Plumbing Theory
Plumbing Theory
Plumbing Theory
1
3
8
4
WATER CONDITIONERS
A water conditioner is not a water softener but a device that
reconditions the small dissolved particles of limestone,
referred to as calcium salts, held in suspension in the water
so that they do not readily stick together to form noticeable
limescale. If you viewed untreated hard water under a
microscope, the calcium salts would appear star-shaped,
with jagged edges. It is in this form that they stick together.
The water conditioner aims to take off these jagged edges so
that they cannot easily bind together, and instead they
simply flow through the system (Figure 1.11). There are
two basic types of water conditioner. First there are
chemical water conditioners, which use crystals that
dissolve in water and bind to the star-shaped salts, sticking
in the crevices and jagged edges and having the effect of
rounding off the sharp points. The other type of water
conditioner passes a small electric current of a few
milliamps across the flow of water. This current alters the
shape of the calcium salts, changing them to a smoother and
more rounded shape. This current is often produced by a
magnet, although other methods can be used.
Gravity causes the water to flow from the trap along pipes
that run down to adjoin the vertical discharge stack, referred
to as the soil and vent pipe, and from here all the various
waste pipes converge to take the fluid to the drainage
system below ground. Obviously, the pipe must always be
laid to fall in the direction of the water flow and the pipe
must never, under any circumstances, be run uphill as water
simply will not drain from the pipe.
depth of
water seal
‘p’ trap
basin
32 mm
bidet
32 mm
bath
40 mm
objectionable
smells
soil stack
hopper head
waste stack
trapped gully
inspection chamber
Figure 1.14 The older system of separate waste stack and soil
stack
hydraulic
jump
negative self-siphonage
pressure (–)
plug of water
induced siphonage
(–)
the valve
self-sealing resealing
waste valve bottle trap
Figure 1.16 Alternative trap designs
ACCESS POINTS
All good drainage systems should have a means of access
for internal inspection of the pipe, which is particularly
useful when there is a blockage. Sometimes a large access
point is positioned to the end of a small vertical section of
100 mm diameter discharge pipe, used as an alternative to
the air admittance valve for an additional ground-floor toilet
within the property. This method is acceptable provided that
the pipe lengths are not excessive and, in all cases, no
further than 6 m from a ventilated drain, otherwise
additional pressure fluctuation problems will be created
within this section of pipe (Figure 1.18).
As with the air admittance valve, this access point must be
installed above the spill-over level of the appliance. If it is
not and there is a blockage to deal with, when it is opened
the foul water will discharge all over the floor.
100 mm
discharge
stack
6.0 m maximum
to ventilated
drain
unswitched fused
electrical supply
22 mm
discharge
pipe
any vertical
rise must
precede a
horizontal run
drain valve
drain valve
300 mm macerator
maximum
waste connection
from bath or basin
cistern
siphon
pressure-
flush pipe reducing
fitting
SURFACE WATER
In addition to the water that flows into the drains from the
various sanitary appliances in the home, water is also
collected
100 m vent
inlet
from the gutters, rainwater pipes and large paved areas; this
is generally referred to as surface water. If the drain is
serviced by a septic tank or cesspool, it will require an
additional, separately run drain for the purpose of collecting
the surface water because, if this water is allowed to flow
into these holding tanks, it will cause them to fill too
rapidly. In these cases, the surface water might be collected
and run into a drainage ditch, river or soakaway.
The soakaway is simply a large hole filled with rubble, into
which the drainpipe runs. The water collects here and
gradually drains into the surrounding ground (Figure 1.23).
CONNECTIONS TO PUBLIC DRAINAGE SYSTEMS
If the foul-water drain is connected to a public sewer, the
surface water may be collected within the same pipe and
they run off from the property together. This is referred to
as a combined system of drainage. Whether a combined
system of drainage is used will depend very much upon the
local authority that treats all the water. As a consequence,
some areas have separate systems of drainage, in which the
surface water is run into its own specific pipe.
large broken impervious membrane
hardcore to prevent soil dropping or clinker
from above
surface-
water drain
water draining
into ground
FWG
RWP
a) combined system
inspection chambers
FWG
RWP
RWP
to public
drain,
drainage
ditch or
soakaway
b) separate system
Figure 1.24 Connections to public drainage systems
ground level
Instantaneous Storage
3
4
Hot water storage systems
Domestic hot water is stored in an enclosed vessel, which is
most likely to be a cylinder, suitably insulated to keep the
heated water warm. This vessel is found typically in an
airing cupboard. The water is heated either directly or
indirectly.
The installation of modern domestic hot water systems is
controlled by legislation, which is particularly rigorous
with regard to energy efficiency. If you want a new gas or
oil boiler to use with a hot water cylinder, you cannot just
install any old appliance. It must conform to the standards
laid down in the Building Regulations, which are
administered by the local authority. Consequently, when a
boiler or cylinder is replaced, the local authority may wish
to be notified in order to ensure that it complies with
current standards.
Storage cylinders have developed and become more
efficient over the years. Older cylinders:
CC required a cylinder jacket to be tied around them in order
to keep as much heat as possible from being lost to the
surrounding space. They were usually installed in a
cupboard, which stayed warm and dry and thus provided
an ideal storage area for airing clothes. However, in this
modern age of energy efficiency, they have been
identified as using fuel inefficiently
CC had 1½–2 turns in the internal pipe coil that made up the
heat exchanger. This led to a very slow heat transference
rate and increased the time taken to heat the water in the
cylinder as it passed from the primary heating circuit.
Modern cylinders:
CC are foam-lagged at the manufacturing stage
CC have at least 5–6 turns in the heat exchanger, increasing
heat transference times.
It is also possible to purchase high-performance cylinders
that have a bank of many coils passing through the
cylinder, allowing for even faster heat-up times (Figure
2.5).
If you have an old style of boiler, it may be worth
considering replacing it with a new one next time it needs
any repair or maintenance work. This will reduce the time it
takes to warm up the water and will in turn save money and
provide better fuel efficiency.
a b
Figure 2.5 (a) A normal cylinder heat exchanger coil; (b) a high-
performance cylinder heat exchanger coil
WATER TEMPERATURE
The temperature of the hot water is set by the installer and
should be adjusted to meet the needs of the end user. The
temperature within a stored hot water cylinder should be
adjusted to no higher than 60°C at the top of the cylinder. If
it is set higher than this, the water may scald the user and
limescale deposits may also form in hard-water areas.
Equally, the water should not be stored at a temperature
much below this as the growth of Legionella bacteria may
occur.
PREVENTING LEGIONELLA
Legionella – the bacterium that causes legionnaires’
disease – is rarely a problem in domestic homes. The
bacteria are killed off above 60°C and will not survive
long at this temperature. However, they can survive within
the temperature range of 20–45°C. Legionella can be
dangerous to humans and is transmitted when water is in a
misty or vapour form, so areas around boosted shower
outlet sprays could be vulnerable if the water is maintained
at too low a temperature. The best alternative, where
cooler water temperatures are required, is to store the
water at 60°C and then use a blending/mixing valve, which
mixes the hot water with a quantity of cold water to reduce
the temperature to the desired level.
20 amp
heatproof
flex
wash
bath basin
drain-off
cock immersion
heater
element
boiler
sink
drain-off cock
drain-off cock
top view
drain-off cock
Key idea
The immersion heater is generally found in a hot water cylinder as a
backup to the boiler – as a means of heating water to be drawn off at
the taps.
GRAVITY CIRCULATION
The hot water from the boiler (see Figure 2.8) is transferred
to the cylinder by natural gravity circulation. That is, hot
water rises up the primary flow and is displaced by the
column of descending cooler water within the primary
return. This system is found in a large number of older
properties, but it is slow: the water in the cylinder can take
up to two hours to heat up. Modern systems use a
circulating pump to push this water around the circuit
rapidly, allowing heat-up times of around 30 minutes or
sometimes even less (see Chapter 3 for examples of fully
pumped central heating systems).
VENTED SYSTEMS
In a vented system the f & e cistern ensures that the water in
the boiler and heating system, where applicable, does not
mix with the water used for the domestic hot water. There
are two specific reasons for this separation, which are:
CC to combat the problem of limescale build-up
CC to reduce the amount of atmospheric corrosion.
