Truss Design
Truss Design
PURLINS Instructions
1 LOADING Input Data: Green Cells
1.1 DEAD LOADS (ROOF LOAD) Output Data: Orange Cells
Weight(kg/m)= 3.14
width(m)= 0.782
Weight/width(kg/m/m)= 4.015
Area load(kn/m/m)= 0.039
Terrain category= 4
Kt= 0.24
Zo(m)= 1
Zmin(m)= 16
Roughness coef. Cr(z)= 0.69
2. LOAD COMBINATIONS
Area(mm2)= 209
Truss spacing(m)= 6.4
Weight(kg/m)= 1.64
Purline Depth(m)= 0.25
Purline spacing(m)= 1.2
L(m)= 6.4
-1.077 kn/m
m
d= 0.25
SMa=0=d*T+0.5*Pd*(L/2)2-(L/2)R1=0
Solving the above equation:
T(KN)= 18.35
Lower bound
Roof angle Wind normal to ridge Wind parallel to
approximated, ridge (suction)
deg
Windward Windward Leeward
(pressure)
(suction) (suction)
cpe 5 -1.2 0 -0.3 -0.7
Upper bound
Roof angle Wind normal to ridge Wind parallel to
approximated, ridge (suction)
deg Windward Windward Leeward
(pressure)
(suction) (suction)
cpe 10 -1 0.1 -0.35 -0.75
Interpolation
Roof angle Wind normal to ridge Wind parallel to
approximated, Windward ridge (suction)
deg Windward Leeward
(pressure)
(suction) (suction)
cpe 8 -1.08 0.06 -0.33 -0.73