6EP19612BA00 Datasheet en

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Data sheet 6EP1961-2BA00

SITOP SELECT DIAGNOSIS MODULE


SITOP select Diagnostics module 4-channel input: 24 V DC/40 A
output: 24 V DC/4x 10 A Level adjustable 2-10 A

Input
Type of the power supply network Controlled DC voltage (SITOP select is not designed for operation
with DC UPS module 40 A (6EP1 931-2FC21/-2FC42)
Supply voltage / at DC / Rated value 24 V
Input voltage / at DC 22 ... 30 V
Overvoltage overload capability 35 V; 100 ms
Input current / at rated input voltage 24 V / Rated 40 A
value

Output
Voltage curve / at output controlled DC voltage
Formula for output voltage Vin - approx. 0.3 V
Relative overall tolerance / of the voltage / Note In accordance with the supplying input voltage
Number of outputs 4
Output current / up to 60 °C / per output / rated value 10 A
adjustable pick-up value current / of the current- 2 ... 10 A
dependent overload release
Type of response value setting via potentiometer
Product feature
● parallel switching of outputs No

6EP1961-2BA00 Subject to change without notice


Page 1/3 08/14/2020 © Copyright Siemens
● bridging of equipments Yes
Type of outputs connection Simultaneous connection of all outputs after power up of the
supply voltage, delay time of 24 ms or 100 ms programmable for
sequential connection

Efficiency
Efficiency in percent 97 %
Power loss [W] / at rated output current / for rated 30 W
value of the output current / typical

Switch-off characteristic per output


Switching characteristic
● of the excess current Iout = 1.0 ...1.3 x set value, switch-off after approx. 5 s
● of the current limitation Iout = 1.3 x set value, switch-off after approx. 50 ... 100 ms
● of the immediate switch-off Iout > set value and Vin < 20 V, switch-off after approx. 0.5 ms
Residual current at switch-off / typical 20 mA
Design of the reset device/resetting mechanism Using keys on the module
Remote reset function -

Protection and monitoring


Fuse protection type / at input Blade-type fuse per output (equipped when delivered with 15 A
fuse)
Display version / for normal operation Two-color LED per output: green LED for "Output switched
through"; red LED for "Output switched off due to overcurrent"
Design of the switching contact / for signaling Common signal contact (NO contact, rating 0.5 A/24 V DC)
function

Safety
Galvanic isolation / between input and output at No
switch-off
Standard / for safety according to EN 60950-1 and EN 50178
operating resource protection class Class III
Protection class IP IP20

Approvals
Certificate of suitability
● CE marking Yes
● UL approval Yes; UL-Recognized (UL 2367) File E328600; cULus-Listed (UL
508, CSA C22.2 No. 107.1) File E197259; cURus (UL 60950,
CSA C22.2 No. 60950) File E151273
● ATEX Yes; ATEX (EX) II 3G Ex nA nC IIC T4 Gc; cCSAus Class I, Div.
2, Group ABCD, T4
Standard / for explosion protection ATEX (EN 60079-0, -15); cCSAus (CSA E60079-0, -15; UL
60079-0, -15; UL 1604)
Certificate of suitability
● Shipbuilding approval No

EMC

6EP1961-2BA00 Subject to change without notice


Page 2/3 08/14/2020 © Copyright Siemens
Standard
● for emitted interference EN 55022 Class B
● for interference immunity EN 61000-6-2

environmental conditions
Ambient temperature
● during operation 0 ... 60 °C; with natural convection
● during transport -40 ... +85 °C
● during storage -40 ... +85 °C
Environmental category / acc. to IEC 60721 Climate class 3K3, 5 … 95% no condensation

Mechanics
Type of electrical connection screw-type terminals
● at input +24 V: 2 screw terminals for 0.5 ... 16 mm²; 0 V: 2 screw terminals
for 0.5 ... 4 mm²
● at output Output 1 ... 4: 1 screw terminal each for 0.22 ... 4 mm²
● for signaling contact 2 screw terminals for 0.22 ... 4 mm²
● for auxiliary contacts -
Width / of the enclosure 72 mm
Height / of the enclosure 90 mm
Depth / of the enclosure 90 mm
Installation width 72 mm
Mounting height 190 mm
Required spacing
● top 50 mm
● bottom 50 mm
● left 0 mm
● right 0 mm
Net weight 0.4 kg
Mounting type Snaps onto DIN rail EN 60715 35x7.5/15
Product component / belonging to 4x blade-type fuse 15 A
MTBF / at 40 °C 616 675 h
Other information Specifications at rated input voltage and ambient temperature +25
°C (unless otherwise specified)

6EP1961-2BA00 Subject to change without notice


Page 3/3 08/14/2020 © Copyright Siemens