In domestic hot water pipework, water is constantly passing
through the system and this constant flow of oxygenated
water contains a quantity of dissolved limescale. However,
Figure 2.8 shows that the water entering the boiler and
heating system via the f & e cistern – which is heated to far
above 60°C – is never emptied unless it is drained out for
maintenance purposes. Limescale build-up is eliminated
because, once the water has been heated, no more limescale
will be generated.
Also, after a short period of heating the water and moving it
around the system with a circulating pump, all the air will
have been expelled from the system. It is this air, in
particular the oxygen in it, that causes the corrosion of iron,
from which the boiler and radiators are invariably made, so
losing this air prevents them from rusting. (Corrosion is
looked at in more depth in Chapter 6.)
stop
valve
‘primatic’ cylinder
stop
valve
pipework
to central
heating
sink
boiler
primary
return
drain-off cock
Figure 2.9 A single-feed system of indirect hot water supply
UNVENTED SYSTEMS
Many homes built today incorporate an unvented system of
hot water supply. It has the advantage of:
CC having a stored supply of potable hot water
CC maintaining a good flow rate to the various outlet points
CC being at water supply mains pressure
CC freeing up roof space, which aids the design of modern
roof structures.
This type of system has only been permitted since 1985 and,
as a result, is generally only found in newer developments
or houses that have been refurbished. It is essential to note
that the minimum size of the supply pipe to these systems is
22 mm – if it is any smaller, you will not get the flow rate
expected compared to that of a vented system with its larger
pipe sizes. New homes are constructed with this larger
mains supply pipe, thereby generally posing no problems;
existing properties, however, may only have a 15 mm inlet
cold water mains supply, which will be inadequate to serve
all the hot and cold outlets within the property.
The installation of these systems falls within the
requirements of the Building Regulations, as administered
by the local authority, so the installation and maintenance of
the systems must be undertaken only by approved
operatives. This means that the installer will have taken and
passed an assessment course aimed specifically at the
design and safety of these systems.
Looking at the two systems shown in Figure 2.10, you will
see that there are several controls in addition to those found
on the more traditional systems (Figures 2.6 and 2.8). Two
systems have been illustrated because one design uses a
sealed expansion vessel to take up the expanding water,
whereas the other uses an air pocket, located inside the
cylinder with a floating baffle.
The following notes provide a brief outline of the controls
found on an unvented system, purely for interest and
identification but, as stated above, remember that these
systems must be installed and serviced only by qualified
personnel. Should you have such a system and require
work to be done on these controls, remember to ask the
operatives to show you an approval certificate or card,
otherwise your house insurance may not be valid should
something go wrong, as these systems can explode if not
looked after properly.
spring
spring
gauze
pressure containing
the expanding water
Instantaneous systems
of hot water supply
The storage systems discussed above work well, and a good
flow rate of water from the taps can be expected from a
correctly sized system. However, in the case of unvented
systems for homes with many occupants or older properties
with a small inlet supply pipe – which might be just 15 mm
in diameter – an instantaneous system may be the only
choice where a connection to the cold mains supply pipe is
made. This has very much been the traditional system of
domestic hot water supply.
Older properties without heating systems often have an
instantaneous system of hot water supply. They may have a
centrally installed multipoint water heater or several
singlepoint water heaters found at the appliances where the
water is required (see Figure 2.14). These heaters may be
electrically operated or gas fuelled.
Many homes have upgraded from the multipoint system by
installing a combination boiler (often called a combi boiler
for short) to supply hot water and central heating. These
units heat water as it is required, rather than storing it at
high temperatures, and also provide hot water for heating
purposes.
The biggest drawback with the instantaneous water heater is
the fact that the water can be heated at only a limited rate
and, as a result, the flow rate from the outlet tap is
invariably slower than that expected from a storage system.
The layout of the pipework to the various appliances is,
however, the same (see Figure 2.15).
water heater
cold tap
cold
supply
Figure 2.14 Localized single-point instantaneous hot water
heater at the point of use
wash
bath basin
combination boiler
or multipoint
sink
additional central
heating flow and
return if a
combination
boiler is used
drain-off cock
cold mains supply
these
systems
dry systems wet systems may be
vented or
unvented
(sealed)
Radiant heating
Radiant heating uses infrared heat rays that do not warm up
the air through which they pass but the structure upon
which they fall. In other words, radiant heating does not
directly increase the temperature of the air in a room;
instead, it warms up the structure of the building.
When a person enters a room, their body tries to become the
same temperature as the surrounding structure and, as a
consequence, if the building is cooler than you are, your
body loses infrared heat as it tries to even out the
temperature difference. If, however, the structure of the
building is warm, no heat will be lost from your body in this
way. As a consequence, the ambient temperature of the
room can in fact be cooler than your body and the building
as the air temperature does not unduly affect your body
temperature.
The advantages of having a radiant heating system include:
CC cooler room temperatures, which create a sense of
freshness
CC less transference of dust and airborne bacteria caused by
the effects of convection currents
CC very low water temperatures resulting in greater
efficiency from the boiler – typically around 90 per cent
(efficiency is explained later in this chapter).
connection
to system
+ –
+ – + + – + + – + –
N N N
+ + + + – –
pump
motorized
valves boiler
c.h. flow and return
fully pumped system using an air separator
vent
co
ld feed
three tapping air separator
(the cold feed is introduced within 150 mm of vent)
Figure 3.8 Using an air separator
Micro-bore systems
Micro-bore is the name given to a central heating design
that uses very narrow water pipes. At first sight, the pipe
layout may look rather different from the two-pipe system
but, in fact, it still follows the same basic design
principles. The illustration of the micro-bore system in
Figure 3.9 shows that a flow-andreturn connection has
been run from the boiler to each radiator. The main
difference between micro-bore systems and the usual
systems using 22 mm and 15 mm pipework is that, instead
of using tee joints at the connection to each radiator, a
manifold is employed, from which several branch
connections are made. (Figure 3.9 shows another variation
on the theme of central heating design: the micro-bore
system has been run from a combination boiler.)
cast-iron
column radiator
Radiator valves
A control valve will be fitted to each end of your radiator.
CC One is designed to open and close the radiator as
required.
CC The other, called a lockshield valve, is non-adjustable
and will have a plastic dome-shaped cap.
These are shown in Figure 3.11. The first valve, used to
open and close the radiator, may be a simple plastic-
headed on/ off control valve or a thermostatic radiator
valve (TRV). For many years the heating system installer
would choose whether or not to use a manual valve or a
TRV, but current Building Regulations dictate the use of
TRVs. The only radiators that can be fitted with a manual
valve are those connected to radiators in rooms with a
room thermostat.
The TRV automatically closes off the water supply to the
radiator when the room has reached the desired
temperature and therefore saves on fuel by avoiding
continuously supplying heat to a sufficiently heated room.
The purpose of the lockshield valve at the other end of the
radiator is to control the amount of water flowing through
the radiator. It is identical to the manual on/off valve at the
other end, except that the plastic head does not have an
internal square socket to fit over the turning spindle of the
valve. The installer would have pre-adjusted this valve
with a spanner when balancing the system at the time of
installation.
temperature-
bellows
thermostatic
chamber radiator valve (TRV) manual radiator valve
packing
pressure
pin
valve
cap to
seal off
valve
washer
inlet
The boiler
What about the heat source for the system? In its most
fundamental form, this is simply a metal box that is
surrounded by a fire. In fact, the first heating systems were
just this, a metal box referred to as a back boiler, found
within the fireplace of the lounge. Surprisingly, there are a
few still out there in some older properties.
.
Boilers today are fully automatic devices that turn up the
heat as necessary and, with the exception of solid fuel
systems, completely turn off when not required. The water
is just heated until the required temperature is achieved, as
set by its built-in thermostat, and then the heat source
turns off. The fuels that could be used for the boiler
include:
CC solid fuel, including coal, wood and straw
CC electricity
CC gas
CC oil.
Electric boilers are quite rare and so they fall beyond the
scope of this book. The remaining fuel types, however,
have been used in boilers for many years, and the design
of the boiler has developed into a very efficient appliance,
unlike those of yesteryear.
Solid fuel has limitations in its design, and because these
boilers tend to be more labour-intensive – i.e. you need to
load the fuel and empty the ash – they are not very popular
and account for around only 0.5 per cent of all
installations. Around 92 per cent of installations use gas
and the rest use oil.
