A Modified Differential Evolution Algorithm For Frequency Management of Interconnected Hybrid Renewable System
A Modified Differential Evolution Algorithm For Frequency Management of Interconnected Hybrid Renewable System
Debayani Mishra1, Manoj Kumar Maharana1, Manoj Kumar Kar2, Anurekha Nayak3
1
School of Electrical Engineering, KIIT Deemed to be University, Bhubaneswar, India
2
Electrical and Electronics Engineering Department, Tolani Maritime Institute, Pune, India
3
Department of Electrical Engineering, DRIEMS, Cuttack, India
Corresponding Author:
Debayani Mishra
School of Electrical Engineering, KIIT Deemed to be University
Bhubaneswar, India
Email: [email protected]
1. INTRODUCTION
Under the notion of sustainable development, the production of renewable energy sources (RESs)
like wind, hydro, and solar has expanded significantly in recent years replacing the traditional thermal power.
The day by day increase in load demand is managed by the power generation from the renewable sources.
The ability of the central grid is strengthened by lowering the peak loads due to evolution of the idea of
decentralization in power generation. In light of this, renewable energy sources are utilized and the concept
of microgrid is implemented. Microgrids are an amalgamation of renewable source, storage units and loads.
The intermittent nature of low inertia renewable sources creates a disparity between generation and demand
which impelled the formation of interconnected microgrid system. Interconnection of microgrid enables the
sharing of surplus power but makes the system more difficult to govern. The frequency change and power
flow in the interconnected tie line gradually deviates from their nominal value when the load changes
dynamically in the interconnected microgrid system. This intensifies severe frequency deviations which
further deteriorates the power quality and hence impacts the microgrid efficiency. In order to balance the
power transmission across the various power system to maintain a steady grid frequency, load frequency
control is used in micro grids with multiple generating units.
Recent advances in contemporary power networks have necessitated the use of decentralized control
methods rather than centralized control schemes to ameliorate unreliable and inefficient power system control.
The power system frequency was controlled by robust optimal [1], stochastic optimal [2], and secondary loop
frequency control methods [3] in literature. In order to get an enhanced LFC response the controller parameters
need to be tuned rapidly and precisely. In this context, various meta-heuristic optimization techniques like
firefly algorithm [4], ant lion optimizer (ALO) [5], grey wolf optimization [6] and differential evolution [7]
have been proposed in literature. An integrated multi-source, multi-area power system's voltage and frequency
are controlled by a model predictive controller (MPC), whose parameters are tuned via salp swarm algorithm
[8], model predictive controller [9] and using intelligent techniques for energy storage devices [10]. Harris hawk
optimization (HHO) based model predictive controller (MPC) has been implemented for regulating the voltage
and frequency and validated under different conditions in three area hybrid power system as shown in [11] and
[12]. Leader Harris hawk optimization (LHHO) based MPC has been proposed for controlling voltage and
frequency of the system. A hybrid interconnected power system comprising of thermal, wind, diesel,
photovoltaic (PV) and hydrogen units in [13] has been designed. The algorithm was tested in conjunction with
capacitive energy storage units and virtual inertia units. The work in [14] explain an intelligent fuzzy logic
controller was implemented for a multi-area interconnected power system further the controller was compared
with PI and PID subjected to minimization of integral of time-weighted absolute error (ITAE) function.
However, these optimization techniques do not offer exceptional performance in terms of settling time, peak
overshoot or undershoot. Differential evolution (DE) search strategy proposed in [15] was capable to address
optimization problems effectively. In a specific procedure DE performance is dependent on the selection of
values of crossover constant and scaling factor. In this paper modified differential evolution (MDE) technique is
suggested which will overcome the drawback of DE.
