1 PRODUCTION
A LANTAI 1
- LOADING DOCK 178 10.0 1,780 0.8 1,424 100% 1,424
- PRODUCTION AREA 988 50.0 49,400 0.8 39,520 100% 39,520
B LANTAI 2
- PRODUCTION AREA 442 50.0 22,100 0.8 17,680 100% 17,680
C LANTAI 3
- DRY ROOM 149 50.0 7,450 0.8 5,960 100% 5,960
- PERALATAN DRY ROOM 1 24,000 24,000 0.8 19,200 100% 19,200
- PERALATAN DRY ROOM (FUTURE) 1 24,000 24,000 0.8 19,200 100% 19,200
- HOIST MOVING AREA 300 50.0 15,000 0.8 12,000 100% 12,000
D PERALATAN/MESIN
- Discharge Pump 4 6,875 27,500 0.8 22,000 100% 22,000
- LST Agitator 2 27,500 55,000 0.8 44,000 100% 44,000
- LST Agitator (FUTURE) 1 27,500 27,500 0.8 22,000 100% 22,000
- LST Pump 2 9,375 18,750 0.8 15,000 100% 15,000
- LST Pump (FUTURE) 1 9,375 9,375 0.8 7,500 100% 7,500
- FT Agitator 2 27,500 55,000 0.8 44,000 100% 44,000
- FT Agitator (FUTURE) 1 27,500 27,500 0.8 22,000 100% 22,000
- Formulation Pump 2 9,375 18,750 0.8 15,000 100% 15,000
- Formulation Pump (FUTURE) 2 9,375 18,750 0.8 15,000 100% 15,000
- Activated Carbon Tower 1 18,750 18,750 0.8 15,000 100% 15,000
- CIP Pump 1 13,750 13,750 0.8 11,000 100% 11,000
- Product loading Pump 4 9,375 37,500 0.8 30,000 100% 30,000
- Product loading Pump (FUTURE) 4 9,375 37,500 0.8 30,000 100% 30,000
- Electric Insulation 1 12,500 12,500 0.8 10,000 100% 10,000
- Electric Insulation (FUTURE) 1 12,500 12,500 0.8 10,000 100% 10,000
- Process Control Panel 1 6,250 6,250 0.8 5,000 100% 5,000
- Process Control Panel (FUTURE) 1 6,250 6,250 0.8 5,000 100% 5,000
- Field Instruments 100 63 6,250 0.8 5,000 100% 5,000
- Field Instruments (FUTURE) 20 63 1,250 0.8 1,000 100% 1,000
- Electric Heat Insulation 1 6,250 6,250 0.8 5,000 100% 5,000
B LANTAI 2
- TF OFFICE 50 100.0 5,000 0.8 4,000 100% 4,000
- MEETING ROOM 3 29 100.0 2,900 0.8 2,320 100% 2,320
- WAR ROOM 58 100.0 5,800 0.8 4,640 100% 4,640
- MAIN OFFICE 2 154 100.0 15,400 0.8 12,320 100% 12,320
- PANTRY 13 60.0 780 0.8 624 100% 624
- OFFICE ROOM 3 21 100.0 2,100 0.8 1,680 100% 1,680
- OFFICE ROOM 4 19 100.0 1,900 0.8 1,520 100% 1,520
- STORAGE/ARCHIVE ROOM 18 60.0 1,080 0.8 864 100% 864
- SERVER ROOM 16 100.0 1,600 0.8 1,280 100% 1,280
- MULTI ROOM 59 100.0 5,900 0.8 4,720 100% 4,720
4 GUARD HOUSE
- GUIDE HOUSE 31 100.0 3,100 0.8 2,480 100% 2,480
- TOILET 5 30.0 150 0.8 120 100% 120
- MEETING ROOM 8 100.0 800 0.8 640 100% 640
REKAPITULASI :
- Daya Tersambung = 6,430 kVA
- Daya Kebutuhan = 4,588 kVA
- Daya Emergency = 5,006 kVA
- Kapasitas Transformator = 2x3200 kVA
- Kapasitas Generator Set = 2x3000 kVA
- Sambungan PLN (TM) = 4,670 kVA, TM 20 Kv