IAQ6

Air Quality Monitor

INDOOR AIR QUALITY MONITOR


Description:
IAQ6 is an indoor air quality monitor with screen provides
customers with visual indoor air quality readings, such as
PM1.0, PM2.5, PM10, CO2, TVOC, temperature and RH; It is
widely used in residential, commercial and industrial
applications, and can effectively improve air quality and create
a healthy, comfortable, efficient,environmentally friendly,
energy-saving living and working environment.
Features:
▪ Compatible with embedded and wall-mounted fixing methods;
▪ Compatible with push-button and touch-screen operation;
▪ PM1, PM2.5, PM10, CO2, TVOC, temperature and humidity;
▪ Customizable filter alert function.
Working Principle:
▪ The built-in PM sensor uses the principle of laser scattering technology to detect the
indoor PM2.5 mass concentration in real time (μg/m³)
▪ The TVOC sensor uses the semiconductor principle and NDIR technology to detect
indoor CO2 concentration in real time (ppm);
▪ The temperature and humidity sensor use capacitor resistance material to detect the
indoor temperature (OC) and humidity (%) in real time.

Performance Specifications:
Response Time
Parameter Principle Range Accuracy
(T90)
≤ 50μg/m3: ±5μg/m3
PM1 / PM2.5 / Laser Scattering 0~1000μg/m3 ≤ 10s
> 50μg/m3: ±5% reading
PM10
±(30ppm+3%
CO2 NDIR 0~5000ppm < 60s
of reading)

TVOC Semiconductor 0 to 3 levels ±10% of reading < 60s

Temperature Resistance -10OC ~ 50OC ±0.5OC < 10s

Humidity Capacitive 0% ~ 100%RH ±3% of F.S < 10s

▪ PM Values of only PM2.5 and PM10 can be displayed on the screen. PM1 shall not be
visible on the screen

1
IAQ6
Air Quality Monitor

INDOOR AIR QUALITY MONITOR


Performance Specifications:
Operating conditions : -10~50OC,0~100%RH(Non-condensing)
Storage condition : -20~60OC,0~100%RH(Non-condensing)
Coverage Area : 300 sqm
Power supply : 24VDC
Signal Output : RS485

UI Interface Description :

Parameter Range corresponding to color LIST

Gas Level Range Color

Good 0~75
PM2.5
Average 75~115
(μg/m³)
Bad ≥115

Good 0~600
CO2
Average 600~1000
(ppm)
Bad ≥1000

Precautions For Use :


• Do not place the monitor in an environment where the ambient temperature is too high
(above 60OC) or too low (below -20OC).
• Keep it out of reach of children as much as possible to prevent injury from collision and fall.
• Do not drop the monitor or rub it against hard objects during use, otherwise it may cause
damage to the monitor's external light and damage.
• Do not place the monitor in a dusty environment to avoid dust accumulation in the
monitor and affect the measurement accuracy.
• When using the monitor, do not cover or block the vent hole with any object to avoid
affecting the air quality monitoring.
• Do not disassemble, repair or modify the monitor without permission.

2
IAQ6
Air Quality Monitor

INDOOR AIR QUALITY MONITOR


Dimensions (in MM) :

No. Pin Description


1 TA Communication port˄RS485_TA˅
2 TB Communication port˄RS485_TB˅
3 +V Power input˄+24V˅
4 GND Power input˄GND˅

3
IAQ6
Air Quality Monitor

INDOOR AIR QUALITY MONITOR


Installation :
Step 1: Fix the wall mounted bracket with screws on the 86 box which in the embedded
wall, as shown below

Step 2: Connecting Cable, connect the corresponding cable to the monitor's RS485
interface according to the interface definition, as shown below:

Step 3: Match the two holes in the monitor with the hooks in the wall mount bracket and
slide the monitor down to ensure that the monitor is tightly locked with the bracket.