Due to developments over the years, there are many
different boiler designs from many different
manufacturers, with a neverending list of models
applicable to the particular designs. But fundamentally
they all fall into one of four basic types:
CC natural draught open-flued
CC forced draught open-flued (fan-assisted)
CC natural draught room-sealed
CC forced draught room-sealed (fan-assisted).
from room
open-flued appliance
than
54°C)
Figure 3.15 Internal view of a condensing boiler
When talking of efficiencies, one is effectively talking
about the running cost. For example, for every £100 spent
on fuel, if your boiler is only 55 per cent efficient, you
will be getting only £55 worth of heat, and £45 would
simply be going up the chimney. But where your boiler is
90 per cent efficient, you will be getting £90 worth of heat
for every £100 spent.
It is because older boiler designs waste fuel in this way
that current regulations no longer permit them to be
installed. If you need a new boiler, the chances are, with a
few exceptions, that the heating installer will be bound by
law to install a boiler with an efficiency of 86 per cent or
higher.
Heating controls
In your home you may or may not have all of the controls
listed below; in fact, you may have no more than a switch
to turn the power on to the boiler and pump. However, the
design of a modern central heating system will use a
whole range of controls for increased efficiency. One
requirement of the current Building Regulations for all
new and replacement systems using gas or oil as the fuel
source is to have a minimum of the following controls:
1 A full programmer or an independent time switch for
heating and hot water
2 A room thermostat, providing boiler interlock
THE PROGRAMMER
This is, in effect, a fancy clock. It allows the heating to
come on at specific times as set by the occupant of the
building. Modern installations require the use of what is
referred to as a full programmer. This basically means that
the heating circuit(s) and domestic hot water circuit can be
controlled independently, allowing separate time settings
for heating and hot water. Earlier designs of programmers
did not have this independence, for example:
CC mini-programmers allowed heating and hot water to be
on together, or hot water only (but not heating only)
CC standard programmers allowed heating and hot water to
be on on their own, but used the same time settings.
These older time controllers will need to be replaced if the
boiler is replaced, to comply with the current Building
Regulations.
BOILER INTERLOCK
Boiler interlock is when the boiler is linked with the
thermostat system so that the boiler will only ignite if heat
is required by either the domestic hot water or the central
heating system, as regulated by the cylinder and room
thermostats respectively.
Older systems did not always have a room or cylinder
thermostat. For example, central heating systems were
often designed only with TRVs fitted to the radiators, and
gravity circulation of hot water to the cylinder from the
boiler was allowed to continue until the boiler thermostat
was satisfied.
Sometimes, to prevent the domestic hot water becoming
too hot, a mechanical thermostat was installed in the
return pipe to close off the flow of water in the circuit, and
the boiler thermostat was the only control for switching
the boiler on or off. Invariably it continued to heat up and
cool down, night and day, as the boiler slowly lost its heat
to the surrounding atmosphere. This is referred to as ‘short
cycling’ and is clearly a drastic waste of heat and fuel, and
this is what boiler interlock prevents.
Systems without boiler interlock need to be upgraded
when major work is undertaken on the system, such as
when replacing the boiler. Where you only intend to
replace the hot water cylinder, you must include a
cylinder thermostat to operate a motorized valve to close
off the circuit and switch off the boiler, but you do not
need to upgrade the central heating controls. However, if
you replace the boiler, both the cylinder thermostat and
the room thermostat must be provided, thereby providing
total boiler interlock.
MOTORIZED VALVES
Older central heating systems will not have these controls
because, prior to the 1980s, systems generally were
installed as shown in Figure 3.3. These older systems
either had TRVs fitted to all but one radiator on the
system to control the room temperature, or a room
thermostat was used to control the heating requirements,
which switched off the pump when the temperature within
the room where the thermostat was located reached the
required level. The temperature of the domestic hot water
was generally only regulated by the boiler thermostat.
These earlier systems, of which many thousands are still
in existence, are far less efficient than the modern well-
designed systems that use a motorized valve to close off
the water supply to a particular circuit.
Closing off the motorized valve by way of the electrical
power supply, from the room or cylinder thermostat as
appropriate, provides a situation where the boiler is
prevented from firing unnecessarily. The boiler of the
modern system cannot fire unless either the room or
cylinder thermostat is calling for heat, because it is these
controls that send the power supply to feed a motorized
valve.
FROST PROTECTION
Sometimes, if pipework or the boiler is located in an
unheated part of the building, such as a garage or the roof
space, or where a separate outbuilding has been used for
the boiler, it will be necessary to provide some form of
protection against frost damage, including:
CC filling the system with special central heating antifreeze
CC using a special frost thermostat and pipe thermostat,
positioned at the predicted coldest points, in order to
bring on the boiler with the intention of heating the
water within, thereby maintaining it at a temperature
just above the freezing point of water (0°C).
The two thermostats listed, the frost and pipe thermostats,
are used in conjunction with each other:
CC The frost thermostat is designed to make its electrical
contact when the outside air temperature drops.
CC The pipe thermostat allows electricity to flow through
its contact only where the water temperature inside the
pipe, on which it is positioned, drops to around 5°C.
Thus, when it is very cold outside, the frost thermostat
makes its electrical contacts, which allows the electricity
to flow to the pipe thermostat. If the water inside the pipe
is sufficiently warm, the electricity will not flow beyond
this point but, if the water inside the system is dangerously
cold, it will allow the electricity to pass to the boiler and
pump. Once the pipe thermostat is satisfied, with
sufficient heat detected within the pipe, it breaks the
electrical circuit.
CORROSION INHIBITORS
Corrosion inhibitors can be added to a central heating
system in order to prolong its estimated lifespan. Several
trade brands can be purchased from any plumbers’
merchant. The corrosion inhibitor serves several functions,
including:
CC lining the pipework in order to minimize the problems
of corrosion
CC lubricating the pump
CC reducing the build-up of bacteria within the system.
The only problem is the fact that, to have any real effect, it
must be added to the system within a short time of
installing the system.
Turning off the water supply
To turn off the internal cold water supply stopcock, take
the following steps:
1 Find the valve (see Chapter 1, Figure 1.2).
4 Open the kitchen sink tap to check that the water has
stopped flowing.
It is advisable to check that this valve works before an
emergency arises. Simply try closing the valve as you
would any other tap in the home. This will involve turning
the operating handle or head in a clockwise direction. It is
a good sign if the valve operates freely. Continue turning
clockwise, counting the number of turns, until you feel the
valve is fully closed. Then check that it has worked
correctly by going to the cold sink tap in the kitchen and
turning it on to see if the water stops flowing.
We should always choose the kitchen tap because it is sure
to be on mains supply, unlike other downstairs cold taps
that may be fed via a cold water storage cistern in the roof
space. When you try this tap, be prepared for the water to
continue flowing for a short period before stopping
completely because water may be draining out from the
cold supply pipe within the house. Once the supply stops
completely, there shouldn’t be any problems. However, if
the sink tap continues to drip, you may need to apply a
little more turning force to the supply stopcock to force
the washer inside this valve tighter on to the seating.
To re-establish the water supply, you simply open the
stopcock, turning it anticlockwise the same number of
turns as you counted when closing the valve. Finally,
check to see that the
water is flowing freely from the sink tap outlet. It might
spurt out at first, due to the air pressure build-up caused by
the air in the pipe compressing when the water is turned
on; this is quite normal.
If all has gone well, you have completed your very first
plumbing job! Simple really, wasn’t it?
Remember this
It is essential to make sure that you know where to turn
off the water supply in an emergency. Remember, if you
turn off this valve, eventually all water in the pipes will
cease to flow, whatever the system. Make sure you know
the valve works before an emergency arises!
Key idea
To help you identify the purpose of a particular in-line
stopcock or valve anywhere in the home, it is a good idea
to tie a label to the valve indicating what water pipes will
be isolated when the valve is closed shut.
rising spindle
packing gland nut
packing
headgear
body
jumper
washer
stopcock
key
wheel head
seating
(b)
valve open
quarter-turn head
valve closed
Figure 4.3 (a) A gate valve and (b) a quarter-turn lever-
operated valve
If you find you have a gate valve, it may only halt the main
flow of water and still let a little water through – this type
of valve is not always very effective. Sometimes gate
valves fail altogether and, even when they do work, they
sometimes fail to re-open. Quarter-turn valves do not
usually cause problems and, if you have one, you simply
turn it one-quarter of a turn until the handle is
perpendicular to the pipe. This type of valve should always
be installed if you are considering a new or replacement
valve. When choosing a new valve, make sure the type
you select maintains a full bore when you look through it
in the open position; if you choose a design with a reduced
bore, you will notice the lack of water flow after it has
been installed.
