18.34 2021 ASHRAE Handbook-Fundamentals: 7. Heating Load Calculations
18.34 2021 ASHRAE Handbook-Fundamentals: 7. Heating Load Calculations
18.34 2021 ASHRAE Handbook-Fundamentals: 7. Heating Load Calculations
Layer ID from F01 F01 F01 F01 F01 F01 F01 F01 F01
outdoors to indoors F14 F15 F15 F13 F13 F13 F13 F13 F13
(See Table 18) G05 G05 G05 G03 G03 G03 G03 G03 G03
F05 F05 F05 I02 I02 I02 I02 I02 I02
I05 I05 I05 G06 I02 G06 I02 F08 I02
I05 F05 I05 F03 G06 F05 G06 F03 F08
F05 G01 F05 0 F03 F16 F05 0 F03
G01 F03 G01 0 0 F03 F16 0 0
F03 0 F03 0 0 0 F03 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
loads. for those estimating design cooling loads for such uses, with the fol-
lowing exceptions:
7. HEATING LOAD CALCULATIONS
• Temperatures outdoor conditioned spaces are generally lower
Techniques for estimating design heating load for commercial, than maintained space temperatures.
institutional, and industrial applications are essentially the same as
• Credit for solar or internal heat gains is not included
• Thermal storage effect of building structure or content is ignored.
Nonresidential Cooling and Heating Load Calculations 18.35
Layer ID from F01 F01 F01 F01 F01 F01 F01 F01 F01
outdoors to indoors F13 F13 F13 F13 F08 M17 M17 F13 F13
(See Table 18) G03 G03 G03 G03 G03 F13 F13 G03 G03
I02 I02 I03 I03 F05 G03 G03 I03 I03
F08 I02 F08 I03 I05 I03 I03 M11 I03
F05 F08 F03 F08 G01 F08 I03 F03 M11
F16 F05 0 F03 F03 F03 F08 0 F03
F03 F16 0 0 0 0 F03 0 0
0 F03 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0
Thermal bridging effects on wall and roof conduction are greater This simplified approach is justified because it evaluates worst-
for heating loads than for cooling loads, and greater care must be case conditions that can reasonably occur during a heating season.
taken to account for bridging effects on U-factors used in heating Therefore, the near-worst-case load is based on the following:
load calculations.
Heat losses (negative heat gains) are thus considered to be instan- • Design interior and exterior conditions
taneous, heat transfer essentially conductive, and latent heat treated • Including infiltration and/or ventilation
only as a function of replacing space humidity lost to the exterior • No solar effect (at night or on cloudy winter days)
environment. • Before the periodic presence of people, lights, and appliances has
an offsetting effect
18.36 2021 ASHRAE Handbook—Fundamentals
Layer ID from F01 F01 F01 F01 F01 F01 F01 F01 F01 F01
outdoors to indoors F13 F13 F13 F13 F13 F13 F13 F13 F13 F13
(See Table 18) G03 G03 G03 G03 G03 G03 G03 G03 M14 M14
I03 I03 I03 I03 I03 I03 I03 I03 F05 F05
M12 I03 M13 I03 M14 I03 M15 I03 I05 I05
F03 M12 F03 M13 F03 M14 F03 M15 F16 I05
0 F03 0 F03 0 F03 0 F03 F03 F16
0 0 0 0 0 0 0 0 0 F03
0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0
0 0 0 0 0 0 0 0 0 0
Typical commercial and retail spaces have nighttime unoccupied some perimeter heat may be required, leaving infiltration and ven-
periods at a setback temperature where little to no ventilation is tilation as the primary heating loads. Ventilation heat load may be
required, building lights and equipment are off, and heat loss is pri- offset with heat recovery equipment. These loads (conduction loss,
marily through conduction and infiltration. Before being occupied, warm-up load, and ventilation load) may not be additive when siz-
buildings are warmed to the occupied temperature (see the follow- ing building heating equipment, and it is prudent to analyze each
ing discussion). During occupied time, building lights, equipment, load and their interactions to arrive at final equipment sizing for
and people cooling loads can offset conduction heat loss, although heating.