From literature it has been studied that the performance of load frequency control (LFC) system
does not depend on the optimization strategy but also rely on the controller design. Different controller such
as adaptive control [16], [17] model predictive control [18] have been proposed to control the frequency in
isolated MG system. These conventional controllers fail to work effectively under various operating
conditions due to aberrant nature of RESs. In contrast, fractional order controllers which improves the
stability of an interconnected MG system have gained a great deal of interest in recent years due to its
versatile structure and has a greater number of tuning parameters. In recent years cascaded controller have
been employed in interconnected power system as it can withstand diverse disturbances effectively. In this
context, a cascaded proportional integral derivative fractional filter (PIDFN) controller is suggested for an
interconnected microgrid system for diminishing the frequency disruption in this paper. The, classical
controller like P, PI and PID works effectively for hybrid MG system. These controllers are sluggish in event
of rapid load disturbance in terms of parameter adjustments. Further sliding mode controllers, fractional order
PI and PID controllers have structural issues and incur more cost. These findings encourage the development
of a cascaded PIDFN controller [19]. The suggested controller has a better performance for abating the
deviations of frequency in the system. Inspired by the research works, this paper suggests a MDE algorithm
for tuning the parameter of the cascaded-PIDFN controller. The suggested optimization techniques surmount
other optimization algorithms in terms of ITAE and convergence.
The contributions and features of the proposed work are as follows: i) A novel modified differential
(MDE) algorithm is used to adjust the parameter of the cascaded PIDFN controller, ii) The supremacy of the
MDE has been established by comparing with other optimization techniques such as differential evolution
(DE), particle swarm optimization (PSO), teaching learning-based optimization (TLBO) and invasive weed
optimization (IWO), iii) The proposed cascaded PIDFN controller performance is studied under various
situations such as variable load disturbance, system uncertainties, communication delay and real time data of
solar irradiance and measurement of wind speed. The actions of unified power flow controller (UPFC) are
also tested on the two-area interconnected microgrid system in MATLAB/Simulink environment, and iv) The
efficacy of optimization technique MDE is verified for different performance parameters.
The article is established as follows: the hybrid renewable energy system (HRES) model is
described in section 2, and the proposed cascaded PIDFN controller is covered in section 3. The performance
of the MDE is discussed in section 4 and simulation results are presented in section 5. Finally, the conclusion
is presented in section 6.
Int J Pow Elec & Dri Syst, Vol. 14, No. 3, September 2023: 1711-1721
Int J Pow Elec & Dri Syst ISSN: 2088-8694 1713
ultracapacitor (ULC) whereas area 2 comprises of a photovoltaic cell (PV), DEG, battery storage as shown in
Figure 1. When the MG system is exposed to load perturbations and the intermittent nature of RES generation
introduces ambiguity in the system which leads to instability. Hence each area required to monitor and control
for proper operation of power system. In this paper a cascaded-PIDFN controller is used, whose parameters are
tuned by MDE algorithm to minimize the frequency deviation and oscillations in each area and tie line.
Additionally, the performance of MDE-PIDFN controller is compared with DE, PSO, TLBO and IWO. The
various components of the proposed MG system are briefly illustrated in the following subsections.
where 𝜌 = is the density of air in kg/m3 and A = is the region swept by the turbine blades in m 3.
Δf, TGOV, TGE, TDE and R corresponds to the frequency deviation, governor’s time constant, generator time
constant, delay time constant and speed regulation of governor respectively.
3. CONTROLLER DESIGN
To reduce the frequency variation in the MG, a cascaded-PIDFN controller is implemented [19].
The performance of the controller is also compared to that of other controllers under various scenarios. The
suggested controller is a cascaded design of PIDN and PIDFN based on fractional calculus, with
differentiators and integrators. The PIDN controller comprises of P, I, D controller with a derivative filter
coefficient N and the PIDFN controllers is of the form of PI λ Dµ and a derivative filter coefficient N. λ and µ
are the order of integrators and differentiators respectively. With the inclusion of a fractional order PIDN
controller, the integer order PIDN controller may be extended from point to plane, making the PIDN control
method more adaptable and robust [20], [21].The scaling parameters provided by the advanced control
optimization, the gain parameters of a cascaded PIDFN controller becomes more flexible [22], [23] and by
implementing a fuzzy PID filter [24].