If you cannot locate the valve from the storage cistern or it
does not work effectively, it is possible to block the outlet
pipe from the cistern with a cork. Alternatively, turn off
the supply feeding the cistern and drain out the water via
the taps fed from it. The cistern can be turned off at its
inlet stopcock or screwdriveroperated quarter-turn valve. If
you cannot find a valve, you can lift the arm of the float-
operated valve, which will stop the water flowing into the
cistern. You can tie this up using a piece of string and a
batten resting across the top of the cistern.
If the storage cistern feeds the hot water supply as well as
the cold water, draining out the water from the cistern will
also stop the flow of water from the hot taps.
cold feed
tap opened
drain-off drain-off
cock cock
hose
connection
backnut
washer
body
washer
body of tap
tap head
removed
seating of tap
washer
automatic self-
closing device
(b) (c)
nut
automatic
selfclosing device
(d) (e)
ceramic discs
‘O’ ring
circlip
storage cistern
partial blockage
SIPHON TYPE
This type uses a lever arm to flush the toilet; this lever lifts
the large diaphragm washer inside the siphon tube (see
Chapter 1).
If the WC fails to flush, the first thing to do is simply to
lift the lid from the cistern and check the operation of the
linkage system used to lift up the diaphragm washer.
Assuming this is OK, the fault will almost certainly be a
split or worn-out diaphragm washer. This can easily be
replaced but, with close-coupled WC suites, you have to
remove the whole cistern from the wall in order to remove
the siphon. There is a siphon design built as two parts,
which allows you to pull the siphon apart to facilitate this
repair, but unfortunately these are not commonplace.
Toilet cisterns with flush pipes such as that shown in
Figure 1.20 do not need to be removed from the wall.
To replace the washer, take these steps:
1 Turn off the water supply to the WC cistern – there
may be a quarter-turn valve on the inlet supply pipe.
2 You now need to bail out the water from the cistern,
using a sponge if necessary to draw out every
remaining drop of water; otherwise what remains will
discharge on to the floor when the siphon is removed.
3 For cisterns with a flush pipe, unwind the large nut
securing it to the siphon, turning it anticlockwise.
4 Next, unwind the big nut securing the siphon to the
cistern.
5 You can now lift the siphon from the body of the
cistern. To complete this action you will need to
unhook the linkage to the lever arm and sometimes, if
the arm of the floatoperated valve gets in the way, you
may need to remove this as well.
6 With the siphon removed from the cistern you can now
see beneath the base of it and you’ll see the location of
the old perished diaphragm washer.
7 Remove the hook attached to the top of the shaft that
pulls the diaphragm; this then allows the diaphragm
housing to drop from the base of the siphon (see Figure
4.15).
8 With the old washer removed, a replacement can be
inserted. You can buy them, if you are lucky to find
one of the same size; however, I personally have
always used thick plastic polythene sheeting and cut
out my own, simply laying the old washer on the
plastic as a template. The type of plastic you require is
the type used as a damp-proof membrane or one of
those heavy-duty plastic builder’s bags. When you get
the old washer out, you will see the type of plastic I
mean.
9 With the new washer cut, replace everything in the
reverse order. All jointing washers should be in good
condition, but where they have perished simply wrap
some PTFE tape around the joining parts (not around
the threads) where the old jointing washer or material
was.
replace PVC
remove hook
from top of
siphon
diaphragm washer
VALVED TYPE
These flushing devices have only been installed since the
turn of the twenty-first century and therefore are relatively
new in the scheme of things (see Figure 1.8). When you
operate the push-button mechanism to flush the cistern, the
valve inside lifts up from its seating to allow the water to
discharge directly into the cistern outlet. If the unit fails to
flush, it is generally due to a broken component and, in
most cases, the whole internal flushing valve will have to
be replaced because spares for these devices are not
generally available.
If you are lucky, you may be able to purchase an identical
unit, making a replacement a relatively simple process.
Looking at the new component, you will notice that there
is a facility to turn and remove the valve from its base
plate. So, once you have done this and removed the
existing valve unit within the cistern, the damaged part can
be replaced without the need to remove the cistern.
Remember to turn off the water supply before carrying
out this task.
Water continuously discharges
into the pan
This problem might occur for one of the following
reasons:
cistern wall
union nut
replacement valve
inlet horn
flush pipe
WC pan
1
4
FINDING THE LEAK
Here are some indicators that will provide clues as to
which system is leaking:
CC Can you hear the float-operated valve running in the
loft storage cistern? If so, the leak is not on the mains
supply.
CC If you turn off the mains supply only, does the leak stop
immediately? If so, this indicates that it is fed directly
from the mains supply.
CC Is the water hot, suggesting that it is from the hot water
or central heating system? Where the leak is from the
hot water or central heating system, it is advisable also
to turn off the heat source.
Once you have stopped the water flow, you can begin to
control the situation. If the leak is in a section of pipework
that is hidden from view, such as above a ceiling, the first
thing to do is expose the pipework where the leak is most
apparent by lifting floorboards or removing any covering
panels. Now turn the water back on for a short while in
order to pinpoint the leak. Don’t be surprised if, when you
turn on the water, the leak is not from the area you
suspected. Water has an uncanny way of travelling long
distances undetected.
When you turn the water back on, consider again the clues
above, which may give some indication of which system is
leaking. If you hear cisterns filling in the loft, look to see
which cistern is filling. If it is the f & e cistern, you know
that the heating system is leaking. If it is the larger cold
storage cistern, it will be the low-pressure hot or cold
water that has the leak. Each of the cold water outlets from
the cistern can be closed off to pinpoint which pipe is
leaking.
1
4
A bit of detective work often needs to be done to locate the
source of a leak. You will need to call on your
understanding of the system designs described in Chapters
1 and 2. You may need to expose more pipework and
listen very carefully to the sound of the water hissing from
the pipe.
One of the most difficult leaks to locate is one beneath a
sandand-cement floor screed. The water seems to travel
everywhere through the channels preformed for the pipes,
making detection very difficult. It is invariably a case of
trial and error, exposing test holes in the floor to find the
wettest sections.
Eventually, however, the point of discharge will be found,
as will the supply isolation valve. The rest is now basic
plumbing, cutting out the affected section of pipe and
replacing it. For this work, see the notes in Chapter 6 about
jointing pipework.
1
4
CC noise generated by a pump
CC creaking floor timbers
CC splashing noises as water refills a cistern
CC noises from a boiler, like a kettle boiling
CC gurgling noises in the pipework
CC gurgling noises from an appliance waste trap.
This is not an exhaustive list, but it represents the more
common situations dealt with below.
1
4
waves formed on the surface of the water in the cistern.
The waves are formed as water flows into the cistern when
the float-operated valve opens to make up the water level
after some water has been drawn off.
If the plastic cistern has been installed without the metal
reinforcing piece that came with it, the cistern wall will
flex as the float rides over the ripples on the water. There
are several possible cures for this problem:
1 Secure the float-operated valve (ballvalve) by fully
supporting the cistern wall.
2 Replace the normal 100 mm diameter float with a larger
ball float.
3 If a larger float cannot be obtained, secure a damper
plate to the lever arm to create a larger surface area (see
Figure 5.1).
4 Fit a baffle within the cistern to prevent waves forming.
This is basically a dividing plate to reduce the total
surface area of the water.
5 Turn down the incoming supply stopcock to reduce the
water flow into the home.
float-operated valve
metal reinforcement
to plastic cisterns
damper plate
1
4
A SHUSHING NOISE AS WATER PASSES THROUGH THE
PIPEWORK This noise often occurs if the installer has
failed to take the small internal burr off the pipe when
using a copper tube cutter. It is also sometimes generated
where pipework has been run within a timber stud wall.
The plasterboard over the timber studwork acts as a
resonator, amplifying the sound of the water flowing
through the pipe. When pipes are run within timber stud
walls, they should ideally be insulated and the pipe clips
placed on rubber or felt mountings to stop this
transmission of noise.
