HVAC Design Basics!!
HVAC Design Basics!!
AUTOCAD- DESIGN
DESIGN
Course Coordinator –
Md.kaysher Ahammed
Senior Design engineer
Lesson 1
HVAC introduction
Application Of HVAC :
➢ High-rise building .
➢ Commercial complex.
➢ industrial Operation .
➢ Hospital Area .
➢ Pharmaceuticals.
➢ Food industry.
➢ Car parking Area.
➢ Hotels etc.
People
Qsensible = N(Sensible heat gain)CLF
Qlatent = N(Latent heat gain)
N = number of people in space, from best
available source. Sensible and latent heat gain
from occupancy,
CLF = cooling load factor, by hour of occupancy,
CLF 1.0 with high density or 24-hr occupancy
and/or if cooling off at night or during
weekends.
Latent heat load ( QL )= (Factor 0.68 * fresh air* Humidity ratio Difference F)
Latent heat LS Factor CFM Outdoor Gr/lb Indoor gr/lb Diff gr/lb
Btu/Hr 553738
0.68 13572 100 40 60
Total AIR Flow = 13572 CFM Total Colling load = 69.35292 Ton
Dehumidifier Selection
Dehumidifier selection
Cal in M Cal in ft
Room temperature 30 °C 30 °C
Room Size
Room Length 5 M 16.4 Ft
Room Width 5 M 16.4 Ft
Room Hight 3 M 9.84 Ft
Room Volume 75 CuM 2646.566 CuFt
Duct Type
1) Rectangular duct
2) Circular /Round duct
3) Oval duct
Duct Materials
1)Galvanized Steel
2) Aluminium
3) Stainless steel
4)Carbon steel
5) Copper
1) Galvanized steel
Most common materials used in duct
fabrication work for comfort air
conditioning
Specification : ASTM A653
Coating G90
Ventilation Procedure.—In
ventilation procedure a minimum
amount of acceptable outdoor air must
be supplied to the conditioned space in
order to maintain acceptable
concentrations of indoor pollutants
such as carbon dioxide (CO2), odor ,
tobacco smoke generated by
occupants, and other pollutant
sources.
Fresh Air Required from ASHRAE
Fresh Air Required from ASHRAE
Fresh Air Required from ASHRAE
Fresh Air Required from ASHRAE
Exhaust Air Rate ASHRAE
Fresh Air Required from ISHRAE
Fresh Air Required from ISHRAE
Fresh Air Required from ISHRAE
Public Toilet Ventilation
Input only in Blue space,Never change the red value
Toilet ventilation with ASHRAE
Public toilet
Continious exhaust
Exhaust CFM Exhaust CFM Exhaust Cfm
Toilet No CFM/Toilet cell Area sq ft CFM/Sq ft Fresh air Cfm
toilet Cell area Total
6 50 390 1 300 390 690 552
Intermitent (only used time) exhaust
Exhaust CFM Exhaust CFM Exhaust Cfm
Toilet No CFM/Toilet cell Area sq ft CFM/Sq ft Fresh air Cfm
toilet Cell area Total
6 70 390 1 420 390 810 648
Private toilet
Continious exhaust
Exhaust CFM Exhaust CFM Exhaust Cfm
Toilet No CFM/Toilet cell Area sq ft CFM/Sq ft Fresh air Cfm
toilet Cell area Total
6 25 390 1 150 390 540 432
Intermitent (only used time) exhaust
Exhaust CFM Exhaust CFM Exhaust Cfm
Toilet No CFM/Toilet cell Area sq ft CFM/Sq ft Fresh air Cfm
toilet Cell area Total
6 50 390 1 300 390 690 552
Kitchen Ventilation
METHOD 1 --- ASHRAE
HOOD Overhang
Hood type End Front Rear
Wall Mounted canopy 150 150 _
single island 150 150 150
Double island 150 150 _
Eyebrow _ 150 _
Back shelf 150 250 _
Pass over 150 250 _
Hood sizing
Hood selected type Single island
Length (mm) Add 2 side mm Width (mm) Add2 side mm
Stove size 2500 300 1500 300
Hood size 2800 mm 1800 mm
Kitchen Ventilation
Maximum Net flow rate,CFM per linear foot of Hood Length
Light duty Midium duty Heavy duty Extra heavy duty equipment
Hood type equipment equipment Equipment
CFM Requirment
Btu/hr/(factor 1.08 *Temp rise)
CFM Requirment 13292.18107 CFM
ASSUMPTIONS
Ambient temp. = 115 F
Acceptable Air Change/Hr = 10 times
CALCULATION
Ventilated Air Quantity for H.T Room (Room Ref. S/S-1,5,6)
Room Volume =
Length L= 100 ft
Width D= 50 ft
Hight H= 30 ft
Acceptable Air Change/Hr = 10 Times
THEN :-
Ventilated Air Quantity for H.T Room = 150000 Cu.Ft/Hr
CFM= Room volume Cuft*ach/(60) 25000 CFM
Fan wall mounted axial type with Ext. Est. Static Pressure of 0.5 " W.G
Fan Quantity 2 Nos
Fan air Flow 12500 CFM
Chiller System
Compressor
The compressor is the driving unit of any
chiller system. It generates the pressure
gradient necessary to push refrigerant
around the chiller unit to achieve process
cooling. Various condensers are
available, with the most popular types
including centrifugal, screw, and
reciprocating compressors.
Evaporators
An evaporator is placed between the
expansion valve, and the condenser
removes heat from any associated
process into circulating refrigerant. This
is then channelled to a cooling tower or
air-cooled depending on the chiller
configuration.
1.Chiller
2.Cooling Tower
3.Chilled Water Pump
4.Condenser Water Pump
Valve and accessories
Isolation valves are used to isolate a
section of pipe and prevent water
from flowing through in order for
people to do maintenance and repair
works.
1) cooling-only,
2) heat pump,
3) and Heat recovery.