4. MDE STRATEGIES
A DE algorithm is proposed which was found to be superior in reference to other evolutionary
algorithm simplicity, ease of implementation, and fewer variables [25]. The operation of DE algorithm
follows four steps: i) initialization, ii) mutation, iii) crossover, and iv) selection. In the first step, it starts with
n numbers of population size and number of decision vectors distributed randomly as, ⃗⃗⃗⃗ 𝑋𝑘𝑙 = (𝑋1𝑙 , 𝑋2𝑙 , . . . , 𝑋𝐷𝑙 )
over D-dimensional search space. In second step, a mutant vector (𝑀 ⃗⃗⃗⃗⃗𝑙 ) is generated by applying the mutation
𝑘
operator any of the following:
DE/rand/1: ⃗⃗⃗⃗⃗
𝑀𝑘𝑙 = ⃗⃗⃗⃗⃗⃗ ⃗⃗⃗⃗⃗⃗𝑙 − ⃗⃗⃗⃗⃗⃗
𝑋𝑘𝑙 1 + 𝑓 (𝑋 𝑘2 𝑋𝑘𝑙 3 ) (6)
DE/best/1: ⃗⃗⃗⃗⃗
𝑀𝑘𝑙 = ⃗⃗⃗⃗⃗⃗⃗⃗⃗
𝑙
𝑋𝑏𝑒𝑠𝑡 ⃗⃗⃗⃗⃗⃗𝑙 − ⃗⃗⃗⃗⃗⃗
+ 𝑓 (𝑋 𝑘1 𝑋𝑘𝑙 2 ) (7)
DE/rand/2: ⃗⃗⃗⃗⃗
𝑀𝑘𝑙 = ⃗⃗⃗⃗⃗⃗ ⃗⃗⃗⃗⃗⃗𝑙 − ⃗⃗⃗⃗⃗⃗
𝑋𝑘𝑙 5 + 𝑓 (𝑋 𝑘1
⃗⃗⃗⃗⃗⃗𝑙 − ⃗⃗⃗⃗⃗⃗
𝑋𝑘𝑙 2 ) + 𝑓 (𝑋 𝑘3 𝑋𝑘𝑙 4 ) (8)
DE/best/2: ⃗⃗⃗⃗⃗
𝑀𝑘𝑙 = ⃗⃗⃗⃗⃗⃗⃗⃗⃗
𝑙
𝑋𝑏𝑒𝑠𝑡 ⃗⃗⃗⃗⃗⃗𝑙 − ⃗⃗⃗⃗⃗⃗
+ 𝑓 (𝑋 𝑘1
⃗⃗⃗⃗⃗⃗𝑙 − ⃗⃗⃗⃗⃗⃗
𝑋𝑘𝑙 2 ) + 𝑓 (𝑋 𝑘3 𝑋𝑘𝑙 4 ) (9)
Int J Pow Elec & Dri Syst, Vol. 14, No. 3, September 2023: 1711-1721
Int J Pow Elec & Dri Syst ISSN: 2088-8694 1715
DE/current-to-best/1: ⃗⃗⃗⃗⃗
𝑀𝑘𝑙 = ⃗⃗⃗⃗ ⃗⃗⃗⃗⃗⃗⃗⃗⃗
𝑋𝑘𝑙 + 𝑓 (𝑋 𝑙 ⃗⃗⃗⃗𝑙 ⃗⃗⃗⃗⃗⃗⃗⃗⃗
𝑙 ⃗⃗⃗⃗⃗⃗𝑙
𝑏𝑒𝑠𝑡 − 𝑋𝑘 ) + 𝑓 (𝑋𝑏𝑒𝑠𝑡 − 𝑋𝑘2 ) (10)
in last step, the vector for the next generation is selected as per the (12):
where, ⃗⃗⃗⃗
𝑋𝑘𝑙 is the kth decision vector of lth generation; ⃗⃗⃗⃗⃗
𝑀𝑘𝑙 is the kth mutant vector of lth generation; ⃗⃗⃗⃗
𝑋𝑘𝑙 and
⃗⃗⃗⃗⃗⃗⃗⃗⃗
𝑋 𝑙 are the lth generation's randomly chosen decision vector and best solution vector, respectively where f
𝑏𝑒𝑠𝑡
is the scale factor and 𝐶𝑟 is the crossover rate having value between 0 to 1.
