⋅ Pn ,i
K online = i =1
N units

∑P
i =1
n ,i
(68)

N
u =
wt wtr
K physical2p N units

∑P
i =1
n ,i

where ki is 1 if unit i is online and 0 if unit i is offline and Nunits is the number of units. The gain
Konline is containing information about how much production capacity is in the system, e.g. how
many units are online or not. Notice that Konline is equal to one, when all the units in the system
are online. It adjusts properly the mechanical power in per-unit (power system base) produced
wt
by the aggregated prime mover model for all units in the system. K physical 2 pu is used to
transform first the wind turbine delta power (physical!) in the delta power of a wind farm
consisting of Nwtr wind turbines and second from physical to per-units system (power system
base). Remark that the power system base is by definition equal with the total power capacity,
namely the sum of nominal power of all units installed in the system no matter whether they are
online or not. Pwtphysical
0 is the wind turbine power in the initial steady state condition.

Figure 38 sketches a more detailed block diagram of the wind turbine modeled. Description
of the aerodynamic model is found in details in [8]. ω gen0
pu
is the generator speed in the initial
steady state condition.

Wind turbine
ω gen0
pu

+
∆ω pu ω gen
pu
ω gen 1 ω wtr
ω gen
base
N gear
Pwtphysical
+

vwind
Aerodynamic
model
θ

Figure 38: Wind turbine model.

References
[1] Kundur P. [1994], Power system stability and control, McGraw-Hill.
[2] https://www.entsoe.eu/the-association/
[3] Søder L. [2002], Explaining Power system operation to nonengineers, Power
Engineering Review, IEEE 22(4), 25-27.
[4] Nordic grid code - Entsoe
https://www.entsoe.eu/fileadmin/user_upload/_library/publications/nordic/planning/070115_e
ntsoe_nordic_NordicGridCode.pdf

46 DTU Wind Energy E-0103


[5] Miller R., Malinowski J. H. [1995], Power system operation, McGraw-Hill.
[6] Wood A.J, Wollenberg B.F. [1996], Power generation, Operation and Control, John
Wiley and Sons.
[7] Ogata K. [2010], Modern control engineering, Prentice-Hall International.
[8] Hansen A.D. [2010], Introduction to wind power models for frequency control
studies.

DTU Wind Energy E-0103 47


DTU Vindenergi er et institut under Danmarks Tekniske Universitet med en unik integration af forskning, uddannelse, innovation og
offentlige/private konsulentopgaver inden for vindenergi. Vores aktiviteter bidrager til nye muligheder og teknologier inden for udnyttelse af
vindenergi, både globalt og nationalt. Forskningen har fokus på specifikke tekniske og videnskabelige områder, der er centrale for udvikling,
innovation og brug af vindenergi, og som danner grundlaget for højt kvalificerede uddannelser på universitetet.

Vi har mere end 240 ansatte og heraf er ca. 60 ph.d. studerende. Forskningen tager udgangspunkt i ni forskningsprogrammer, der er organiseret i
tre hovedgrupper: vindenergisystemer, vindmølleteknologi og grundlag for vindenergi.

Danmarks Tekniske Universitet


DTU Vindenergi
Nils Koppels Allé
Bygning 403
2800 Kgs. Lyngby
Telefon 45 25 25 25

[email protected]
www.vindenergi.dtu.dk

You might also like