Using 1062 /8101 Keypad Engineering Setup Menu

NOTE: 1 the Passwords are the default passwords. They may be


different if panel has already been configured

NOTE: 2 when the System is in Engineering Mode all alarms are


disabled except point type “Raid Points” and the flag
“Raid Alarms in Engineering Mode” is selected

1> NIGHT MODE Push the ‘DAY’ key


22/05/09 16:00

Enter ‘1’ then the ‘ENT’ key


ENTER ID

Enter ‘2461’ then the ‘ENT’ key


ENTER PIN

ACCESS GRANTED Will be displayed briefly


OUTSIDE HOURS

F1= TEMP ACCESS


Push ‘F2’ key
F2= STAY

F1= DAY MODE


F2= STAY NIGHT Push ‘F1’ key

1> DAY MODE


Push the ‘MENU’ key
FRIDAY 16:00

F1=ATM F2=SERV Push the ‘F4’ key


F3=AUX F4=MENU

Enter ‘2’ then the ‘ENT’ key


ENTER ID

Enter ‘2462’ then the ‘ENT’ key


ENTER PIN

1> Engin Mode Push the ‘MENU’ key


22/05/09 16:00

TEST MODE
Push the ‘F2’ key
F1=PgDn F2=PgUp
Using 1062 /8101 Keypad Engineering Setup Menu

SETUP
F1=PgDn F2=PgUp Push the ‘ENT’ key

F1=RTU# F2=TIME Push the ‘F1’ key


F3=PROG F4=NETWK

Rtu Number _ Enter the RTU number then push


the ‘ENT’ key

Writing to EEprom
After this is displayed the RTU will restart. You
will need to log on again to go to next step

F1=RTU# F2=TIME Pushing the ‘F2’ key


F3=PROG
F4=NETWK
New Time (hhmm) Enter correct time 0 to 24
hours 0 60 minutes

Date (YYMMDD) Enter correct date

Enter correct Day but entering the day number 1=


Day (1=Sunday)
Sunday 2= Monday 3= Tuesday

F1=RTU# F2=TIME Pushing the ‘F3’ key


F3=PROG F4=NETWK

F1=Inovnx F2=EOL Pushing the ‘F1’ key


F3=DiagPt F4=Nxt

F1=InovTX Pushing the ‘F1’ key


F3=InovRX

F1=ProgTX F2=Register TX F1= Program Transmitters is


F3=IStatus F4=De-RegTX for 403 receivers only

No 403 Receiver If the 403 has not been


Found configured in Port Parameters

TX IDM:

TX IDL: This is the Application ID


Using 1062 /8101 Keypad Engineering Setup Menu
This is the Receiver ID

EOL Resistor ?
F1=YES F2=NO

External switch
F1=N/O F2=N/C

External contact
F1=YES F2=NO

Internal contact
F1=YES F2=NO

Frequency ?
F1 AUS F2=US

Checkin Time:
Value 0 -7

Correct cable to TX This is the Reset Button on the


Press Reset button on TX
403

F1=ProgTX F2=Register TX Pushing the ‘F2’ key Note: This will


F3=Status F4=De-RegTX add Transmitted that has been De-
RegTX Echo Stream only

Input: _ Enter input number

Input: xx Push the Reset button on the


Hit RESET button Transmitter

TX Registered
ENT to Accept

ALm Bat Tmp Sig


Push the DEL/ESC key
OFF OFF OFF - - -

F1=ProgTX F2=Register TX
F3=Status F4=De-RegTX Pushing the ‘F3’ key
Using 1062 /8101 Keypad Engineering Setup Menu

Input: xx Enter input number

ALm Bat Tmp Sig


Push the DEL/ESC key
OFF OFF OFF - - -

F1=ProgTX F2=Register TX Pushing the ‘F4’ key Note: the


F3=Status F4=De-RegTX RTU will not report any alarms
from this point and will have to be
registered again Echo Stream Only

Input: xx Enter input number

TX De-Registered

F1=InovTX This is for the FA 400 Note: this can also


F3=InovRX be set in System Parameters

Max Checkin Time How often the Receiver expects a


(mins) = 0 transmitter to check in

RTU Port: This is whish port the 1068 is hooked to.


Note the RTU will automatically find it

Rx Addr: This is the Address of the 1068. Note the


RTU will automatically find it

New IDH: _ This is the System number and can also


be programmed in System Parameters

Receiver Found If the receiver was found then this


IDH Programmed message will be displayed

No 400 Receiver If the receiver was NOT found then


Found this message will be displayed
Using 1062 /8101 Keypad Engineering Setup Menu

F1=Inovnx F2=EOL Pushing the ‘F2’ key


F3=DiagPt F4=Nxt

aaasss x100 Ohm 1065/1064


_0 0 aaa= alarm sss= secure

Writing to EEprom

F1=Inovnx F2=EOL
Pushing the ‘F3’ key
F3=DiagPt F4=Nxt

EPCP PCP= 4800 baud


F1=PCP F2=EPCP
EPCP = 38400

F1=Inovnx F2=EOL F4 Nxt was added in version 5


F3=DiagPt F4=Nxt
older version it was RAP

F1=RAP F2=Licens Pushing the ‘F1’ key

RAP users Setting the Number of Controller users


F1=99 F2=66 to 99 (6 digit Pins) or 66 (8 digit Pins

WARNING-reset
RAP type _

F1=RAP F2=Licens Pushing the ‘F2’ key

F1 will enable all licenses for


Enable Grace?
F1=YES F2=NO 14 days

Grace Enabled If F1 is selected then this will


be displayed

F1=RTU# F2=TIME Pushing the ‘F4’ key


F3=PROG F4=NETWK

F1=LI
If the License is not enabled select F1
Using 1062 /8101 Keypad Engineering Setup Menu

After entering a Number press the


CODE x
ENT for the next number. Note: F1 =
A-F

F1=IP PARAMETERS
Pushing the ‘F1’ key
F3=DIAL F4= EMCS

RTU IP ADDRESS Enter the IP Address. Note: the


_10. 1. 1. 1 ‘ENT’ will take you to next field

RTU IP MASK Enter the IP Mask. Note: the ‘ENT’


255. 0. 0. 0 will take you to next field

ROUTER IP ADDR Enter the router IP Address. Note: the


_ 0. 0. 0. 0 ‘ENT’ will take you to next field

LC IP ADDRESS Enter the Line card IP Address. Note:


_ 0. 0. 0. 0 the ‘ENT’ will take you to next field

F1=IP PARAMETERS Pushing the ‘F3’ key


F3=DIAL

F1=PACOM F2=CID Push the appropriate ‘F’ key


F3=SIA

Phone Number. . .
Enter the phone number

Dialing now . . .
Using 1062 /8101 Keypad Engineering Setup Menu

To Exit Engineering MODE

F1=RTU# F2=TIME If this is displayed push the ‘MENU’ key


F3=PROG F4=NETWK

TEST MODE If this is displayed push the ‘MENU’ key


F1=PgDn F2=PgUp

LOG OFF If this is displayed push the ‘F3’ key


F3=YES F4=NO

1>Engin Mode If this is displayed push the ‘DAY’ key


22/05/09 16:00