The mutation operator like DE/rand mutation operator has more exploration feature than
exploitation which also takes more time to attain optimal solution. Similarly, the DE/best mutation operator
has more exploitation feature than exploration and takes less time to obtain optimal solution. This approach,
however, suffers from early convergence and being stuck in local optima. A novel mutation operator is
presented in the MDE algorithm to prevent the above difficulty and maintain a balance between exploitation
and exploration. Here, six best solutions from the current generation are chosen to find three mutant vectors
in (13) to (15). The final mutant vector (𝑀 ⃗⃗ 𝑘𝑙 ) is then determined by taking the average of these three mutant
vectors. In crossover step, a new trial vector is obtained as (16). Finally, in selection step, the decision vector
for next generation is obtained as expressed in (17).
𝑀1 = ⃗⃗⃗⃗
⃗⃗⃗⃗⃗ ⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗
𝑋𝑘𝑙 + 𝑓 (𝑋 𝑙 ⃗⃗⃗⃗𝑙 ⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗
𝑙 ⃗⃗⃗⃗𝑙
𝑏𝑒𝑠𝑡1 − 𝑋𝑘 ) + 𝑓 (𝑋𝑏𝑒𝑠𝑡2 − 𝑋𝑘 ) (13)
𝑀2 = ⃗⃗⃗⃗
⃗⃗⃗⃗⃗ ⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗
𝑋𝑘𝑙 + 𝑓 (𝑋 𝑙 ⃗⃗⃗⃗𝑙 ⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗
𝑙 ⃗⃗⃗⃗𝑙
𝑏𝑒𝑠𝑡3 − 𝑋𝑘 ) + 𝑓 (𝑋𝑏𝑒𝑠𝑡4 − 𝑋𝑘 ) (14)
𝑀3 = ⃗⃗⃗⃗
⃗⃗⃗⃗⃗ ⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗
𝑋𝑘𝑙 + 𝑓 (𝑋 𝑙 ⃗⃗⃗⃗𝑙 ⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗⃗
𝑙 ⃗⃗⃗⃗𝑙
𝑏𝑒𝑠𝑡5 − 𝑋𝑘 ) + 𝑓 (𝑋𝑏𝑒𝑠𝑡6 − 𝑋𝑘 ) (15)
⃗⃗ 𝑘𝑙 = 𝑀𝑒𝑎𝑛(𝑀
𝑀 ⃗⃗ 1 , 𝑀
⃗⃗ 2 , 𝑀
⃗⃗ 3 ) (16)
𝑙
𝑓 = 2 × (1 − ) (17)
𝐿𝑚𝑎𝑥
𝑙 𝑙 𝑙 𝑙 𝑙 𝑖
Where, 𝑋𝑏𝑒𝑠𝑡1 , 𝑋𝑏𝑒𝑠𝑡2 , 𝑋𝑏𝑒𝑠𝑡3 , 𝑋𝑏𝑒𝑠𝑡4 , 𝑋𝑏𝑒𝑠𝑡5 and 𝑋𝑏𝑒𝑠𝑡6 are the six best decision vectors chosen from lth
generation. 𝑙 and 𝐿𝑚𝑎𝑥 are the current and maximum generation respectively.
calculated using different optimization techniques. The different ITAE values obtained from the optimization
techniques are listed in Table 1.
Figures 3(a)-(c) represents the dynamic performance of ΔF1, ΔF2 and ΔPtie respectively under random
load perturbations. From Figure 3(a) it is observed that the transient response of the variation of frequency (ΔF1)
in area 1 has better response using the MDE-PIDFN controller compare to another controller. Similarly in
Figures 3(b) and 3(c) the MDE-PIDFN controller provide better transient response for the variation of
frequency (ΔF2) in area 2 and change in tie line power (ΔP tie) respectively as compared to other controllers
which is shown in the zoom portion of the figure. From Table 2 it is observed that the MDE-PIDFN controller
has a better fitness as compared to other controllers. The transient specification of the system with respect to
peak undershoot (PUS) and settling time (TS) is represented in Table 2. The MDE algorithm offers improved
dynamic responsiveness in terms of settling time as compare to other optimization techniques.
