Design Guidelines
Design Guidelines
2
1 Rensselaer Polytechnic Institute
2 Network and Telecommunications Department
List of figures
3 ii
1 Rensselaer Polytechnic Institute
2 Network and Telecommunications Department
3
4
5
General
1
Rensselaer Polytechnic Institute Information Technology’s Infrastructure Design Guideline is intended
to be used in conjunction with CSI Formatted 3 part Division 27100 Specifications and T series
drawings and to be incorporated into RENSSELAER POLYTECHNIC INSTITUTE construction project
specifications.
The purpose of the Design Guidelines is to describe and specify the minimum building infrastructure
required to support the communications and networking requirements at Rensselaer Polytechnic
Institute. Architects, engineers and designers should use these Design Guidelines to incorporate the
information provided into Construction Documents. This document is based on industry standards
and codes. This document does not replace any national or local standards, regulations or codes, but
enhances them. If the standards and practices of Rensselaer Polytechnic Institute exceed national or
local standards, regulations or codes, Rensselaer Polytechnic Institute’s practices shall take
precedent.
The scope of this document includes the design and installation methods of Telecommunication
Rooms (TR’s), cabling distributions systems and work area outlet locations, cable specifications,
testing, documentation and administration. For details on products and installation practices for
communications cabling and components refer to the Division 27100 Specifications. This document is
subject to change in form and technical content as warranted by advancements in building
construction techniques and telecommunications technology. As such, Rensselaer Polytechnic
Institute specifically reserves the right to add to and revise, the information contained herein.
2
Normative references
The following codes and standards contain provisions that, through reference in this text, constitute
provisions of Document. At the time of publication, the editions indicated were valid. All codes and
standards are subject to revision; parties to agreements based on this Document shall apply the most
recent editions of the codes standards indicated. All equipment, construction practices, design
principles and installations must conform to the latest version of any or all of the following standards
and codes, published by the following organizations, where applicable;
Reference Documentation
3 All RENSSELAER POLYTECHNIC INSTITUTE staff, architects, engineers, contractors and vendors
4 involved in the design, installation, specifications and details of the RENSSELAER POLYTECHNIC
5 INSTITUTE Network and Telecommunications Distribution Infrastructure and Wiring must have
6 access to the following referenced documentation and will be held accountable to the standards set
7 forth in this document. These documents are to be used in the design, layout and installation of the
8 RENSSELAER POLYTECHNIC INSTITUTE Network and Telecommunications Distribution
9 Infrastructure. The standards, codes, and regulations referenced may have corrections, additions,
10 technical service bulletins, and addendums that are not specifically called out in this section. In all
6 3
1 Rensselaer Polytechnic Institute
2 Network and Telecommunications Department
1 cases, the latest versions are to be referenced regardless of versions stated in this document.
2 Questions, problems or comments concerning this document or the referenced document should be
3 directed to RENSSELAER POLYTECHNIC INSTITUTE Network & Telecommunications Department
4
5 FCC Regulations
6 FCC Part 68 Regulations for connecting premise cabling and customer provided equipment to
7 regulated networks
3 4
1 Rensselaer Polytechnic Institute
2 Network and Telecommunications Department
3
4
5
1 BICSI Methodologies
2 BICSI Telecommunications Distribution Methods Manual (TDMM - 10th edition)
3 BICSI Telecommunications Cabling Installation Manual (2nd edition)
4 BICSI Customer Owned Outside Plant Design Manual (2nd edition)
5 ANSI/NECA/BICSI 568-2001
6 Installing Commercial Building Telecommunications Cabling
General
This section contains definitions of terms, acronyms, and abbreviations that have a special meaning or
that are unique to the technical content of this document. The terms that are used in only one clause
may be defined within, and at the beginning of, that clause.
Definition of terms
Equipment Room (ER): An ER Room is a special purpose room designed to serve as a campus point
of demarcation. An ER Room may service multiple TRBs in a campus design. In large campuses,
multiply ERs may be required and interconnected. This room will only contain Network &
Telecommunications hardware and CATV. Any other utilities(s) must be approved by the Network &
Telecommunications Department management.
Building Telecommunications Room (TRB) : A TRB is a special purpose room designed to serve a
single building with multiple TRs . The TRB may also contain the necessary equipment to function as a
TR for the floor it is located on. This room will only contain Network & Telecommunications hardware
and CATV. Any other utilities(s) must be approved by the Network & Telecommunications
Department management.