.
NOISE GENERATED BY A PUMP
Where this problem occurs with a central heating system,
turning down the setting – if a variable speed pump has
been installed – will generally alleviate the problem.
However, this may create a different problem in large
heating systems in that the furthest radiators from the
pump may not get warm enough.
Where the pump noise comes from a shower booster
pump, it may be that the pump has not been fitted with
flexible connections and on to a flexible mounting, and
so this would need to be provided if necessary. Also
check that the pump is not touching anything that would
act as a sounding box and elevate the noise level.
1
4
When passing copper pipework through notches that have
been cut in the joist, ideally a felt pad or piece of carpet
underlay should be laid to dampen any movement noise
caused by the pipe expanding or contracting. The only
option is to lift the floorboards and investigate.
1
4
apparent reason, it is possible that a narrow pocket of air
has become trapped within the boiler, perhaps as a result
of limescale or corrosion. The noise is generated by the
formation of steam and its subsequent condensing within
this area of trapped air. The only remedy, apart from a new
boiler, is to treat the system with a descaling solution.
Where a power flush is sought, this may require the
services of a reputable heating engineer; however,
depending on the age of your system and the materials it is
made from,
e.g. aluminium, copper or steel, several manufacturers
produce chemical cleaning solutions, available from any
plumbers’ merchant. These come with the necessary
application instructions and can be administered to clean
out your system.
1
4
GURGLING NOISES FROM AN APPLIANCE WASTE
TRAP
These noises are the result of water being siphoned out
from the trap. See Chapter 1 for a discussion of this
problem.
1
4
NO HOT WATER OR CENTRAL HEATING
A lack of hot water or central heating could be due to one
of several possibilities. You may have hot water but no
heating, or vice versa. There may be a blockage within the
pipeline, such as limescale or sludge build-up, but this type
of problem is fairly uncommon. The most likely cause, and
the first thing to investigate, is an electrical control fault
preventing the power reaching the point where it is
required. The areas to investigate are:
CC a blown fuse or loss of power supply
CC the time clock/programmer wrongly set or faulty
CC a faulty thermostat (room, cylinder or immersion heater
thermostat as appropriate)
CC a faulty motorized valve
CC a fault with the boiler or pump.
Electrical faults generally require the assistance of an
expert. The engineer will go through the above list and, by
a process of elimination, find where the fault lies.
The power supply to the boiler and pump ultimately
follows a set route (see Figure 5.3), and in order to
determine the cause of a problem you will need to check
that power is going to the first component, then that it
leaves that component to move on to the next component,
and so on until it reaches the boiler and pump. Along the
way you will discover where the interruption in the
sequence occurs, so you can focus on the area causing the
fault. So, for example, if you find that 230 volts is going
into the cylinder thermostat yet there is no voltage coming
from it, this suggests that this component or the wiring to
or from it is at fault.
1
5
power fuse programmer cylinder motorized
supply thermostat valve
1
5
pump back into action. If the impeller fails to turn, it will
need to be replaced.
1
5
Setting the speed too high might create unacceptable
noises within the system.
pump
below
Figure 5.4 Replacing a central heating pump
1
5
individual treatment and flushing through with a high-
pressure hose.
CCBleeding a radiator
There may be just one or two radiators on your system
that are not getting warm. Assuming that the valves at
each end of the radiator are open, the first thing to check
is that they are not cold simply because they are full of
air. Air is expelled from the system radiators through a
small air-release valve located at the top and to one side
of the radiator, a process referred to as ‘bleeding’. Do this
as follows:
1 Turn down the room thermostat. This will turn off the
pump. (The reason for turning off the pump while
bleeding the radiator is to ensure that air is not sucked
into the system if the pump is creating a negative
pressure within.)
2 Use a special square-headed radiator key to open the
airrelease valve, turning it anticlockwise. You will hear
the air being forced out and eventually water will appear
at this point, whereupon you simply close the air-release
valve.
3 Turn the room thermostat back to the desired setting.
1
5
pump only generates so much pressure and will only push
the water so far, so a larger pump may be required. The
pump may have variable settings and it might be possible
to increase its speed and pressure by making a simple
adjustment on the side of the pump itself.
Another possibility is that some of the radiators closer to
the pump have their lockshield valves open to such an
extent that they are taking all the flow of water, in which
case they need to be closed a little in order to balance the
system (see Chapter 3). A simple test to see if balancing is
required is to close off the manual radiator valve operating
heads to several radiators that are working fine, to see if
the cold radiators then get hot; if so, you need to balance
the system better.
1
5
3 Now replace the packing gland nut, tightening it just
enough to squeeze the new packing material within the
gland.
4 Re-open the radiator valves and test it.
1
5
3 You must now block up the overflow pipe. To do this,
take a piece of rag and stuff it hard against the overflow
opening. You must make a good seal here in order to be
successful in the plunging operation.
4 All you need to do now is push the plunger up and
down over the waste pipe outlet several times.
Using a plunger will usually clear a blockage; however,
blockages to appliances such as sinks and basins are often
the result of soap and fatty deposits. Plunging will give
some relief to the problem but will not remove all the fatty
debris and may make only a small hole in the blockage,
which will soon block up again. In this instance the ideal
solution is to remove the trap from the appliance for
internal inspection.
1
5
block the overflow
with a piece of rag
appliance waste
waste pipe
1
5
2 Now position a bucket or suitable receptacle beneath the
appliance to catch any spillage and remaining water
from within the trap itself.
3 If a bottle trap has been fitted, you will just need to
remove the lower dome-shaped bottom, as shown in
Figure 5.5. Where a tubular trap has been installed, you
will need to remove this in its entirety, as follows:
i Undo the large nut that joins the trap to the appliance
waste outlet, turning it anticlockwise.
ii Now undo the nut that joins the trap to the pipe; this
will allow you to remove the trap.
4 Be prepared for a sickly sight of fat, hair and general
grime. However, once all this rubbish has been removed
(undoing the third large nut adjoining the two sections
of the trap if necessary), you will have a clean trap with
an effective internal bore.
5 Before replacing the components, just look into the
outlet pipe for any further signs of blockage. If there is
excessive blockage, it may be time to consider using a
series of long drainage springs to poke down the tube,
or you could remove the whole pipe section and replace
it, but this is not usually necessary.
During this process no water, apart from that held within
the sink and trap itself, will flow from the appliance. In
most instances the trap is fairly easy to access, but
sometimes it may be difficult to reach the nut adjoining the
waste outlet of a pedestal basin. It might be possible to
ease the pedestal forward a small amount to gain better
access, but take care as it is designed to give support to the
basin and is easily chipped, being made of porcelain.
When you reassemble the waste pipe, take extra care when
doing up the nuts as they are made of plastic and it is easy
1
5
to cross-thread a joint, preventing it from doing up tightly.
The seal that was in place before you undid it will
probably still be fine to reuse, but if necessary you can
wrap a few turns of PTFE tape to the mating surfaces near
the damaged sealing washer. Do not wrap PTFE tape
around the pipe threads themselves as the nut and thread
are just used to pull or clamp the two mating surfaces
together, crushing jointing material in place to form the
seal – they do not themselves form the watertight seal.
BLOCKED TOILET
When a toilet blocks, the natural instinct is to panic and to
wish the problem would go away as quickly as possible.
When you flush the toilet, the bowl fills with foul water,
which just sits there. It may slowly drain away but the
blockage still remains, and after the next flush the water
will back up and fill the bowl again.
Purchasing a simple drain rod and a 150 mm rubber
plunger to screw on to its head could easily save you
hundreds in plumbers’ call-out charges. If you call out a
plumber, they will probably fix the problem within 30
seconds of arriving, leaving you happy to pay whatever
they ask. But there is no magic – it is simply a matter of
them using their plunger to create the pressure needed to
dislodge the blockage.
So what do you do?
1 Obtain a drainage rod or chimney sweep’s rod with a
thread on one end. On to this, screw a 150 mm drain
plunger obtainable from a plumbers’ merchant.
2 Ensure that some water, however disgusting, is in the
WC bowl, or flush the appliance so that it fills and
backs up.
1
6
3 Push the rubber plunger back and forth down inside the
pan, back towards the trap, as shown in Figure 5.6.
