B. THE CONTRACTOR SHALL VERIFY THE SIZES, DIMENSIONS AND LOCATIONS OF ALL
EXISTING STRUCTURES ON SITE. DISCREPANCIES BETWEEN THESE DRAWINGS AND THE
.30L1 .30 L2 .30 L2 .30 L3 .30 L3
ACTUAL CONDITIONS SHALL BE RELAYED TO DCCD SO THAT DETAILS MAY BE REVISED
TO SUIT ACTUAL SITE CONDITIONS.
C. ALL REINFORCED CONCRETE WORK SHALL BE DONE IN ACCORDANCE WITH THE NATIONAL TYPICAL 1- WAY SLAB DETAILS
STRUCTURAL CODE OF THE PHILIPPINES (NSCP) VOL. 1, 1992 EDITION, CHAPTER 5, AND
THE ACI 318-95 BUILDING CODE.
B. ALL STRUCTURAL STEEL PLATES AND SHAPES SHALL CONFORM TO ASTM A36
(MINIMUM SPECIFIED YIELD STRENGTH, fy = 36 ksi).
C. ALL WELDS SHALL BE CONTINUOUS FILLET WELDS, USING NOT LESS THAN THE
TYPICAL 2- WAY SLAB DETAIL
MINIMUM SIZE BASED ON THE THICKNESS OF THE THINNER PART JOINED PER AISC/
AWS AND IN NO CASE LESS THAN 6mm. ALL WELDING ELECTRODES SHALL BE E70xx. 1 SLAB REINFORCEMENT DETAIL
S 2
NOTES ON CONCRETE MIXED AND PLACING FROM 1" X 1" X 1/4" THK.
ANGLE BAR NOSING AS SHOWN FINISH FLOOR LINE
.10
A. CONCRETE SHALL HAVE A MINIMUM 28-DAY CYLINDER COMPRESSIVE STRENGTH AS FOLLOWS: 150 10MM.Ø NOSING BAR SPACED @
EVERY 0.15M. O.C. EXT'G. GRADE LINE
25
1) COLUMNS, BEAMS GIRDERS, WALLS, AND SLABS ----------------- 21.0 MPa (3000 psi)
0.
1
25
2) FOUNDATION, PARTITIONS,, NON-STRUCTURAL WALLS, --------- 21.0 MPa (3000 psi) PROVIDE 10MM.THK. 7-16MM Ø VERT. BARS WITH
GRAVEL FILL AS SHOWN
SIDEWALKS, CURBS, GUTTERS, AND OTHER NON- 10 MM.Ø TIES (DOUBLE) SPACED @
0.20
12MM.Ø MAIN BARS SPACED
STRUCTURAL ELEMENTS
@ EVERY 0.15M. O.C. TOP
AND BOTTOM BAR NOTE : 1-0.05M., 2 @ 0.10M., 3 @ .15M.
AND REST @ 0.20M. O.C.
H
0.18M. RISER SPACING FROM FROM 1" X 1" X 1/4" THK.
12MM.Ø TEMP. BAR SPACED
3) LEAN CONCRETE --------- 10.0 MPa (1500 psi) @ EVERY 0.20M. O.C. 2ND FLR. TO 3RD FLR. TO ANGLE BAR NOSING AS SHOWN
7-16 MM.Ø TEMP.BARS PROVIDE 3-10MM.Ø
ROOF DECK
EQUALLY SPACED BOTH WAYS EXTRA LATERAL TIES
N. G. L. 10MM.Ø NOSING BAR SPACED @
.30 EVERY 0.15M. O.C.
B. CONCRETE SHALL BE DEPOSITED IN ITS FINAL POSITION WITHOUT SEGREGATION, RE-HANDLING
0.50
OR FLOWING. PLACING SHALL BE DONE PREFERABLY WITH BUGGIES, BUCKETS OR WHEEL
.05
T
0.
