General Notes & Specifications: Electrical
General Notes & Specifications: Electrical
PROVINCE OF ANTIQUE
1. ALL ELECTRICAL WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH THESE PLANS AND CIRCUIT C15 SPARE 500 VA allocated
CIRCUIT C1 12-100VA Lighting Outlet CIRCUIT C7 Special Purpose Outlet 1HP ACU CIRCUIT C11 Special Purpose Outlet 1HP ACU MUNICIPALITY OF PANDAN
SPECIFICATIONS, THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE (PEC), I = [(13x20)]/230 = 1.1 A Full Load Current If = 2.2 A
Full Load Current If = 8A Full Load Current If = 8A
THE REGULATIONS OF NATIONAL AND LOCAL AUTHORITIES CONCERNED IN THE ENFORCEMENT
Ic = 1.1 x 1.25 = 1.37 A Ic =8 x 1.25 = 10 A Ic =8 x 1.25 = 10 A Ic =2.2 x 1.25 = 2.75 A OFFICE OF THE BUILDING OFFICIAL
OF ELECTRICAL LAWS, AND THE REQUIREMENTS OF THE ELECTRIC POWER & TELEPHONE
A: 2-3.5 sq. mm. THHN Cu. Wire IN 20mmØ Conduit Ip =8 x 1.50 = 12 A Ip =8 x 1.50 = 12 A Ip =2.2 x 1.50 = 3.3 A
UTILITY COMPANY.
15AT, CB, 2P, 230V, 10KAIC B: 2-3.5 sq. mm. THHN Cu. Wire + 1-3.5 sq.mm. B: 2-3.5 sq. mm. THHN Cu. Wire + 1-3.5 sq.mm. THHN Cu Wire in 20mm.dia. conduit
2. TYPE OF SERVICE SHALL BE 230-V, SINGLE-PHASE, 2-WIRE, 60-Hz. THHN Cu Wire in 25mm.dia. conduit THHN Cu Wire in 25mm.dia. conduit 20AT, CB, 2P, 230V, 10KAIC
CIRCUIT C2 12-100VA Lighting Outlet 20AT, CB, 2P, 230V, 10KAIC 20AT, CB, 2P, 230V, 10KAIC
I = [(16x20)]/230 = 1.4 A CIRCUIT C16 SPARE 500 VA allocated
3. WIRING METHOD SHALL BE IN RIGID PVC CONCEALED ON WALLS, SLABS, CEILINGS OR Ic = 1.4 x 1.25 = 1.75 A CIRCUIT C8 Special Purpose Outlet 1HP ACU CIRCUIT C12 Special Purpose Outlet 1HP ACU
PARTITIONS. ALL MATERIALS TO BE INSTALLED SHALL BE BRAND NEW AND APPROVED TYPE Full Load Current If = 2.2 A
A: 2-3.5 sq. mm. THHN Cu. Wire IN 20mmØ Conduit Full Load Current If = 8A Full Load Current If = 8A
FOR LOCATION AND PURPOSE. Ic =8 x 1.25 = 10 A Ic =8 x 1.25 = 10 A Ic =2.2 x 1.25 = 2.75 A
15AT, CB, 2P, 230V, 10KAIC
Ip =8 x 1.50 = 12 A Ip =8 x 1.50 = 12 A Ip =2.2 x 1.50 = 3.3 A
4. MOUNTING HEIGHTS SHALL BE: B: 2-3.5 sq. mm. THHN Cu. Wire + 1-3.5 sq.mm. B: 2-3.5 sq. mm. THHN Cu. Wire + 1-3.5 sq.mm. THHN Cu Wire in 20mm.dia. conduit
LIGHT CONTROL SWITCHES - 1.30m ABOVE FINISHED FLOOR LINE CIRCUIT C3 16-180VA Duplex Convenience Outlet
THHN Cu Wire in 25mm.dia. conduit THHN Cu Wire in 25mm.dia. conduit 20AT, CB, 2P, 230V, 10KAIC