(a) (b)
(c)
Figure 3. Frequency fluctuations a random load perturbation (a) ΔF1, (b) ΔF2, and (c) ΔPtie
Int J Pow Elec & Dri Syst, Vol. 14, No. 3, September 2023: 1711-1721
Int J Pow Elec & Dri Syst ISSN: 2088-8694 1717
Table 4. System specifications under action of UPFC and random load disturbance in Area 1 and Area 2
Controller ΔF1 (Hz) ΔF2 (Hz) ΔPtie (p.u)
PUS (Hz) × 10-4 TS (sec) PUS (Hz) × 10-6 TS (sec) PUS (Hz) × 10-6 TS (sec)
IWO-PIDFN - 9.65 5.5 - 17.2
TLBO-PIDFN - 7.87 6.78 -0.02 11.6
PSO-PIDFN - 8.23 8.9 - 12.2
DE-PIDFN -1.5 Unstable -2.5 Unstable -0.68 Unstable
MDE-PIDFN - 6.35 4.88 - 9.3
(a) (b)
(c)
Figure 6. Dynamic response under UPFC (a) ΔF1, (b) ΔF2, and (c) ΔPtie
When the HRES system is exposed to variation in parameters and CTD the system ITAE values is
represented in Table 5 for various controllers. From Table 6 it is observed that the ITAE value of the
proposed controller has a better value as compared to other optimization methods. Figures 7(a)-(c) depict the
dynamic response of frequency deviations F1 and F2 in each location, as well as the tie line power variation of
ΔPtie in Areas 1 and 2 respectively. Figure 7(a) demonstrates that the MDE-PIDFN controller provides a
superior transient response to conventional controllers for the frequency fluctuation (F1) in region 1.
Similarly, in Figures 7(b) and 7(c), the MDE-PIDFN controller provides a better transient response for the
frequency variation (F2) in area 2 and the change in tie line power (Ptie) than other controllers, as seen in the
zoomed region. The transient specification of the HRES under this scenario is represented in Table 7. From
Table 7 it is examined that the MDE method provides enhanced dynamic responsiveness in terms of settling
time in comparison to other optimization strategies.
Table 6. ITAE values of different optimization techniques under action of CTD and variation in parameters
Controller IWO-PIDFN PSO-PIDFN TLBO-PIDFN DE-PIDFN MDE-PIDFN
ITAE 0.005945 0.004812 0.004218 0.002984 0.002105
Int J Pow Elec & Dri Syst, Vol. 14, No. 3, September 2023: 1711-1721
Int J Pow Elec & Dri Syst ISSN: 2088-8694 1719
(a) (b)
(c)
Figure 7. Dynamic response under CTD and parameter variation (a) ΔF 1, (b) ΔF2 and (c) ΔPtie
6. CONCLUSION
An interconnected microgrid system constituting wind generator, photovoltaic, diesel engine
generator, battery and capacitor is modelled in this paper. The HRES comprising of nature dependent sources
results in frequency perturbations in the system which can be ameliorated by using a controller. In this paper
a MDE technique is suggested to tune the parameters of the cascaded-PIDFN controller of two area MG
system. To assess the effectiveness of the proposed controller the microgrid is subjected to load perturbation,
parametric variations, effect of CTD and UPFC in the system. The dynamic behavior of the MG system is
analyzed and compared with the results of DE, PSO, TLBO and IWO tuned cascaded-PIDFN controller. In
Area 1 the proposed controller improves the settling time by 80.10%, 68.95%, 61.79% as compared to DE-
PIDFN, TLBO-PIDFN and IWO-PIDFN controller. Similarly in Area 2, the settling time is improved by
23.42%, 21.29%, 32.63% and 41.44% in contrast with DE-PIDFN, PSO-PIDFN, TLBO-PIDFN and IWO-
PIDFN controller. The settling time in the tie line is also improved by 83.55%, 72.95% and 30.38% as
compared to DE-PIDFN, TLBO-PIDFN and IWO-PIDFN controller. The proposed controller is accountable
for maintaining frequency fluctuation and making the power system more stable with reduced peak
overshoot, undershoot, and muted oscillations.