Nonresidential Cooling and Heating Load Calculations 18.37
Carpet
Carpet
Carpet
Carpet
Carpet
Carpet
With
With
With
%
No
No
No
Glass 10% 50% 90% 10% 50% 90% 10% 50% 90% 10% 50% 90% 10% 50% 90% 10% 50% 90%
Hour Radiant Time Factor, %
0 47 50 53 41 43 46 46 49 52 31 33 35 34 38 42 22 25 28 46 40 46 31 33 21
1 19 18 17 20 19 19 18 17 16 17 16 15 9 9 9 10 9 9 19 20 18 17 9 9
2 11 10 9 12 11 11 10 9 8 11 10 10 6 6 5 6 6 6 11 12 10 11 6 6
3 6 6 5 8 7 7 6 5 5 8 7 7 4 4 4 5 5 5 6 8 6 8 5 5
4 4 4 3 5 5 5 4 3 3 6 5 5 4 4 4 5 5 4 4 5 3 6 4 5
5 3 3 2 4 3 3 2 2 2 4 4 4 4 3 3 4 4 4 3 4 2 4 4 4
6 2 2 2 3 3 2 2 2 2 4 3 3 3 3 3 4 4 4 2 3 2 4 3 4
7 2 1 1 2 2 2 1 1 1 3 3 3 3 3 3 4 4 4 2 2 1 3 3 4
8 1 1 1 1 1 1 1 1 1 3 2 2 3 3 3 4 3 3 1 1 1 3 3 4
9 1 1 1 1 1 1 1 1 1 2 2 2 3 3 2 3 3 3 1 1 1 2 3 3
10 1 1 1 1 1 1 1 1 1 2 2 2 3 2 2 3 3 3 1 1 1 2 3 3
11 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 3 3 3 1 1 1 2 2 3
12 1 1 1 1 1 1 1 1 1 1 1 1 2 2 2 3 3 3 1 1 1 1 2 3
13 1 1 1 0 1 0 1 1 1 1 1 1 2 2 2 3 3 2 1 1 1 1 2 3
14 0 0 1 0 1 0 1 1 1 1 1 1 2 2 2 3 2 2 1 0 1 1 2 3
15 0 0 1 0 0 0 1 1 1 1 1 1 2 2 2 2 2 2 0 0 1 1 2 3
16 0 0 0 0 0 0 1 1 1 1 1 1 2 2 2 2 2 2 0 0 1 1 2 3
17 0 0 0 0 0 0 1 1 1 1 1 1 2 2 2 2 2 2 0 0 1 1 2 2
18 0 0 0 0 0 0 1 1 1 1 1 1 2 2 1 2 2 2 0 0 1 1 2 2
19 0 0 0 0 0 0 0 1 0 0 1 1 2 2 1 2 2 2 0 0 1 0 2 2
20 0 0 0 0 0 0 0 0 0 0 1 1 2 1 1 2 2 2 0 0 0 0 2 2
21 0 0 0 0 0 0 0 0 0 0 1 1 2 1 1 2 2 2 0 0 0 0 2 2
22 0 0 0 0 0 0 0 0 0 0 1 0 1 1 1 2 2 2 0 0 0 0 1 2
23 0 0 0 0 0 0 0 0 0 0 0 0 1 1 1 2 2 1 0 0 0 0 1 2
100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Fp = heat loss coefficient per foot of perimeter, Btu/h·ft·°F, Table 24 Table 25 Common Sizing Calculations in Other Chapters
p = perimeter (exposed edge) of floor, ft Subject Volume/Chapter Equation(s)
Surfaces Adjacent to Buffer Space. Heat loss to adjacent Duct heat transfer ASTM Standard C680
unconditioned or semiconditioned spaces can be calculated using a Piping heat transfer Fundamentals Ch. 4 Table 2
heating factor based on the partition temperature difference: Pump power Systems Ch. 44 (3), (4)
Moist-air sensible heating and cooling Fundamentals Ch. 1 (43)
Moist-air cooling and dehumidification Fundamentals Ch. 1 (45)
HF = U (tin – tb) (42)
Air mixing Fundamentals Ch. 1 (46)
Space heat absorption and moist-air Fundamentals Ch. 1 (48)
Infiltration moisture gains
Adiabatic mixing of water injected into Fundamentals Ch. 1 (47)
Infiltration of outdoor air through openings into a structure is moist air
caused by thermal forces, wind pressure, and negative pressure
(planned or unplanned) with respect to the outdoors created by
mechanical systems. Typically, in building design, if the mechani- 7.2 HEATING SAFETY FACTORS AND LOAD
cal systems are designed to maintain positive building pressure, ALLOWANCES
infiltration need not be considered except in ancillary spaces such
as entryways and loading areas. Before mechanical cooling became common in the second half
Infiltration is treated as a room load and has both sensible and of the 1900s, and when energy was less expensive, buildings