CONVENIENCE OUTLET - 0.30m ABOVE FINISHED FLOOR LINE I = (8x180) / 230 = 6.3 A ELECTRICAL
20AT, CB, 2P, 230V, 10KAIC 20AT, CB, 2P, 230V, 10KAIC
PANELBOARD - 1.8m FROM TOP OF PANEL TO FINISHED FLOOR LINE B: 2-3.5 sq. mm. THHN Cu. Wire in 20mmØ Conduit
CIRCUIT C17 SPARE 500 VA allocated
OTHER OUTLETS - AS SPECIFIED IN THE PLAN 20AT, CB, 2P, 230V, 10KAIC CIRCUIT C9 Special Purpose Outlet 1HP ACU CIRCUIT C13 Special Purpose Outlet 1HP ACU
Full Load Current If = 2.2 A
Full Load Current If = 8A Full Load Current If = 8A
CIRCUIT C4 16-180VA Duplex Convenience Outlet Ic =8 x 1.25 = 10 A Ic =2.2 x 1.25 = 2.75 A
5. WHENEVER REQUIRED AND NECESSARY, PULL BOXES AND JUNCTION BOXES OF APPROPRIATE Ic =8 x 1.25 = 10 A
I = (5x180) / 230 = 3.9 A Ip =8 x 1.50 = 12 A Ip =8 x 1.50 = 12 A Ip =2.2 x 1.50 = 3.3 A
SIZES SHALL BE INSTALLED AT CONVENIENT LOCATIONS ALTHOUGH SUCH BOXES ARE
NOT SHOWN ON THE PLANS. B: 2-3.5 sq. mm. THHN Cu. Wire in 20mmØ Conduit B: 2-3.5 sq. mm. THHN Cu. Wire + 1-3.5 sq.mm. B: 2-3.5 sq. mm. THHN Cu. Wire + 1-3.5 sq.mm. THHN Cu Wire in 20mm.dia. conduit
20AT, CB, 2P, 230V, 10KAIC THHN Cu Wire in 25mm.dia. conduit THHN Cu Wire in 25mm.dia. conduit 20AT, CB, 2P, 230V, 10KAIC
6. FOR EACH SPARE BRANCH CIRCUITS IN PANELBOARDS, PROVIDE ONE 20mm DIA. CONDUIT 20AT, CB, 2P, 230V, 10KAIC 20AT, CB, 2P, 230V, 10KAIC
TERMINATED TO A 100mm OCTAGONAL BOX ABOVE. PROVIDE GALVANIZED PULL CIRCUIT C5 16-180VA Duplex Convenience Outlet
I = (8x180) / 230 = 6.3 A CIRCUIT C10 Special Purpose Outlet 1HP ACU
WIRES IN ALL EMPTY CONDUITS.
B: 2-3.5 sq. mm. THHN Cu. Wire in 20mmØ Conduit Full Load Current If = 8A
7. ALL WORKS HEREIN SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULY LICENSED 20AT, CB, 2P, 230V, 10KAIC Ic =8 x 1.25 = 10 A
ELECTRICAL ENGINEER (PEE/REE) OR A REGISTERED MASTER ELECTRICIAN (RME). Ip =8 x 1.50 = 12 A
CIRCUIT C6 16-180VA Duplex Convenience Outlet B: 2-3.5 sq. mm. THHN Cu. Wire + 1-3.5 sq.mm.
I = (7x180) / 230 = 5.5 A THHN Cu Wire in 25mm.dia. conduit
B: 2-3.5 sq. mm. THHN Cu. Wire in 20mmØ Conduit 20AT, CB, 2P, 230V, 10KAIC
20AT, CB, 2P, 230V, 10KAIC
DISTRIBUTION PANEL
Size Conductor Ic = 1.25 {84.8 + (8 x .25) = 108.5 A
Use 2 - 38 mm² THW Cu + 1 - 14 mm² TW
Use Over Current Protection Device 125 AT. 2 pole, 60Hz.
PTR NO. :