Programmable Fire Alarm Control Panel Series 4010ES (FM Approved)
Programmable Fire Alarm Control Panel Series 4010ES (FM Approved)
Other option modules in addition to the 4010-9929, A010-9929 IDNet 2+2 module, which may be included inside the system consist of a selection of
the following assemblies: 4010-9902 and -9922 modular network interface with the 4010-9818 wired (RS-485) or 4010-9819 �ber communication
media modules, 4010-9905 and -9926 [old NFPA 72 designation: Style 4] Class B or 4010-9906 and -9927 [old NFPA 72 designation: Style 7] Class X
TCP/IP Physical Bridge, 4010-9914 Building Zone and Relay Card is an 8 point Input and output, Class B Card & Class A, 4100-9935, 4010-9936 or
4010-9916, software rev. 1.02, con�guration programmer software 3.06. Building Network Interface card used to communicate with control via an
Ethernet connection to obtain system status for service only, 4010-9909 and -9010 city circuit modules, 4010-9908 and -9911 relay modules,
4010-9918 dual RS-232 interface card, 4010-9916 Twenty-Five Volt Regulator module, 4010-9920 Class B and -9921 (Class A) zone modules which are
compatible with two-wire detectors, 4010-9930 Dual Class A Isolator (DCAI), 4010-9901 VESDA interface for connecting Xtralis aspiration type smoke
detectors to the 4010ES. Zone and IDNet assemblies that support two-wire detectors are compatible with the following: Models 2098-9201, -9202,
-9203, -9544 , and -9576 smoke detectors with 2098-9211 and 9637 bases; Models 4098-9401, 9402, 9403, and 9404 heat detectors; Models
4098-9601, -9602, -9603, and 9605 detectors with 4098-9788 and 9683 bases; Models 4098-9612, -9613, -9614, and 9615 heat detectors with
4098-9788, -9683, and 9684 bases; and Models 4098-9681, -9685 and -9688 duct sensor housings with 4098-9601 smoke detector .
4120 Fiber Media Bidi card is for optional network modules, for Network communications, or local Control Panel equipment communications to
support the 4120 network SIMPLEX UART/network data link protocol. 4120 Fiber Media Bidi card consists of the following part numbers: 4190-6301
[single mode left (SM – L)], 4190-6302 [single mode right (SM – R)], 4190-6303 [multi mode left (MM – L)], and 4190-6304 [multi mode right (MM – R)].
Standby batteries from 6.2 to 50 AH are available to provide 24 hour emergency power. Model 4100-0650 battery shelf can be provided to prevent
the batteries from shifting inside of the enclosure. Up to 110 AH of emergency battery power can be provided by utilizing the Models 4081-9306 or
-9308 expansion battery chargers. The central unit can further be connected to a selection of the following operator annunciators: 4100-9401,
-9402, -9421, -9422, -9441 or -9442 remote user interfaces; or 4606-9102 or -9102C F remote LCD annunciators. Optional remote accessories
include the Models 4190-9021 and -9022 (single mode) or -9024 and -9025 (multimode) Fiber Optic communication modules and expansion
cabinets. The expansion cabinets can optionally include a 4190-9023 (single-mode) or -9026 (Multi-mode) Right-Port Fiber Optic communication
module. As well as the Fiber communication modules, other remotely connected accessories include the 4009 TrueAlert Power Supply (4009 TPS)
that consists of the following 4100U/ES option modules mounted in either the 2975-9229 or -9330 cabinet: 4009-9813 Transponder Interface Card
and one of the 4100-5120 through -5122 TrueAlert Power Supplies, Models 4009-9601 and -9602 IDNAC Repeaters [with or without the optional
4009-9814 Class A Adapter Module] can be used with the Models 4010-96XX and -97XX control units to extend the length of the IDNAC circuit by
10,000 feet. When wired in a Class B manner, the Repeater also increases the IDNAC circuit’s maximum current rating by 3A (See separate
description of the 4009-9401 TrueAlert NAC Extender under LOCAL PROTECTIVE SIGNALING for a list of compatible TrueAlert addressable noti�cation
appliances). Isolator modules model 4905-9849 are used in pairs on TrueAlert signal line circuits to disconnect shorted or failed segments of the
circuit and allow devices located before the �rst isolator and after the second isolator to remain operable. Equipment suitable for operation in
ambient temperatures from 32° to 120°F (0 o to 49° C). (See also AUTOMATIC RELEASES FOR PREACTION AND DELUGE SPRINKLER
SYSTEMS,PROPRIETARY SIGNALING SYSTEMS, CENTRAL STATION, REMOTE STATION SIGNALING; and AUTOMATIC RELEASES FOR EXTINGUISHING
SYSTEMS AND OTHER FIRE PROTECTION EQUIPMENT.)
*
Note 1: 4098-9775, 4098-9776, 4098-9780, 4098-9792, 4098-9789, 4098-9791, 4098-9772, 4098-9794, 4098-9770, 4098-9771, 4098-9773,
4098-9777, 4098-9793.
The Connected Services Gateway Module (CSGM) 4010-2500 and 4010-2501 [Simple Power Over Ethernet Switch (SPES)] include:
IP DACT with a dual phone line interface, RJ45 10/100 Base-Tx Ethernet interface, cellular interface for connection to a central station.
DACT supports –
ADEMCO Contact ID,
DSC Fiber protocol (cellular or Ethernet).
The CSGM with the IP links can also connect to the panel as a remote service monitor interface [similarly to currently listed TrueInsight Remote
Gateway].
The CSGM mounts inside the panel.
The gateway can be mounted remotely and powered through the SPES, mounted in the panel (using the same space the CSGM occupied),
ethernet connection up to 100m away. This connection supports Class B only.
When the CGSM is remote mounted, it must use the CSGM external enclosure (3 colors) with the following PIDs: 2975-9234 (R), 2975-9235 (P),