DESIGN OF GANTRY SUPPORT COLUMN

1. Member Properties
Section size UC 305X305X97 kg/mPlate Thick= 0 mm
Beam dept= 307.9 mm Plate Widt = 0 mm
Beam width = 305.3 mm
Top Flange= 15.4 mm Root radius= 15.2 mm
Bottom Fla= 15.4 mm Depth betwe= 246.7 mm
Web thickn= 9.9 mm Section Mo= 478615 mm3
Sectional a= 12147 mm2 Plastic mod= 724491.9 mm3
Moment of=i 2.19E+08 mm4 Plastic mod= 1565265 mm3
Moment of=i 73060576 mm4 Radius of g= 134.2 mm
Section Mo= 1421668 mm3 Radius of g= 77.6 mm

2. Material Properties
Steel grade= E350 (Fe 490)
Design stre= 350 N/mm2 Elastic mo = 200 kN/mm2
Poisson's r= 0.3
3. Section Classification r1 = Fc/(d x= 1
e = [250/fy= 0.845 r2 = Fc/(Ag= 0.26
Outstand element of compression flange, bWeb , Neutral axis at mid Depth, d/tw
Plastic - 7.9 Plastic - 35.5
Compact - 8.9 Compact - 35.5
Semi-comp- 13.3 Semi-comp- 70.5
Actual b/T = 9.9 Actual d/t = 24.9
Flange is semi-compacClass 3 web is plastic. Class 1

Hence, sectnon-slender The sectionClass 3 OK


Rolled I-Segiven is of BuckliClass b about z-z Axis
Class b about y-y Axis

4. Applied Forces
Bending m= 15.32 kNm Effective l = 1.7 m
Bending Mo = 33.1 kNm Effective le= 1.7 m
Shear Forc= 67.3 kN LLT = 18.58 m
Axial load = 1086.3 kN

5. Moment & Shear Capacity

(I) Shear check (as per cl. 8.4)

Check for sd/tw < 67e Plastic shear resistance is governing


Plastic shear resistance
Vd = fyAv/ 560 kN Shear capacity from plastic shear resistance as per cl. 8.4.1
Av= tfD = 3048 mm2
Vd > V
560 > 67.3 OK.
0.6Vd = 336 kN
0.6Vd > V Low shear, no reduction in moment capacity
β1 = -
Sv = - mm3

(II) Moment check (as per cl. 8.2)


bb = 1
Md = bbfyS 498 kNm, as per cl. 8.2.1.2
Sr = (S-Svb - mm3
Md = fySr/- kNm, for plastic or compact sections as per cl. 9.2.2.a
Md = bbZpf 138.6 kNm, for laterally unsupported beams as per cl. 8.2.2
fbd = cLTf 88.5 N/mm2
cLT = 1/{flt 0.2782 G = 76923 N/mm2
fLT = 0.5[1 2.2334 Mcr = 1.75E+08 Nmm
aLT= 0.21 It = 832980.8 mm4
lLT = √(bb 1.7711 Iw = 1.56E+12
Mcr= bbZpf1.77E+08 Nmm
fcr,b = 1.1 113.2 N/mm2
hf= 292.5 mm bf = 0.5

Md > Mz
138.6 > 33.1 OK Mcr = 0.5p27.54E+09
6). Local Capacity Check (as per cl. 9.3.1)
Moment ca= 498 kNm
Moment ca= 183 kNm
Sectional A= 12147 mm2
Ag fy/gm0 = Cross sectional area x Design strength
= 3865 kN
Interaction expressio N/Nd + My/Mdy + Mz / Mdz ≤ 1
= 0.281 0.084 0.066 = 0.43 OK
7). Overall Buckling Check (as per cl. 9.3.2)

Bending & Axial Compression

Equation 1 P / Pdy KyCmy My / Mdy + KLT


≤ 1

Equation 2 P / Pdz 0.6KyCmy My / Mdy +≤ 1


Compressive strength
l zz = 12.7 OK l yy = 21.9 OK
Euler streng
= 12317.1 N/mm2 Euler streng = 4111.6 N/mm2
Imperfectio= 0.34 Imperfectio= 0.34
f = 0.51 f = 0.56
Effective s = 0.17 Effective s = 0.29
fcd in z-z d= 318.1818 N/mm2 fcd in y-y d= 307.72 N/mm2
Compressive = 3865 kN Compressive = 3738 kN
Kz=1+(lz-0.= 0.99 Ky=1+(ly-0 = 1.02
nz
(CmLT- = 0.281 ny = 0.291
0.25)) = 0.96
lLT = 1.77
Mcr = 1.75E+08 Nmm
Cmz = 1 Cmy = 1 from Table 18 IS 800
CmLT = 1

Equation 1= 0.291 0.09 0.23 = 0.61 OK

Equation 2= 0.281 0.05 0.237 = 0.57 OK