Access Point: - An Access Point is a space use to transition backbone and horizontal cabling
between floors within a building riser system.
Acronyms
AP Access Point
AFF Above the Finished Floor
BICSI Building Industry Consultants Service International
CAT Category
CATV Community Antenna Television (cable television)
HH Handhole
6 5
1 Rensselaer Polytechnic Institute
2 Network and Telecommunications Department
MH Maintenance Hole
PBX Private Branch Exchange (Phone Switch)
TR Telecommunication Room
TRB Building Telecommunications Room
TGB Telecommunications Grounding Busbar
TMGB Main Telecommunications Grounding Busbar
TDMM Telecommunications Distribution Methods Manual (BICSI Publication)
UTP Unshielded Twisted Pair
Also, see “Normative references” for additional codes and standards Acronyms.
3 6
1 Rensselaer Polytechnic Institute
2 Network and Telecommunications Department
3
4
5
DESIGN GUIDELINES
1 Symbols Guide :
Network Symbols
Drop Location: 2 cat 6
Pay Phone
P
W Wall Phone
Floor Mounted
EX Existing Jack
GR Ground Bar
Ladder Rack
General
The following section will outline the location, design and pathway requirements for Building
Equipment Rooms (TRB) and Telecommunication Rooms (TR).
6 7
1 Rensselaer Polytechnic Institute
2 Network and Telecommunications Department
Figure 1 – Example of a Telecommunications Room
Location
TRBs and TRs locations must meet the following requirements
Location should be selected so that the room may be expanded.
Shall be located as close as practicable to the center core of the building to minimize
horizontal cable distances (Maximum cable length is 200’ (60m) from TR to drop location)
Shall be accessible through common-use corridors that will allow the delivery of large cable
reels and equipment and access for repairs 24x7.
In multiple floor applications, TRBs and TRs shall have all 4 walls vertically stacked.
TRBs and TRs may not be inside of or be part of a Mechanical space, Equipment room,
Washroom, storage area, janitor closet. All room locations must be approved in writing by
Rensselaer Polytechnic Institute prior to design.
Electromagnetic interference
Rooms shall be located away from sources of electromagnetic interference. Special attention shall
be given to electrical power supply transformers, motors and generators, x-ray equipment, elevator
equipment, and induction devices.
Access
Access to the Rooms shall be 24 hours-per-day, 365 days-per-year basis (24x7). Access shall be
through common use corridors and not accessed by way of any other room.
3 8
1 Rensselaer Polytechnic Institute
2 Network and Telecommunications Department
3
4
5
Design
Architectural
Size
Rooms shall have a minimum inside dimension of 8ft. x 10ft. If these rooms require additional square
footage based on additional requirements, the size shall be determined on a case-by-case basis.
Rensselaer Polytechnic Institute must approve all room dimensions in writing.
Walls
All four (4) walls shall be floor to deck and have a 2-hour fire rating.
Plywood backboards
All four (4) walls shall be covered with ¾ in. exterior grade plywood, preferably void free. Plywood
shall be fire-rated to meet applicable codes. To reduce warping, fire-rated plywood shall be kiln-dried
to maximum moisture content of 15%. Plywood shall be painted on all 6 sides with a white fire
retardant paint. Mount plywood 2” above the top of the electrical outlets or surface raceway. Top of
plywood shall be level with the top of the cable tray but shall not exceed 9’ AFF.
Ceiling height
The height between the finished floor and the lowest point of the ceiling should be a minimum of 3 m
(10 ft).
Treatment
Floors, walls, and ceiling shall be treated to eliminate dust. Finishes shall be light in color to enhance
room lighting. Floor covering shall be a vinyl anti-static material. Color shall be determined on a
case-by-case basis.
False ceiling
Room shall not have a false ceiling to permit maximum use of cable pathways both vertically and
horizontally. In such cases where fire-proofing may be sprayed onto the exposed ceiling, the fire-
proofing shall be treated to mitigate airborne dust.
Door
Doors shall be a minimum of 0.9 m (36 in) wide and 2 m (80 in) high, without doorsill, hinged to open
outward (code permitting) or slide side-to-side, or be removable. Consideration should be given to
using double doors with a removable center-post. The door(s) shall be fitted with a lock, which is
keyed for an MH1 key.