latent components. During winter, this means heat and humidity included much less insulation; large, operable windows; and gener-
loss because cold, dry air must be heated to design temperature and ally more infiltration-prone assemblies than the energy-efficient and
moisture must be added to increase the humidity to design condi- much tighter buildings typical of today. Allowances of 10 to 20% of
tion. Typically, during winter, controlling indoor humidity is not a the net calculated heating load for piping losses to unheated spaces,
factor and infiltration is reduced to a simple sensible component. and 10 to 20% more for a warm-up load, were common practice,
Under cooling conditions, both sensible and latent components are along with other occasional safety factors reflecting the experience
added to the space load to be treated by the air conditioning sys- and/or concern of the individual designer. Such measures are less
tem.Procedures for estimating the infiltration rate are discussed in conservatively applied today with newer construction. A combined
Chapter 16. The infiltration rate is reduced to a volumetric flow rate warm-up/safety allowance of 20 to 25% is fairly common but varies
at a known dry bulb/wet bulb condition. Along with indoor air con- depending on the particular climate, building use, and type of con-
dition, the following equations define the infiltration sensible and struction. Engineering judgment must be applied for the particular
latent loads. project. Armstrong et al. (1992a, 1992b) provide a design method to
deal with warm-up and cooldown load.
qs (Btu/h) = 60(cfm/v)cp (tin – to) (43)
7.3 OTHER HEATING CONSIDERATIONS
where
cfm = volume flow rate of infiltrating air
Calculation of design heating load estimates has essentially
become a subset of the more involved and complex estimation of
cp = specific heat capacity of air, Btu/lbm ·°F cooling loads for such spaces. Chapter 19 discusses using the
v = specific volume of infiltrating air, ft3/lbm heating load estimate to predict or analyze energy consumption over
time. Special provisions to deal with particular applications are cov-
Assuming standard air conditions (59°F and sea-level condi- ered in the 2019 ASHRAE Handbook—HVAC Applications and the
tions) for v and cp , Equation (43) may be written as 2020 ASHRAE Handbook—HVAC Systems and Equipment.
The 1989 ASHRAE Handbook—Fundamentals was the last edi-
qs (Btu/h) = 1.10(cfm)(tin – to) (44) tion to contain a chapter dedicated only to heating load. Its contents
were incorporated into this volume’s Chapter 17, which describes
The infiltrating air also introduces a latent heating load given by steady-state conduction and convection heat transfer and provides,
among other data, information on losses through basement floors
and slabs.
ql (Btu/h) = 60(cfm/v)(Win – Wo)Dh (45)
chapter, which is general in nature. Table 25 lists the most fre- Variable-Air-Volume Systems
quently used calculations in other chapters and volumes.