REFERENCES
[1] H. Li, X. Wang, and J. Xiao, “Adaptive event-triggered load frequency control for interconnected microgrids by observer-based
sliding mode control,” IEEE Access, vol. 7, pp. 68271–68280, 2019, doi: 10.1109/ACCESS.2019.2915954.
[2] A. Rafinia, J. Moshtagh, and N. Rezaei, “Stochastic optimal robust design of a new multi-stage under-frequency load shedding
system considering renewable energy sources,” Int. J. Electr. Power Energy Syst., vol. 118, 2020, doi:
10.1016/j.ijepes.2019.105735.
[3] H. Gozde, M. Cengiz Taplamacioglu, and I. Kocaarslan, “Comparative performance analysis of Artificial Bee Colony algorithm
in automatic generation control for interconnected reheat thermal power system,” Int. J. Electr. Power Energy Syst., vol. 42, no.
1, pp. 167–178, 2012, doi: 10.1016/j.ijepes.2012.03.039.
[4] N. K. Gupta, M. K. Kar, and A. K. Singh, “Load frequency control of two-area power system by using 2 degree of freedom PID
controller designed with the help of firefly algorithm,” in Control Applications in Modern Power System, vol. 710, 2020, Springer
Singapore, 2021.
[5] M. Raju, L. C. Saikia, and N. Sinha, “Automatic generation control of a multi-area system using ant lion optimizer algorithm
based PID plus second order derivative controller,” Int. J. Electr. Power Energy Syst., vol. 80, pp. 52–63, 2016, doi:
10.1016/j.ijepes.2016.01.037.
[6] Y. Sharma, and L. C. Saikia, “Automatic generation control of a multi-area ST - thermal power system using grey wolf optimizer
algorithm based classical controllers,” Int. J. Electr. Power Energy Syst., vol. 73, pp. 853–862, 2015, doi:
10.1016/j.ijepes.2015.06.005.
[7] M. K. Kar, S. Kumar, A. K. Singh, and S. Panigrahi, “Reactive power management by using a modified differential evolution
algorithm,” Optim. Control Appl. Methods, no. October, pp. 1–20, 2021, doi: 10.1002/oca.2815.
[8] A. Singh, and V. Sharma, “Salp swarm algorithm-based model predictive controller for frequency regulation of solar integrated
power system,” Neural Comput. Appl., vol. 31, no. 12, pp. 8859–8870, 2019, doi: 10.1007/s00521-019-04422-3.
[9] Z. Ji, X. Huang, C. Xu, and H. Sun, “Accelerated model predictive control for electric vehicle integrated microgrid energy
management: A hybrid robust and stochastic approach,” Energies, vol. 9, no. 11, 2016, doi: 10.3390/en9110973.
[10] R. Shankar, K. Chatterjee, and R. Bhushan, “Impact of energy storage system on load frequency control for diverse sources of
interconnected power system in deregulated power environment,” Int. J. Electr. Power Energy Syst., vol. 79, pp. 11–26, 2016,
doi: 10.1016/j.ijepes.2015.12.029.
[11] H. Shukla, S. Nikolovski, M. Raju, A. S. Rana, and P. Kumar, “SMES-GCSC coordination for frequency and voltage regulation
in a multi-area and multi-source power system with penetration of electric vehicles and renewable energy sources,” Energies, vol.
16, no. 1, 2023, doi: 10.3390/en16010251.
[12] M. A. Sobhy, M. Ezzat, H. M. Hasanien, and A. Y. Abdelaziz, “Harris hawks algorithm for automatic generation control of
interconnected power systems,” 2019 21st Int. Middle East Power Syst. Conf. MEPCON 2019 - Proc., 2019, pp. 575–582, doi:
10.1109/MEPCON47431.2019.9007968.
[13] J. Zhao and J. Wang, “Integrated model predictive control of hybrid electric vehicles coupled with aftertreatment systems,” IEEE
Trans. Veh. Technol., vol. 65, no. 3, pp. 1199–1211, 2016, doi: 10.1109/TVT.2015.2405918.
[14] J. Brest, S. Greiner, B. Bošković, M. Mernik, and V. Zumer, “Self-adapting control parameters in differential evolution: A
comparative study on numerical benchmark problems,” IEEE Trans. Evol. Comput., vol. 10, no. 6, pp. 646–657, 2006, doi:
10.1109/TEVC.2006.872133.