Floor loading
The TRBs shall be located on floor areas designed with a minimum floor loading of 4.8 kPa
(100 lbf/ft2). The TRs shall be located on floor areas designed with a minimum floor loading of
2.4 kPa (50 lbf/ft2). The project structural engineer shall verify that concentrations of proposed
equipment do not exceed the floor-loading limit.
Signage
Signage, if used, should be developed within the security plan of the building.
6 9
1 Rensselaer Polytechnic Institute
2 Network and Telecommunications Department
Environmental
Contaminants
The rooms shall be protected from contaminants and pollutants that could affect operation and
material integrity of the installed equipment.
Continuous operation
HVAC shall be available on a 24 hours-per-day, 365 days-per-year basis. A stand-alone unit should
be considered for Telecommunication Rooms.
Standby operation
If a standby power source is available in the building, consideration should be given to also
connecting the HVAC system serving the Communications Rooms to the standby supply.
Operational parameters
The temperature and humidity shall be controlled to provide continuous operating ranges of 18 C
(64 F) to 24 C (75 F) with 30% to 55% relative humidity.
The ambient temperature and humidity shall be measured at a distance of 1.5 m (5 ft) above the floor
level, after the equipment is in operation, at any point along an equipment aisle centerline.
Positive pressure
A positive pressure differential with respect to surrounding areas should be provided with a minimum
of one air change per hour.
Vibration
Mechanical vibration coupled to equipment or the cabling infrastructure can lead to service failures
over time. A common example of this type of failure would be loosened connections. If there is a
potential for vibration within the building that will be conveyed to the TR via the building structure, the
project structural engineer should design in safeguards against excessive TR vibration.
Electrical
Lighting
Lighting shall be a minimum of 500 lx (50 foot candles) measured 1 m (3 ft) above the finished floor,
mounted 8.5 ft minimum above the finished floor. Light fixtures must be independently supported from
the building structure. Light fixtures shall not be mounted to, or supported by the cabletray.
NOTE - Lighting fixtures should not be powered from the same electrical distribution
panel as the TR/TRB. Dimmer switches shall not be used and emergency lighting
and signs should be properly placed such that an absence of primary lighting will not
hamper emergency exit.
Power
General
Each TR shall contain an electrical sub panel for the TRB and all the TRs that will be fed from that
TRB.
3 10
1 Rensselaer Polytechnic Institute
2 Network and Telecommunications Department
3
4
5
TRs shall be fed from the sub panel in the TRB so that all outlets in all TRs are on emergency power.
Panel
The electrical sub panel shall be fed from the building emergency electrical power system. The panel
shall be sized to accommodate the TRB and all the TRs that will be serviced by it. The panel shall
have a laser printed directory to indicate rooms served by breaker.
Equipment 208vOutlets
TRBs / TRs shall be equipped with a minimum of two (2) dedicated 208V, 30A dedicated ( L6-3R
Hubbell ) dedicated circuits. Outlets shall be 208V, 30A duplex outlets. Outlets may be wall mounted,
installed in divided surface raceway or installed on Kindorf channel above equipment racks
depending on room configuration. Outlets shall be installed 12" from finished floor to center. All
outlets shall have a laser printed circuit identifiers affixed to it indicating the panel room number,
panel ID and circuit number. Rensselaer Polytechnic Institute Network & Telecommunications
Department may specify additional outlets on a case-by-case basis.
Convenience 110vOutlets
TRBs/ TRs shall be equipped with convenience outlet placed on each wall of the TR for uses other
than network equipment (i.e. power tools, testing equipment). This outlet shall be run from a separate
electrical panel. All outlets shall have a laser printed circuit identifiers affixed to it indicating the panel
room number, panel ID and circuit number. Network & Telecommunications Department may specify
additional outlets on a case-by-case basis.
TRBs shall have a TMGB installed to which all TGBs in TRs, equipment, conduits, cable shields,
cable trays, sleeves, etc. shall be bonded. The TMGB shall be connected to the main electrical
service ground of the building with a minimum conductor size 2 AWG. A larger conductor size may be
required based on the distance between the TMGB and the main electrical service ground. The
TMGB shall also be bonded to building structural steel.