With any luck this will cure the problem. I once cleared a
blockage using this technique but without a plunger. I used
an old-fashioned floor mop on to which I secured a plastic
bag; this made a suitably effective plunger. Plunging can
be very effective and so, if a toilet remains blocked after
plunging, this suggests a blockage further down the
pipeline. Air is simply getting in via the open vent pipe at
the top of the drain, relieving the partial vacuum you are
trying to create.
Blockages further along the drainpipe might also affect
other appliances, in effect putting several appliances, such
as sinks and baths, out of action.
150 mm rubber
plunger on a
drain rod
blockage
1
6
BLOCKED DRAINS
What a nightmare! Nobody likes blocked drains.
Everything in the household may be put out of action as
a result of this kind of blockage. The first course of
action is again to consider the plunger.
Let’s assume that you lift up the inspection/manhole
covers outside your home and find that they are filled with
sewage. Arm yourself with a set of drainage rods now, not
just the single one required to unblock a WC pan (rods can
be hired quite cheaply from most hire centres). Secure a
100 mm plunger on to the end and insert this into the next
dry manhole chamber down from the blockage, aiming
towards the one full of liquid. Insert the rod several metres
and then pull it from the pipe. Nine times out of ten, this
will create the suction required to dislodge the blockage. If
you cannot locate a dry inspection chamber, you will need
to try to pass your rods, with the plunger attached, through
the sewage towards the outlet to pass it into the pipe.
Again, once it is inserted, simply push and pull the plunger
to create an alternating pressure to dislodge the blockage.
1
6
no longer installed because they were often the cause of
blockages.
If one of these is blocked in an older property, it will need
to be plunged in the same way as a WC pan. However, if
the blockage is downstream of the trap, there is a stopper
that allows rodding access towards the sewer. The stopper
should be removed by lifting it from its seating, pulling it
up with the attached chain.
Key
One final point regarding blocked pipes is that, if you have
to remove bolted-on access covers, particularly those
inside the house in the above-ground part of the drainage
system, give some thought to what might be behind the
access door. These doors are designed to be watertight, so
prior to opening them you cannot tell what is behind them.
Since the pressure of the backed-up liquid contained
within could be quite considerable, spraying the contents
some distance from the opening, you will need to take
precautions to avoid getting covered in effluent.
1
6
Take care when working up a ladder. If you do not feel
confident doing so, it may be advisable to call on someone
else
1
6
person so that it will not slip, and never overreach when
working up a ladder. Never lean the ladder up against the
gutter itself as it may cause damage, especially where a
plastic gutter has been installed, but, more importantly,
your ladder can also easily slip to the side when it is
resting against such a smooth surface, making it very
dangerous.
Should the rainwater pipe itself become blocked with
debris, it poses a much more difficult problem. You can
try poking a drainage spring up or down the pipe, but
sometimes, especially if it is a plastic rainwater pipe, it is
quicker to disconnect the entire pipe section and do the
unblocking at ground level. Fortunately, it is usually just a
blockage at the bottom end of the pipe that is creating the
problem, causing the water to back up and come out of the
joints, which are not made watertight – and, incidentally,
were never intended to be watertight. A blockage at the
bottom of the pipe is often the result of a blocked gully,
which can simply be emptied physically by hand.!
1
6
Key idea
Just as you should know the location of your mains inlet
water supply stopcock, you should know the location of
the gas supply inlet. Make sure you can access it easily, in
case you need to turn off the supply in an emergency.
The telephone number of the national UK gas emergency
service is 0800 111 999. In the US, simply call 911.
In newer houses, the gas meter and emergency control
valve are often outside in a meter box. If you have a gas
meter box, make sure you know where the key is kept in
case of an emergency. You can close off the supply
completely by turning the handle attached to the control
valve just a one-quarter turn.
!
fresh air.
4 Call a doctor if necessary.
Focus points
1 Turning down the incoming cold water supply
stopcock will often cure a host of sloshing and
banging noises in pipework.
1
6
2 Creaking floor joists are often the result of
insufficient expansion allowance between the notch
in the timber and a hot water pipe passing through,
so, as the pipe expands due to heating up, it rubs
against the timber.
3 A noisy boiler is often caused by corrosion or scale
build-up within the heating circuit, leading to air
becoming trapped in the boiler.
4 Do not undertake electrical work, such as changing
the circulating pump on the central heating system,
unless you are competent with electrical installations
and know how to work safely in this field.
5 When radiators fail to get hot, the system could be
poorly balanced or blocked by sludge, which is
invariably the result of corrosion within the system.
6 Most blockages in wastewater pipework can be
rectified by the use of a plunger.
7 When using a plunger, you must block up the
overflow pipe, where one is fitted.
8 The trap beneath appliances such as sinks and basins
can simply be disconnected and drained into a
bucket. For this task the water does not need to be
turned off.
9 When unblocking drains, take suitable precautions to
avoid contamination by the foul and dangerous
bacteria found in these pipe systems.
10 If you smell gas or fumes within a building, act
immediately by turning off the appliance(s) and
ventilating the property by opening all doors and
windows. Do not operate any light switches, and call
either a gas engineer or the supplier for further
advice.
1
6
Corrosion
Corrosion is a chemical attack on metal, which brings
about its destruction. There are two forms of corrosion:
CC atmospheric
corrosion CC electrolytic
corrosion.
ATMOSPHERIC CORROSION
Everyone has seen atmospheric corrosion: leave a tin can
in the garden and very soon it will be rusty and full of
holes. It is the water and oxygen in the air that causes this
corrosion: their presence on the exposed surface of iron
causes oxidation. The resultant iron oxide is not stable and
falls away, exposing more fresh metal, and the process
continues until there is none of the iron left and only a
scattering of iron oxide (rust) on the ground.
Atmospheric corrosion attacks all metals in this way but
unless the metal is ferrous (i.e. contains iron) the corrosion
formed on the surface of the metal is stable and so
prevents any further corrosion. This process can be seen
on a copper roof that has turned green – the green is the
oxidized copper that has formed due to corrosion over a
period of time. Copper pipe is unaffected by atmospheric
corrosion and it can therefore be used for water supplies
without fear. If we used iron pipes for water services, they
would last only a very short time. You may find iron
pipework in your home, but the iron has been covered with
a coating of zinc, referred to as being galvanized, so the
metal is in fact protected to some degree against
atmospheric corrosion.
1
6
As discussed in Chapter 3, steel radiators are used in
central heating systems and last for many years without
rusting.
This may seem strange as they are totally filled with water,
but for corrosion to occur there also needs to be oxygen
present. There is a certain amount of oxygen within a
sample of water, but the radiators do not rust because the
water is never changed, except for repair work, and within
a week or so of filling the system all the oxygen in it will
have escaped back into the atmosphere. And with no
oxygen there is no rusting.
ELECTROLYTIC CORROSION
Galvanized mild steel – iron coated with zinc – is no
longer installed in the home, although it can still be found.
This pipework, although protected against atmospheric
corrosion, is subject to another form of corrosion brought
about by a process known as electrolysis. This is where
one metal attacks and destroys another metal lower down
the electromotive series. The electromotive series is a list
of metals with different abilities to resist destruction by
another metal – the metals lower down the list are less
able to resist than those higher up the list. Where there is a
mix of different metals within a system, the metal lowest
on the list is destroyed first, before electrolytic corrosion
begins on the metal next highest in the list. The
electromotive series of typical plumbing metals is:
CC copper
CC lead
CC tin
CC iron
CC zinc
1
6
CC aluminium.
Galvanized mild steel pipes are iron with a coating of zinc.
The zinc coating not only protects the iron against
atmospheric corrosion but also provides a sacrificial metal
to be destroyed before the iron when mixed with other
materials such as copper. If you look at the list above, you
will see that the copper would destroy the zinc before the
iron is attacked, as the zinc is lower down the list.
1
7
copper pipes (see below), except that they are much larger
and have a rubber compression ring instead of the brass
ring used for copper. These compression fittings (e.g.
Lead-loc) can be obtained from most plumbers’
merchants. The replacement of old lead mains should be
considered at the earliest possible opportunity, for which a
local government grant may be available.
1
7
use a jointing paste instead of PTFE tape, but you will
need to ensure that it is acceptable for use with the
contents of the pipe, as indicated on the side of the tin.
1
7
Copper pipework and fittings
Copper has become well established as a piping material
suitable for all water supplies and in all circumstances.
