Classic Series: F100 (Globe) F1100 (Angle)

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

R

F100 (Globe)
Classic Series F1100 (Angle)
1/05

Standard Materials Globe Angle


Body & Cover: Ductile Iron ASTM A536 L
Coating: NSF Listed Fusion D M
Bonded Epoxy Lined
and Coated
Trim: 316 Stainless Steel (1-1/4” – 8”)
K
ASTM B62 Bronze (10” – 24”)
(Stainless Steel Optional)
H I J
Elastomers: Buna-N (standard)
EPDM (optional)
Viton (optional)
A E
Stem, Nut & Stainless Steel B F
Spring: C G

Dimensions
A B C D E F G H I J K L M
VALVE GLOBE GLOBE GLOBE COVER TO ANGLE ANGLE ANGLE ANGLE ANGLE ANGLE PORT PORT PORT SHIPPING
SIZE THRD. 150# 300# CENTER THRD. 150# 300# THRD. 150# 300# SIZE SIZE SIZE WEIGHTS*
1-1/4 7-1/4 3-1/2 3-1/4 1-7/8 1/4 1/2 1/8 15
1-1/2 7-1/4 8-1/2 9 3-1/2 3-1/4 4 1-7/8 4 1/4 1/2 1/8 15
2 9-3/8 9-3/8 10 4-15/16 4 4 4-1/4 4 4 4-1/4 1/2 1/2 1/4 35
2-1/2 11 11 11-5/8 7 5-1/2 5-1/2 5-13/16 4 4 4-5/16 1/2 1/2 3/8 65
3 10-1/2 12 13-1/4 7 5-1/4 5-3/4 6-1/8 5-1/4 5-3/4 6-1/8 1/2 1/2 3/8 95
4 15 15-5/8 8-5/8 6-3/4 7-1/8 6-3/4 7-1/8 1/2 1/2 3/8 190
6 20 21 11-3/4 8-1/2 8-7/8 8-1/2 8-7/8 1/2 1/2 1/2 320
8 25-3/8 26-3/8 15-3/4 11 11-1/2 11 11-1/2 1/2 1 1/2 650
10 29-3/4 31-1/8 18-3/4 14-7/8 15-5/8 14-7/8 15-5/8 1 1 1 940
12 34 35-1/2 20-5/8 17 17-3/4 17 17-3/4 1 1 1 1500
14 39 40-1/2 22-1/4 1 1 1 1675
16 41-3/8 43-1/2 26-1/4 1 1 1 3100
*Estimated in lbs.

Description
The Watts ACV Models F100 and F1100 are single chamber basic valves that incorporate a one-piece disc and
diaphragm assembly. This assembly is the only moving part within the valve allowing it to open, close, or modulate as
commanded by the pilot control system.
Model F100: Globe Pattern Single Chamber Basic Valve
Model F1100: Angle Pattern Single Chamber Basic Valve
Operating Pressure
Threaded = 400 psi / 150 Flanged = 250 psi / 300 Flanged = 400 psi
Operating Temperature
Buna-N: 160°F Maximum
EPDM: 300°F Maximum
Viton: 250°F Maximum

8550 Hansen Road • Houston, Texas 77075 • (Ph) 713.943.0688 • (Fx) 713.944.9445 • www.wattsacv.com
Flow Data - ACV F100 (Globe) / F1100 (Angle)
Valve Size - Inches 1-1/4 1-1/2 2 2-1/2 3 4 6 8 10 12 14 16
Maximum Continuous
93 125 208 300 460 800 1800 3100 4900 7000 8500 11000
Flow Rate Gpm (Water)
Maximum Intermittent
115 158 260 370 570 1000 2300 3900 6000 8600 10500 14000
Flow Rate Gpm (Water)
CV Factor GPM (Globe) 25.9 25.67 44.9 87.4 103.1 205.6 414 830 1211 1657 2100 2270
CV Factor GPM (Angle) 39 53 66 99 170 280 650 1100 1600 2500 3060 4210
Estimated

Maximum continuous flow based on velocity of 20 ft. per second.


Maximum intermittent flow based on velocity of 25 ft. per second.
The Cv Factor of a value is the flow rate in US GPM at 60° F that will cause a 1 psi drop in pressure.
The factors stated are based upon a fully open valve.
Cv factor can be used in the following equations to determine Flow (Q) and Pressure Drop (∆ P):

Q (Flow) = Cv ∆ P ∆ P (Pressure Drop) = (Q/CV)2

Headloss
Angle

2-1/ 2-1/2
4
2
1-1/
1-1/

10
12
14
16
4

8
6
3
22
Globe
1-1/ 4
2
1-1/

10
12
14
16
4

8
6
3
2
100
80
60

40

30
Pressure Drop (p.s.i.)

20

10
8
6

4
3

2 4 6 8 10 20 40 60 80 100 200 500 1000 2000 5000 10000 20000


100,000 Flow Rate - Gallons per minute (Water)

Valve Cover Chamber Capacity


Valve Size (in) 1-1/4 1-1/2 2 2-1/2 3 4 6 8 10 12 14 16
fl.oz. 4 4 4 10 10 22 70
U.S. Gal 1-1/4 2-1/2 4 6-1/2 9-1/2

Valve Travel
Valve Size (in) 1-1/4 1-1/2 2 2-1/2 3 4 6 8 10 12 14 16
Travel (in) 3/8 3/8 1/2 5/8 3/4 1 1-1/2 2 2-1/2 3 3-1/2 4

8550 Hansen Road • Houston, Texas 77075 • (Ph) 713.943.0688 • (Fx) 713.944.9445 • www.wattsacv.com