TRs shall have a TGB installed to which all equipment, conduits, cable shields, cable trays, sleeves,
etc. shall be bonded. The TGB shall be connected to the TMGB located in the TRB with a minimum
conductor size 6 AWG. A larger conductor size may be required based on the distance between the
TMGB and the TGB. The conductor shall be continuous from the TMGB to the TGB. The TGB shall
also be bonded to building structural steel if close and accessible. A separately derived ground or
isolated ground system is not permitted.
Miscellaneous Requirements
Fire protection
Fire protection of the Telecommunications Rooms, if required, shall be provided as per applicable
code. If sprinklers are required within the spaces, the heads shall be provided with wire cages to
prevent accidental operation. Drainage troughs shall be placed under the sprinkler pipes to prevent
6 11
1 Rensselaer Polytechnic Institute
2 Network and Telecommunications Department
leakage onto the equipment within the room. For some applications, consideration should be given
to the installation of alternate fire-suppression systems, confirm applications with Rensselaer
Polytechnic Institute.
Water infiltration
The TRBs/TRs shall not be located below water level unless preventive measures against water
infiltration are employed. The room shall be free of water or drain pipes not directly required in
support of the equipment within the room. A floor drain shall be provided within the room if risk of
water ingress exists.
Cable Pathways
General
Conduits and sleeves should extend 4- 6” into the TR/TRB. If the conduits or sleeves are subject to
water intrusion they must drain away from the room and be watertight. All conduits and sleeves must
have the ends plugged upon installation to keep debris from entering the conduits and sleeves. Cable
tray shall not be run through walls. Conduits and sleeves must have bushings install at all ends and at
all pull boxes. Network & Telecommunications Department must approve all pathway designs in
writing.
Conduit pathways built for telecommunication cabling have more stringent bending and pull
box requirements than electrical cabling and must be adhered to (i.e. a telecommunications
conduit can have no more them 180 degrees of cumulative bends between pull points where
as a conduit installed for electrical wiring may have 360 degrees of bends between pull
points).
Ladder Rack
An 18" wide ladder rack shall be run around the inside perimeter of the room for the distribution of
cabling inside the room. An 18” wide ladder rack shall also be run down the center of the room for the
free standing racks that will be installed. The rack shall be mounted 7’0” from finished floor to the
bottom of the tray. There shall be no other equipment, lights, conduits, fixtures etc. attached to,
mounted on, running through or on the ladder rack except those needed to support the ladder rack
systems. Ladder racking may not be run through walls.
Sleeves/Conduits
Horizontal UTP
The quantity of horizontal sleeves installed in each TR/TRB for horizontal cabling shall be six (6) 4"
sleeves. The sleeves shall be a minimum 8’-0” AFF to the bottom of the sleeves. Sleeves that are
installed above 9’-0” AFF must have vertical ladder racking installed from the bottom of the sleeve to
the top of the cable tray for lashing of cables in the vertical run.
Vertical Backbone
In a multi-store building where TRs are stacked to form a riser, a minimum of three (3) -4” sleeves
shall be installed between the stacked TRs.
3 12
1 Rensselaer Polytechnic Institute
2 Network and Telecommunications Department
3
4
5
first TR in the stack. Cable tray can be used for Inter-building Backbone distribution only with the use
of properly sized innerduct or by the installation of a physical separation for the protection of the
Backbone cables from general cable installation. Rensselaer Polytechnic Institute must approve use
of cable tray as a backbone distribution system in writing.
Telecommunication Room design shall follow all BICSI TDMM design recommendations. Rensselaer
Polytechnic Institute must approve all final design in writing. A detailed T3 drawing will be required for
Telecommunication Plans, for more information on drawing detail see BICSI TDMM 10th Edition.
General
Equipment Rooms / PBX and Service Entrance Rooms shall be located and designed on a case-by-
case basis with Rensselaer Polytechnic Institute.
General
The Interior Communications Pathways will provide a distribution system for all system cabling that
will be served by the building TRs. The pathways for a building may include all or some of the
following, cable tray, continues conduit systems, conduit stubs, sleeves, and cable hangers. All
pathways must be approved in writing by Rensselaer Polytechnic Institute prior to design completion.
Interior pathway design shall follow all BICSI TDMM design recommendations and TIA568-B and
TIA569-A standards. A detailed T1 and Pathway Logical drawing will be required for all Pathway
Plans, for more information on drawing detail see BICSI TDMM 10th Edition.