Making a sound water connection to a pipe is a relatively
simple operation and, once you’ve mastered this skill, you
will be able to undertake fairly substantial projects. There
are three basic jointing methods used in the domestic
environment:
compression joints
soldered joints
push-fit joints.
COMPRESSION JOINTS
These are made using a fitting that clamps a compression
ring on to the pipe and wedges it into the fitting at the
same time (see Figure 6.2). To complete a sound joint,
take the following steps:
1 Push the nut on to the pipe.
3 Insert the end of the pipe fully into the fitting, making
sure that it reaches the stop.
4 Push the compression ring along the pipe to the mouth
of the fitting.
5 Now wind the nut on to the thread of the fitting in a
clockwise direction. This pulls the compression ring
into the fitting. It is essential that the compression nut is
not tightened too much as this will distort the
compression ring inside, which may cause a leak. The
joint should only be tightened sufficiently to hold the
connection firm. When the water is turned on, it can
always be tightened a little more if necessary, but once
1
7
tightened too much no further tightening will cure the
leak.
Note that no jointing materials are necessary to make this
connection: it is a dry jointing method. However, a trick
sometimes used by plumbers, especially where the
compression ring used is not new, is either to wrap a ring
of PTFE tape over the compression ring or to apply a little
jointing paste on to the ring to make up for any blemishes.
This is not applied on to the threads of the fitting, as these
are just used to pull the joint together and do not make the
seal.
nut
pipe compression ring
SOLDERED JOINTS
These are joints that have been made with the use of a
blowlamp, although an electric soldering machine can also
be used to supply sufficient heat to the joint without the
need of a blowlamp.
1
7
There are two types of solder fitting: those that contain a
ring of solder (referred to as solder ring fittings) and those
that require the solder to be applied from a reel (referred to
as end-feed fittings) (see Figure 6.3). When using the
solder ring fittings, no additional solder needs to be
applied to the joint.
Note that the solder used for hot and cold water supplies
needs to be lead free in order to avoid contaminating the
water. However, where central heating pipework is being
installed, it makes no difference what kind of solder you
use. Both of these solders are readily available from
plumbers’ merchants.
ring of solder
within fitting
1
7
2 Apply a suitable flux to the cleaned surfaces. This is a
special paste, readily available from plumbers’
merchants, applied in order to keep the work area clean
while soldering, thereby allowing the molten solder to
stick to the copper and flow easily. Note that solder will
not adhere to dirty or oily surfaces. (There are self-
cleansing fluxes that will clean the pipe and fitting as
the heat is applied, but take care: they can be
aggressive, and any residual flux needs to be fully
flushed from both inside and outside the pipe.)
3 Ensure that there is absolutely no water in the pipe
when soldering, otherwise it will not reach a high
enough temperature – even the smallest drop of water
will prevent the solder from melting.
4 Using a blowlamp or a soldering machine, apply heat to
the assembled joint to melt the solder. Apply the solder
as soon as it melts – do not simply hold the blowlamp
there and burn away all the flux. If solder ring fittings
have been used, the solder will be seen emerging at the
mouth of the fitting. Then remove the heat source.
5 Take care not to set fire to any combustible materials in
the vicinity.
6 Allow the joint to cool before moving it.
1
7
The completion of a soldered joint is a relatively
straightforward task if you follow the guidelines above.
There must be no water in the pipe in order to solder
successfully. The pipe must be clean and have a suitable
flux applied. Any joint that fails will need to be completely
removed.
PUSH-FIT JOINTS
There is a whole range of push-fit joints available. These
joints are very effective and you should not worry that
they will not hold the water pressure – as long as you have
assembled the joint correctly, inserting it fully into the
fitting and ensuring that it is pushed all the way up to the
internal stop. The joint is achieved by the use of an
internal ‘O’ ring. When elbow or bend joints are used, they
have the advantage that they can be swivelled around to
any direction, even when water is in the pipe. Because of
this freedom of movement, the pipework does need to be
fully supported with pipe clips (see below).
Push-fit joints cannot readily be pulled from the pipe as
there is an internal grab ring preventing withdrawal.
However, they can be dismantled and reused. To remove
the joint (see Figure 6.4), push the end collet tightly into
the fitting and, while holding it close to the fitting, pull out
the pipe. Different manufacturers use different methods to
disassemble the joint, so you may need to obtain further
advice from the manufacturer of a particular fitting.
elbow
1
7
push and hold
collet in to ‘O’ ring
withdraw pipe
collet
section through a straight coupling
1
7
CC increase the likelihood of leaks
CC reduce the pressure available at the outlet, due to the
increased frictional resistance caused by the fittings
installed.
It is possible to purchase special flexible pipes and these
do have a use in areas such as making the final
connections to bath taps, but these would again increase
the cost of the work if used extensively throughout a
plumbing project and they do look unsightly. Bends pulled
directly on to the pipe are preferable, but in order to form a
bend you will need either a bending spring or a bending
machine.
1
7
CC If it gets stuck, try gently closing and opening the bend
a little to free up the spring.
Bending springs are ideal where small bends and direction
changes are required and when used to form offsets in the
pipework. With the spring inserted into the pipe, pull it
around a round object or around your knee, keeping the
radius smooth and not too sharp (see Figure 6.5). If at any
time a ripple begins to form in the bend, immediately stop
the process and withdraw the spring as it will undoubtedly
get stuck inside the pipe.
1
8
Figure 6.5 Pipe bending with a spring
CCForming a bend
The procedure described here can be used to form a bend
at any angle up to 90°.
1 First, measure and mark on a straight length of pipe the
distance to the back of the bend you require, as shown
in Figure 6.6.
2 Place the pipe into the bending machine with this mark
square in line with the back of the bending machine.
3 Attach the hook of the tube stop to the pipe.
1
8
Finally, pull down the lever arm to form the bend, stopping
when the desired angle is achieved. Note that to form a
bend in 22 mm pipe requires considerable strength.
‘x’ mark pipe here
pipe
proposed bend
lever arm of
bending machine
pulled down
‘x’ roller
back guide
square
pipe
tube stop
Figure 6.6 Pulling a 90° bend
CCForming an offset
An offset is a series of two bends that, in effect, allows the
pipe to continue in the same direction but along a new
parallel plane.
This is achieved as follows:
1 Take a measurement of the required offset.
1
8
needs, but should not be too sharp otherwise there will
be insufficient room for the tube stop and hook to sit on
the pipe when making the second bend. An angle of
around 30° is usually about right.
3 The pipe is now repositioned in the bending machine,
with the bend you have just pulled pointing upwards.
Ensure that the pipe is lying in the bender with the first
offset in line with the direction of the roller, otherwise
your second bend will be pulled in a different plane.
Place a straight edge parallel to the angle of the first
bend formed, to measure the required distance of the
offset (see Figure 6.7).
4 Once you have measured the correct distance for the
required offset and put the tube stop in place, the pipe
can be pulled round until the correct angle is achieved
along the new parallel plane.
1
8
Fortunately, nowadays the external pipe diameter of most
plastic pipe is the same as for copper, and therefore you
can simply use a mix of the two materials, running plastic
below floors and anywhere else they won’t be seen, and
making the final connections that will be on show in
copper. The push-fit method of jointing would be used
(see above).
The polyethylene (PE) plastic pipe used underground, such
as that used for the mains water supply pipe from the road
into a building, is of a different type and to make this type
of joint a special compression fitting is usually used,
although some pushfit joints can be used. It should be
noted that, when making this plastic joint, an internal
sleeve is inserted into the tube end as it enters the fitting,
thereby providing additional support.
Polyethylene pipe has a very thick wall so, for example, 25
mm PE equates to 22 mm copper pipe and 20 mm PE
equates to 15 mm copper pipe.
1
8
proposed offset
on pipe
required
offset
required
offset straight edge
back guide
fir
st bend
Figure 6.7 Forming an offset
PLASTIC WASTE PIPEWORK
Within the home, plastic plumbing materials for internal
drainage pipes have been used now for well over 40 years.
These materials are very simple to join together and, when
1
8
installed correctly, last for many years without any
problems. The three types of joint used are:
CC push-fit
CC solvent-welded
CC compression fitting (see Figure 6.8).