[15] A. K. Qin, V. L. Huang and P. N. Suganthan, “Differential evolution algorithm with strategy adaptation for global numerical
optimization,” in IEEE Transactions on Evolutionary Computation, vol. 13, no. 2, pp. 398−417, April 2009, doi:
10.1109/TEVC.2008.927706.
[16] S. Zheng, X. Tang, B. Song, S. Lu, and B. Ye, “Stable adaptive PI control for permanent magnet synchronous motor drive based
on improved JITL technique,” ISA Trans., vol. 52, no. 4, pp. 539–549, 2013, doi: 10.1016/j.isatra.2013.03.002.
[17] H. Bevrani, and P. R. Daneshmand, “Fuzzy logic-based load-frequency control concerning high penetration of wind turbines,”
in IEEE Systems Journal, vol. 6, no. 1, pp. 173−180, March 2012, doi: 10.1109/JSYST.2011.2163028.
[18] J. Yang, Z. Zeng, Y. Tang, J. Yan, H. He, and Y. Wu, “Load frequency control in isolated micro-grids with electrical vehicles
based on multivariable generalized predictive theory,” Energies, vol. 8, no. 3, pp. 2145–2164, 2015, doi: 10.3390/en8032145.
[19] D. Mishra, M. K. Maharana, and A. Nayak, “Frequency amelioration of an interconnected microgrid system,” Open Eng., vol. 12,
no. 1, pp. 349–358, 2022, doi: 10.1515/eng-2022-0038.
[20] R. Rajbongshi and L. C. Saikia, “Combined voltage and frequency control of a multi-area multisource system incorporating dish-
Stirling solar thermal and HVDC link,” IET Renew. Power Gener., vol. 12, no. 3, pp. 323–334, 2018, doi: 10.1049/iet-
rpg.2017.0121.
[21] R. Rajbongshi and L. C. Saikia, “Combined control of voltage and frequency of multi-area multisource system incorporating
solar thermal power plant using LSA optimised classical controllers,” IET Gener. Transm. Distrib., vol. 11, no. 10, pp. 2489–
2498, 2017, doi: 10.1049/iet-gtd.2016.1154.
[22] S. Oladipo, Y. Sun, and Z. Wang, “Maiden application of a modified HBA-optimized cascaded (2DOF + FOPIDN)-PD controller
for load frequency control of diverse source power system,” Math. Probl. Eng., vol. 2022, 2022, doi: 10.1155/2022/4756347.
[23] N. K. Gupta, M. K. Kar, and A. K. Singh, “Design of a 2-DOF-PID controller using an improved sine–cosine algorithm for load
frequency control of a three-area system with nonlinearities,” Prot. Control Mod. Power Syst., vol. 7, no. 1, 2022, doi:
10.1186/s41601-022-00255-w.
[24] Y. Arya, “AGC of two-area electric power systems using optimized fuzzy PID with filter plus double integral controller,” J.
Franklin Inst., vol. 355, no. 11, pp. 4583–4617, 2018, doi: 10.1016/j.jfranklin.2018.05.001.
[25] L. Kumar, M. K. Kar, and S. Kumar, “Statistical analysis based reactive power optimization using improved differential
evolutionary algorithm,” Expert Syst., vol. 40, no. 1, pp. 1–31, 2023, doi: 10.1111/exsy.13091.
Int J Pow Elec & Dri Syst, Vol. 14, No. 3, September 2023: 1711-1721
Int J Pow Elec & Dri Syst ISSN: 2088-8694 1721
BIOGRAPHIES OF AUTHORS
Debayani Mishra received her B.Tech and M.Tech degree from Biju Pattanaik
University of Technology, Rourkela, Odisha. She is presently working as an Asst. Professor in
Electrical Engineering Department at Ajay Binay Institute of Technology, Cuttack, Odisha.
She is currently pursuing her PhD in KIIT Deemed to be University, Bhubaneswar, Odisha.
She has 14 years of teaching experience her research area includes renewable energy, power
system and energy management system. She can be contacted at email:
[email protected].