Conduit pathways built for telecommunication cabling have more stringent bending and pull
box requirements then electrical cabling and must be adhered to (i.e. a telecommunications
conduit can have no more them 180 degrees of cumulative bends between pull points where
as a conduit installed for electrical wiring may have 360 degrees of bends between pull
points).
Interior Pathways
Cable Tray
A continuous cable tray system shall be installed on each floor. Minimum tray size shall be 24" x 4"
deep with 1" rungs every 9" on floors that have a TR . For all other floors the cable tray shall be 18" x
4" deep with 1" rungs every 9". When making turn and elevation changes the appropriate tray
accessories, having the proper bend radius, must be used. For access to, and installation of, cables
in the cable tray, the following clearances are required around the cable tray. The cable tray system
shall have 1’-0” clearance measured from the top most surface of the tray. Access from the sides
shall be 6" to 1’. Access to the cable tray from below shall be unobstructed its entire length; MUST
HAVE A DROP OUT RADIUS BEND- APPROVED BY NETWORK & TELECOMMUNICATIONS
DEPARTMENT. There shall be no other equipment, lights, conduits, fixtures etc. attached to,
mounted on, running through or on the cable trays except those needed to support the tray systems.
Cable tray may not be run through walls. The tray shall stop at all walls where sleeves or conduits will
be installed, the tray shall continue on the others side of the wall. Quick-Support Center Rod PVC
6 13
1 Rensselaer Polytechnic Institute
2 Network and Telecommunications Department
Sheath ( Cat. No. WBCRSHEATH should be implemented to protect cables from threaded rod when
hanging WB Series Cable Tray from center rod hangers.
Utilize alternative to Cable Tray ( ERICO, CADDY CABLECAT Adjustable Cable Support ) where
applicable and appropriately approved by management of the RPI Network & Telecommunications
Department.
Conduit:
General
Sizes indicated for conduits are trade sizes in all cases.
Conduits shall have an insulated bushing installed prior to the installation of telecommunications
cabling.
Conduits must have the ends plugged upon installation to keep debris from entering them.
Conduit needs to run in the most direct route possible, usually parallel with building lines.
Conduit runs shall contain no continuous sections longer than 100 feet. If runs total more than 100
feet, pull points or pull boxes need to be inserted.
Conduit shall have no more than 180 degrees of cumulative bends between pull points or more than
90 degrees of bends at any one point.
Electrical Metallic Tubing shall be electro-galvanized steel.
(See specifications section 27130 for conduit detail)
Conduits run to the cable tray should end approximately 4”- 6” inches away from the top or bottom
edge of the cable tray to maintain a proper bend radius.
3 14
1 Rensselaer Polytechnic Institute
2 Network and Telecommunications Department
3
4
5
Renovations
For areas being renovated, the minimum requirement is for horizontal wiring to be properly supported
and secured in the work area in either surface raceway, communications pole, enclosed within the
wall or furniture and not exposed to possible damage. From the cable tray to the outlet location, in the
area above the drop ceiling, the cable shall be supported by CAT 6 approved cable hangers mounted
a minimum of 6” above the ceiling at a maximum distance of 3”on center.
Sleeves
Sizes indicated for sleeves are trade sizes in all cases.
Sleeves shall have an insulated bushing installed prior to the installation of telecommunications
cabling.
Sleeves must have the ends plugged upon installation to keep debris from entering them.
Sleeves used at wall transition points for cable tray systems shall be 4”. Quantity of sleeves shall be
equal to the capacity of the cable tray.
Sleeves for distribution of horizontal cable in renovated areas not having conduits to the cable tray
shall be sized so that when all cables have been installed at the completion of the project, the sleeve
will be at 40% capacity of the sleeves maximum fill.
All sleeves shall have a minimum 2-hour UL listed fire rated assembly installed regardless if the wall
or floor is not fire rated or has a rating of lesser value. If the wall or floor has a fire rating greater than
2 hours the sleeve shall have an equal rating in all cases
The minimum sleeve size installed for any penetration shall be 2”.
General
The Exterior Communications Pathways will provide a campus distribution system for all system
cabling that will be served by the TRBs. The pathways for a campus distribution system may include
all or some of the following, maintenance holes, hand holes, innerduct for both in conduits and direct
buried, conduit, multi-cell conduits, All pathways must be approved in writing by Rensselaer
Polytechnic Institute prior to design completion. Exterior pathway design shall follow all BICSI TDMM
and BICSI Customer Owned Outside Plant Design Manual design recommendations and TIA568B
and 569A standards. Rensselaer Polytechnic Institute must approve all final design in writing. A
detailed T0 and Pathway logical drawing will be required for all Pathway Plans, for more information
on drawing detail see BICSI TDMM 10th Edition.