CCPush-fit joints
These consist of a large ‘O’ ring housed within the fitting
and into which the spigot of another fitting or the plain end
of a pipe is pushed. In order to make a successful joint, the
pipe needs to be cut square and a small bevelled edge
chamfered on to the pipe end, using a rasp or similar tool.
Now, ideally, some silicone lubricant or soap solution is
put on to the pipe and it is pushed firmly into the fitting.
Where a long pipe run has been made, it is advisable to re-
pull the pipe from the fitting a little, say 10 mm, thereby
allowing for expansion of the plastic pipe.
Solvent-welded joints
These joints, once formed, cannot be reused, unlike the
push-fit joint, which can be pulled apart and used over and
over again. The solvent-welded joint uses special solvent
weld cement. It is not a glue used to stick the two surfaces
together but a solvent that burns into the pipe and the
fitting, thereby bonding the two to form a sound, firm
joint. Once made, the joint hardens within seconds and,
when fully set, no amount of pulling or twisting will have
any effect. To form this type of joint, follow these steps:
1 First, clean the pipe en d and the internal surface of the
fitting with a solvent cleaner. This process can be
omitted if your fittings and pipe are reasonably clean.
1
8
2 Now smear a thin layer of solvent cement on to the pipe
end and inside the fitting to be joined to it. Bring the
two together quickly, giving a slight twist, thereby
ensuring that the cement is in contact with all parts of
the mating surfaces. Before the solvent sets, make sure
the bend, if used, is facing in the desired direction.
Leave the fitting to stand for a few minutes, after which
time it will be set quite firm and will generally be ready
for use.
3 It is essential not to use too much solvent cement
because excess cement will be pushed into the pipe and
wasted, and the joint will take much longer to set.
Solvent cement gives off vapours, so do not use it in
confined spaces without plenty of ventilation. The
cement is also highly flammable.
‘O’ ring
compression joint
1
8
Remember this
When forming a solvent-welded joint on plastic waste
pipe, remember that, once the joint has set – usually
within 30 seconds or so – the joint cannot be pulled apart.
If incorrectly positioned, the joint would need to be cut
out of the pipeline.
Compression joints
Waste pipe compression joints are generally restricted to
the connections of traps to the pipework. For this joint, a
rubber compression ring is used. To form this type of joint,
follow these steps:
1 Push the nut on to the pipe.
4 Fully insert the end of the pipe into the fitting, making
sure it reaches the stop.
5 Push the compression ring along the pipe to the mouth
of the fitting.
6 Now wind the nut on to the thread of the fitting in a
clockwise direction. This pulls the flat washer up to the
compression ring, forcing it into the fitting. These joints
are generally made watertight by no more force than
that required to tighten the nut up by hand.
1
8
become frustrated very quickly and find you wish you had
never started the job in the first place.
1
8
✲ Dustsheets
✲ Personal safety equipment
* These are specialist items, which are identified further over
the following pages.
adjustable wrench
‘shetack’ type of
basin spanner
1
9
THE TUBE CUTTER
This is not an essential tool because you can cut a pipe
with a hacksaw, even a junior hacksaw, but it will cut the
pipe squarely and with a great deal of ease. However, its
biggest drawback is that it puts a small internal burr on the
pipe. Often the plumber does not worry about this, but it
can cause noise problems that are not identified until it is
too late to do anything about it. The internal burr should
ideally be reamed or filed out, and many cutters include a
reamer for this purpose. The cutter is operated by winding
down the handle until the single roller touches the pipe
(see Figure 6.10). The tool is then rotated fully around the
pipe; the handle is then wound down another half to one
turn and rotated again. You repeat this process as many
times
cutting
wheel
reamer
1
9
getting into tight areas is the pipe slice, but with this you
need to select one of the correct size, i.e. 15 mm or 22 mm.
This design of cutter automatically cuts the pipe as it is
rotated, without you needing to adjust the blade depth.
These cutters will cut right through the pipe so, before you
cut it, it is absolutely essential to check that there is no
water within the pipe, otherwise this will flow
uncontrollably from the pipe ends when they part.
1
9
when inserting a new tee connection. A bonding wire is
essentially the same as a set of car jump-start leads (see
Figure 6.11).
disconnected
pipe
10 mm2 cable
1
9
generated. Secure where necessary, allowing for
movement, and use rubber or foam mountings.
Solid floors
There is no problem in running the pipework within the
floor screed (i.e. the top layer of sand and cement)
providing there is some protection around the pipe to
prevent chemical attack or corrosion caused by the cement.
In the case of heating pipework, there also needs to be
some provision to allow for expansion. This can be
achieved by placing the pipe within some thin lagging
material or running it within a small floor duct, covered
with a plate. If you wish to run the pipe in concrete, it will
need to be fully protected and to do this you could run it
within a larger-sized pipe.
Timber floors
It is essential to remember that, if you cut too much
material from a structural floor joist, you will weaken it,
possibly making it unsafe. For example, the maximum
depth to which a floor joist can be cut is one-eighth of the
overall depth of the joist, and the notch should be made
close to the bearing wall. Also, when running pipes below
timber floors, remember to allow for expansion and
contraction, and possibly consider
1
9
pipe screwed to
stud with resilient
max =
wall width mounting
3
joist length
max = 4
joist depth
max = 8
timber floors
1
9
PIPES WITHIN WALLS
Solid walls
Pipes can be concealed within an internal wall within a
pipe chase (a channel cut into the wall, as seen in Figure
6.12) and simply plastered over; however, there must be
provision to isolate the pipe should a leak occur. Again,
ideally the pipe should be protected against acid attack
from cement-based products. As with floor joists, there is a
maximum depth at which any pipe chase can be placed
before weakening occurs – this depth is onethird of the
thickness of the wall for vertically installed pipes, and one-
sixth where the pipe chase is run horizontally.
Timber walls
When running pipework within timber stud walls, you
must consider the possibility that the water flowing
through the pipes could resonate through the structure.
Securing the pipe clips on to rubber or felt mountings and
adding additional pipe insulation material will help to
reduce this. Above all, ensure that the system is fully
checked for leaks before finally sealing in the pipes.
Gas installations
Many homes in the UK have a gas supply for the purpose
of heating and cooking. The gas supply may be fed
directly from pipes coming from the street outside your
home and enter via a gas meter. Alternatively, you may
buy your gas in bulk in a liquefied form and store it
outside in a special holding tank until it is required, when
it is drawn off automatically as it is converted to its
gaseous form. These two methods of gas supply are
essentially the same to you, the consumer: you open a pipe
and gas comes out. The two gas types are:
1
9
CC natural gas – fed directly from a pipe in the street
CC liquefied petroleum gas (LPG) – supplied in gas
cylinders or bulk-purchased.
Both types of gas burn in the presence of oxygen,
producing a blue flame. They both have a distinctive smell
– not a true property of the gas but a ‘stenching agent’
added at the production plant, so that it is easy to
recognize should there be a leak.
The two gases have slightly different characteristics. One
of the key differences is the way that they react on leaving
the pipe. Natural gas is lighter than air, so it will rise
upwards and be readily dispersed into the environment.
LPG, on the other hand, is heavier than air and sinks down
towards the ground and so is not as easily dispersed, often
gathering in low-lying pockets such as basements. LPG
gas leaking from a pipe drops around your feet and is less
easily smelled, which results in it rapidly accumulating
undetected.
The gas pipework for a natural gas installation is fed
through a gas meter, purely for billing purposes.
Obviously, this is not required when the gas is bulk-
purchased.
It is important to note the location of the emergency
control valve at the point of entry to the building. This
should be accessible at all times so that, if required, the
supply can be shut off very quickly. From this point the
gas pipe is run to all the appliances requiring a gas supply
(Figure 2.1).
1
9
Within a gas appliance, the registration card,
gas is regulated and passed identifying what areas of
through a fine injector in gas work they are allowed
order to allow the correct to undertake (see Appendix
proportion of gas and air to 1: Legislation).
mix within the combustion
chamber where the fuel is cooke
Index
201
Flues and flue
ventilation for
gas- and oil- flow
burning connection
appliances
Oil-burning appliances
and many gas-burning
passage of
appliances require the flue products
by-products of their
combustion to be
expelled to the external return
connection
environment. This is
achieved by way of a
flue pipe, which could
combustion pres
be one of several chamber insulation
different designs chamber
Figure 2.3 An oil boiler
installation
The end.
Index
203