Raspberry PLC Family Datasheet

Technical Features CONECTABLE PLC RASPBERRY PI 24Vcc x2 EXPANSION BOARDS SLOTS


MODEL TYPE Raspberry PLC Customize up to two additional communication expansions on your
Input Voltage 12 to 24Vdc (Fuse protection (2.5A) Polarity protection) Raspberry PLC and prepare your custom-made project:
Input rated voltage 24Vdc GPRS:
Rated Power 30 W Model: SARA-R412M-02B-03
I max. 1.5A Type: 2G EGPRS, GSM/LTE, M1/NB1 (Narrow-Band)
Key Features: : LTE FDD Bands
Size Check the Measures Table
(2/3/4/5/8/12/13/20/26/28), 2G Bands (850-1900MHz),
SRAM 2/4/8 GB LTE Category M1/NB1, 2G GMSK, 2G 8-PSK, LTE Category M1,
Communications I2C, Ethernet (x2), USB (x4), RS485 (x2 HALF-Duplex), SPI , Wi-Fi, LTE Category NB1, GPRS Multi-slot class 33, EGPRS multi-slot
Bluetooth, Serial TTL,, µSD, RTC, µHDMI (x2)
class 33
Applications: Remote monitoring automation, asset tracking,
surveillance and security, home automation systems, point of
sales terminals etc.
CAN:
General Features Model: MCP2515
Type: CAN V2.0B
Power supply voltage DC power supply 12 to 24Vdc Key Features: Speed of 1Mb/s, receive buffers, masks and
Operating voltage range DC power supply 11.4 to 25.4Vdc filters, data byte filtering on the first two data bytes, three
transmit buffers with prioritization and abort features, high speed
Power consumption DC power supply 30 W MIN. . SPI interface (10MHz), etc.
External power supply Power supply voltage 24Vdc Applications: communication with all kinds of CAN devices and
the protocols that can be applied to this communication method
Insulation resistance 20mΩ min.at 500Vdc between the AC
terminals and the protective earth terminal.
Dielectric strength 2.300 VAC at 50/60 Hz for one minute with a
leakage current of 10mA max.
Between all the external AC terminals and the
protective ground terminal.

Shock resistance 80m/s2 in the X, Y and Z direction


2 times each.

Ambient temperature (operating) 0º to 50ºC with Raspberry OS Lite

Ambient humidity (operating) 10% to 90% (no condensation)

Ambient environment (operating) With no corrosive gas

Ambient temperature (storage) -20º to 60ºC

Power supply holding time 2ms min.

Weight Review at the Measures Table

GPIO(x1)
Digital GPIO8 (3.3V )

Expandability
I2C - 127 elements
(x2) RS485 - 32 elements using Modbus RTU

Left side Upper side 2 Right Side


I/Os Table Notes
1. There are XXX on the reference number show:
1 2 - First two characters are related to the
expansion modules connected to the PLC unit
and the RAM Memory model.
- The third character is related to the CPU RAM
memory space:
See the Reference Table. Example:
xxxxx2xxxxxx - 2GB RAM Memory
xxxxx3xxxxxx - 4GB RAM Memory
xxxxx4xxxxxx - 8GB RAM Memory

2. The analog inputs has a 3% of tolerance.

Reference Table I/Os Ranges


Analogic I/Os voltage: 0 - 10 Vdc
Digital I/Os voltage: 5 - 24 Vdc (300 mA)
Relay's voltage:
30 Vdc (3A) / 250 Vac (5 A)

Main changes compared


to previous versions

Customize up to two additional


communication expansions on your
Raspberry PLC and prepare your custom-
made project

Communication pins upgrade! Now located


next to USB Ports instead of microSD layer

CAN Bus is not available by default. Select it


as expansion board if required.

No FAN is required at RPI PLC V4 family


products! Heater passive elements installed
by default.

Zones Table for Raspberry PLC V4 Family products


Performance Specifications
Raspberry Board Raspberry Pi 4 B
I/O control method Combination of the cyclic scan and immediate refresh processing methods.
Programming language Linux applications: Bash Scripts, Python, C++, Node-Red and more!.
CPU Broadcom BCM2711, Quad core Cortex-A72 (ARM v8) 64-bit SoC @ 1.5GHz
Website https://www.raspberrypi.org/

Raspberry PLC Access Warnings


How to access to the Raspberry PLC: Unused pins should not be connected. Ignoring the directive may damage the
controller.
-Linux users: using ssh specifying the IP address: 10.10.10.20/24 Before using this product, it is the responsibility of the user to read the
(eth0) and 10.10.11.20/24 (eth1). product’s User Guide and all accompanying documentation.
Industrial Shields PLCs must be powered between 12Vdc and 24Vdc. If a
-Windows users: we recommend to use PuTTY ssh client. The IP higher voltage is supplied to the equipment can suffer irreversible damage.
address have to be specified: 10.10.10.20/24 (eth0) and
10.10.11.20/24 (eth1). Maintenance must be performed by qualified personnel familiarized with the
construction, operation, and hazards involved with the control.
You can download the latest release of PuTTY here:
https://www.chiark.greenend.org.uk/~sgtatham/putty/latest.html Maintenance should be performed with the control out of operation and
disconnected from all sources of power.
UPS Shield The Industrial Shields Family PLCs are Open Type Controllers. It is required
that you install the Raspberry PLC in a housing, cabinet, or electric control
This PLC has integrated an UPS Shield, a device which provides an room. Entry to the housing, cabinet, or electric control room should be limited
anti-voltage drop protection system designed to avoid data to authorized personnel.
corruption when the current is suddenly cut off.
Inside the housting, cabinet or electric control room, the Industrial Shields
PLC must be at a minimum distance from the rest of the components of a
RTC minimum of 25 cm, it can be severely damaged.
This PLC has integrated the DS3231 Real Time Clock model which is Failure to follow these installation requirements could result in severe
powered by a button battery (CR1216 or CR1220). personal injury and/or property damage. Always follow these requirements
when installing Raspberry family PLCs.

Heater In case of installation or maintenance of the PLC please follow the


This PLC family products include an external heater to refrigerate the instructions marked in the Installation and Maintenance section on the User
Guide.
CPU and the other components connected internally.
Do not disconnect equipment when a flammable or combustible atmosphere
Eth1 is present.
This Ethernet port is configured at 10BT Half-Duplex auto-negotiation Disconnection of equipment when a flammable or combustible atmosphere
disabled. is present may cause a fire or explosion which could result in death, serious
injury and/or property damage.
Outputs
After a reboot/power disconnection and reconnection, the UPS will Inside the encapsulated, there are supercapacitors if 25F which can be
dangerous. Be careful with them.
be activated and, until the device is fully initialized again (it will take
some seconds), the outputs will maintain their last activation state.
For more information about that consult the User Guide.

Symbology Technical Support


Indicates that the equipment is suitable for direct current only; to You can contact with us using the best channel for you:
identify relevant terminals
Indicates that the equipment is suitable for alternating current
@ [email protected]
only; to identify relevant terminals
www.industrialshields.com
To identify the control by which a pulse is started.
Visit our Blog, Forum or Ticketing system
To identify an earth (ground) terminal in cases where neither the
symbol 5018 nor 5019 is explicily required.

To identify the switch by means of which the signal lamp(s) is 34 644 927 900
(are) switched on or off.
DataSheet Rev. 20230524

CE marking indicates that a product complies with applicable Use our chat service
European Union regulations
Indicates a potentially hazardous situation which, Check the user guides
if not avoided, could result in death or serious injury