Conduit pathways built for telecommunication cabling have more stringent bending and pull
box requirements than electrical cabling and must be adhered to (i.e. a telecommunications
conduit can have no more than 180 degrees of cumulative bends between pull points where as
a conduit installed for electrical wiring may have 360 degrees of bends between pull points).
6 15
1 Rensselaer Polytechnic Institute
2 Network and Telecommunications Department
Exterior Pathways
General
Sizes indicated for conduits and innerduct are trade sizes in all cases.
For quantities see Backbone Inter-Building in section 27110.
Conduit
All conduits will be in the form of 4” in all cases.
Conduits must have the ends plugged upon installation to keep debris from entering them.
Conduit runs shall contain no continuous sections longer than 200 feet. If runs total more than 200
feet, pull points need to be inserted.
Conduit shall have no more than 180 degrees of cumulative bends between pull points or more than
90 degrees of bends at any one point.
All bends must be long, sweeping bends with a radius not less than six times the internal diameter of
conduits 50 mm (2 in) or smaller, or ten times the internal diameter of conduits larger than 50 mm (2
in).
All conduits must be mandreled prior to turning over to Network & Telecommunications Department of
occupancy.
All ends of conduit must be reamed.
All conduits entering a building must be pitched to drain away from the building to avert water
intrusion.
To prevent conduit shearing, conduits enter through walls shall be metal and extend to undisturbed
earth, particularly where such backfill is susceptible to load bearing tension.
All conduits that do not have innerduct install inside of them shall be threaded with pull ropes with
footage markers.
Rigid Galvanized Steel Conduit shall be hot-dipped galvanized steel, including threads.
Rigid Non-Metallic PVC Conduit
Extra-Heavy wall conduit: Schedule 80, constructed of polyvinyl chloride, rated for use with 90 degree
C conductors, and UL listed for direct burial and normal above ground use.
Heavy wall conduit: Schedule 40, constructed of polyvinyl chloride, rated for use with 90 degree C
conductors, and UL listed for direct burial and concrete encasement.
(See specifications section 27140 for exterior conduit detail)
Encasement
All underground conduits shall be concrete encased with reinforcing bars.
Conduit Orientation
Manufactured conduit spacer shall be used for all conduits in the ductback so conduits can maintain
the same orientation at all points of access.
Innerducts
3 16
1 Rensselaer Polytechnic Institute
2 Network and Telecommunications Department
3
4
5
For quantities see Horizontal Backbone Inter-Building in section 27110.
Innerducts must have the ends plugged upon installation to keep debris from entering them.
All innerducts shall be threaded with pull ropes with footage markers.
Innerduct shall not be directly buried or concert incased as a replacement to conduits.
Maintenance Holes
General
Joint Use Maintenance Holes (MHs) are not permitted
Covers
Covers shall always be round and centrally located on single- cover maintenance holes.
Frames and covers used in roads or driveways shall be rated to withstand vehicular traffic.
For MH over 3.7 m (12 ft) long, follow these guidelines:
Between 3.7 m (12 ft) and 6 m (20 ft) use two covers.
Over 6 m (20 ft), use three covers.
Interior Hardware
All hardware in MHs must be galvanized.
MHs shall be equipped with the following:
Bonding inserts and struts for racking.
Pulling eyes at least 22 mm (7/ 8 in) in diameter.
A sump of at least 200 mm (8 in) in diameter.
An entry ladder (where feasible).
Identifying Covers
All covers shall have TELECOMMUNICATIONS pre-marked on the cover for easy identification.
Concrete Strength
The strength of concrete used for MHs shall be at least 24 000 kPa (3500 psi).
NOTE: Stronger concrete may be stipulated in certain installations.
6 17
1 Rensselaer Polytechnic Institute
2 Network and Telecommunications Department
Handhole
General
Handholes (HHs) are smaller than maintenance holes (MHs), but the covers provide full access to the
entire space inside the hole. HH shall be used as pull- through points only. HHs shall not be used as
splice points, unless specified by the project manager. HH shall not be used in conduit runs that have
more than three (3) 4in conduits.