0.70
15
BARROWS. NO CHUTES WILL BE ALLOWED EXCEPT TO TRANSFER CONCRETE FROM HOPPER
100
0.18
TO BUGGIES, WHEEL BARROWS OR BUCKETS, IN WHICH CASE, THEY SHALL NOT EXCEED SIX (6) 12MM.Ø @ EVERY 0.12M. 0.C.
TOP AND BOTTOM BAR PROVIDE 10MM.THK.GRAVEL
FILL AS SHOWN
METERS IN AGGREGATE LENGTH. PROVIDE 10MM.THK.GRAVEL FILL L
AS SHOWN 12MM.Ø TEMPERATURE BAR
SPACED @ EVERY 0.15M. O.C.
C. NO DEPOSITING OF CONCRETE SHALL BE ALLOWED WITHOUT THE USE OF VIBRATORS UNLESS
250
12 MMØ @ 0.15 M. O.C. WITH C/F SECTION
3-12MM Ø LONG BARS SCALE 1:30M.
AUTHORIZED IN WRITING BY THE DESIGNERS AND ONLY FOR UNUSUAL CONDITIONS WHERE
VIBRATION IS EXTREMELY DIFFICULT TO ACCOMPLISH. STAIR DETAIL SECTION STAIR STEPS DETAIL SECTION
SCALE 1 : 20 M. SCALE 1 : 20 M.
.10 m. (4")
VER.
0.80M. O.C. AND 10MM.Ø HOR. BAR @ EVERY
3RD LAYER EXT'G. GRADE LINE FINISH FLR. LINE
EXT'G. GRADE LINE
NATURAL GRADE LINE
NATURAL GRADE LINE
VERIFY
0.10M. THK. CONC. SLAB WITH PROVIDE 10MM.THK.GRAVEL FILL
10MM.Ø TEMP. BAR SPACED @ AS SHOWN
EVERY 0.40M. O.C. BOTHWAY USE 10mmØ TIES, 1 @ 0.05m, 2 @ 0.10m,
400
400
H
FTB-1 FTB-1 FTB-1
NATURAL GRADE LINE PROVIDE 3-10MM.Ø
7-16 MM.Ø TEMP.BARS EQUALLY
50
50
T
100
T
3-10MM.Ø CONT. BAR WITH
10MM. THK. GRAVEL FILL SHORT BAR SPACED @ EVERY 10MM. THK. GRAVEL FILL
3-10MM.Ø CONT. BAR WITH 50 50
0.30M. O.C. PROVIDE 10MM. THK.
250 10MM. THK. GRAVEL FILL 250 SHORT BAR SPACED @ EVERY 150 B (m) 7-16 MM.Ø TEMP.BARS
0.30M. O.C. GRAVEL FILL AS SHOWN
EQUALLY SPACED BOTH WAYS
L
WF-1 SECTION CWF-1 SECTION WF-2 SECTION CF / FTB DETAIL SECTION C/CF SECTION
SCALE 1: 20 M. SCALE 1: 20 M. SCALE 1 : 20 M. NOT TO SCALE
SCALE 1:30M.
SEC 3 RA 9266
DRAWINGS AND SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS
DULY SIGNED, STAMPED OR SEALED AS INSTRUMENTS OF SERVICE
ARE THE INTELLECTUAL PROPERTY AND DOCUMENTS OF THE
ARCHITECT,WHETHER THE OBJECT FOR WHICH THEY ARE MADE IS
EXECUTED OR NOT, IT SHALL BE UNLAWFUL FOR ANY PERSON TO
DUPLICATE OR MAKE COPIES OF SAID DOCUMENTS FOR USE IN THE
REPETITION OF AND FOR OTHER PROJECTS OR BUILDINGS, WHETHER
EXECUTED PARTLY OR IN WHOLE, WITHOUT THE WRITTEN CONSENTOF
ARCHITECT OR AUTHOR OF SAID DOCUMENTS.