Covers
Covers shall always be round and centrally located handholes.
Frames and covers used in roads or driveways shall be rated to withstand vehicular traffic.
Identifying Covers
All covers shall have TELECOMMUNICATIONS pre-marked on the cover for easy identification.
3 18
1 Rensselaer Polytechnic Institute
2 Network and Telecommunications Department
3
4
5
6 19
1 Rensselaer Polytechnic Institute
2 Network and Telecommunications Department
General
Backbone cabling is the media over which Voice, Video, Data, Audio, Community antenna television
(CATV) signals will be transmitted to the TR’s. The media used for the transmission of the signals will
be copper, fiber and coax. Backbone cables are broken into two types, inter-building and intra-
building. Inter-building cabling has very strict requirements when entering a building. Cable insulation
type, lightning protection and termination methods are important considerations when designing
outside plant (OSP) cabling.
Sizing of backbone cabling for support of a building is directly related to the building’s functions both
during initial occupancy and future use. There is no generic backbone installation that will fit all
applications. Design of the building’s backbone cabling will be on a case-by-case basis. Generally,
Optical Fiber, High Pair Count Copper and Coaxial cable will be install for backbone applications.
Backbone cable design shall follow all BICSI TDMM design recommendations and TIA568B
standards. Network & Telecommuncations Department must approve all final design in writing. A
detailed T1 and Backbone logical drawings will be required for all Backbone cabling Plans, for more
information on drawing detail see BICSI TDMM 10th Edition.
General
The following will describe the minimum work area outlet requirements for area such as, a standard
8”x10” office, classroom and conference room, special locations and residents halls. The exact
placement and quantities of outlets and pathways must be approved in writing by Network &
Telecommunications Department prior to design completion.
Any deviation from this shall require written approval from the Network & Telecommunications
Project Manager.
Backbone cable design shall follow all BICSI TDMM design recommendations and TIA568B
standards. Rensselaer Polytechnic Institute must approve all final design in writing. Detailed T2
drawings will be required for all Cabling Plans, for more information on drawing detail see BICSI
TDMM 10th Edition.
In general, install one network drop on each wall measuring 12’-0” in linear length. Provide additional
work area outlets as required so that no “point” along the liner wall space is more then 12’-0” from a
network outlet. This rule is intended to keep the network station cord from exceeding the maximum
length of 16’-0” from the wall outlet to the network device.
A minimum of one duplex electrical outlet shall be installed within 16”, but not closer than 8”, of every
work area outlet. If more then 2 data cables are installed at a single work area outlet location, add
duplex electrical outlets in the same proportion.
Classroom
Each classroom shall have a minimum of two (2) work area outlets and one wall phone outlet. One
(1) of the work area outlets shall be an coax drop. The wall phone outlet shall be in the front of the
room near the door. The remaining outlet will be located on the wall opposite of the front of the
classroom.
3 20
1 Rensselaer Polytechnic Institute
2 Network and Telecommunications Department
3
4
5
Conference room
Each conference room shall have a minimum of two (2) work area outlets. One (1) of the work area
outlets shall be a coax drop. Location shall be determined on a case-by-case basis.
Special locations
Computer rooms, labs, shared workspaces and other such areas must be reviewed on an individual
basis for the quantity and types of work area outlets required.
General
Bedroom
There shall be 1 (one) coax outlet for each room. Location shall be determined on a case-by-case
basis.
Coax Outlet
A Coax outlet is comprised of one quad-shielded coax cable. The location of a coax outlet will be located
on a case by case basis. The faceplates shall be a single gang type.
6 21
1 Rensselaer Polytechnic Institute
2 Network and Telecommunications Department
A wireless access point is comprised of one 4-pair Category 6 twisted pair data cable (violet). The
location will typically be located above the drop ceiling when possible and terminated in a typical
surface or flush mounted jack. The cable will be terminated, tested. The locations for these cables
shall be determined by the Network & Telecommunications Department. Contact and arrange for
these engineering services on a per project basis and coordinate closely with Rensselaer Polytechnic
Institute.
Testing
2 Testing of Copper UTP cables shall conform to the requirements of TIA 568-B.1
3 Testing of Optical Fiber cables shall conform to the requirements of TIA 568-B.1
Identification
4 Identification of Cabling, Pathways and Hardware shall conform to TIA 606-A
3 22