Variable-air-volume (VAV) systems have airflow controls that
adjust cooling airflow to match the room cooling load. Damper
8.1 ZONING leakage or minimum airflow settings may cause overcooling, so
most VAV systems are used in conjunction with separate heating
Organization of building rooms into zones as defined for load systems. These may be duct-mounted heating coils, or separate radi-
calculations and air-handling units has no effect on room cooling ant or convective heating systems.
loads. However, specific grouping and ungrouping of rooms into The amount of heat added by the heating systems during cooling
zones may cause peak system loads to occur at different times becomes part of the room cooling load. Calculations must deter-
during the day or year, and may significantly affect heat removal mine the minimum airflow relative to off-peak cooling loads. The
equipment sizes. quantity of heat added to the cooling load can be determined for
For example, if each room is cooled by a separate heat removal each terminal by Equation (8) using the minimum required supply
system, the total capacity of the heat transport systems equals the airflow rate and the difference between supply air temperature and
sum of peak room loads. Conditioning all rooms by a single heat the room indoor heating design temperature.
transport system (e.g., a variable-volume air handler) requires less
capacity (equal to the simultaneous peak of the combined rooms
load, which includes some rooms at off-peak loads). This may sig- Constant-Air-Volume Reheat Systems
nificantly reduce equipment capacity, depending on the configura-
tion of the building. In constant-air-volume (CAV) reheat systems, all supply air is
cooled to remove moisture and then heated to avoid overcooling
rooms. Reheat refers to the amount of heat added to cooling supply
8.2 VENTILATION air to raise the supply air temperature to the temperature necessary
for picking up the sensible load. The quantity of heat added can be
Consult ASHRAE Standard 62.1 and building codes to deter- determined by Equation (8).
mine the required quantity of ventilation air for an application, and With a constant-volume reheat system, heat transport system
the various methods of achieving acceptable indoor air quality. The load does not vary with changes in room load, unless the cooling
following discussion is confined to the effect of mechanical venti- coil discharge temperature is allowed to vary. Where a minimum
lation on sizing heat removal equipment. Where natural ventilation circulation rate requires a supply air temperature greater than the
is used, through operable windows or other means, it is considered available design supply air temperature, reheat adds to the cooling
as infiltration and is part of the direct-to-room heat gain. Where load on the heat transport system. This makes the cooling load on
ventilation air is conditioned and supplied through the mechanical the heat transport system larger than the room peak load.
system, its sensible and latent loads are applied directly to heat
transport and central equipment, and do not affect room heating and
Mixed Air Systems
cooling loads. If the mechanical ventilation rate sufficiently exceeds
exhaust airflows, air pressure may be positive and infiltration from
envelope openings and outdoor wind may not be included in the Mixed air systems change the supply air temperature to match
the cooling capacity by mixing airstreams of different temperatures;
load calculations. Chapter 16 includes more information on venti-
examples include multizone and dual-duct systems. Systems that
lating commercial buildings.
cool the entire airstream to remove moisture and to reheat some of
Depending on ventilation requirements and local climate condi- the air before mixing with the cooling airstream influence load on
tions, peak cooling coil loads may occur at peak dehumidification or the heat transport system in the same way a reheat system does.
enthalpy conditions instead of design dry-bulb conditions. Coil Other systems separate the air paths so that mixing of hot- and cold-
loads should be checked against all those peak conditions. deck airstreams does not occur. For systems that mix hot and cold
airstreams, the contribution to the heat transport system load is
determined as follows.
8.3 AIR HEAT TRANSPORT SYSTEMS
1. Determine the ratio of cold-deck flow to hot-deck flow from
Heat transport equipment is usually selected to provide adequate
Qh
heating or cooling for the peak load condition. However, selection ------ = (Tc – Tr)/(Tr – Th)
must also consider maintaining desired indoor conditions during all Qc
occupied hours, which requires matching the rate of heat transport
to room peak heating and cooling loads. Automatic control systems 2. From Equation (9), the hot-deck contribution to room load
normally vary the heating and cooling system capacity during these during off-peak cooling is
off-peak hours of operation.
qrh = 1.1Qh (Th – Tr)
Heat Gain from Fans qfr = heat release to room housing motor and drive, Btu/h
2545 = conversion factor, Btu/h·hp
Fans that circulate air through HVAC systems add energy to the
system through the following processes: Supply airstream temperature rise may be determined from psy-
chrometric formulas or Equation (8).
• Increasing velocity and static pressure adds kinetic and potential
Variable- or adjustable-frequency drives (VFDs or AFDs) often
energy
drive fan motors in VAV air-handling units. These devices release
• Fan inefficiency in producing airflow and static pressure adds
heat to the surrounding space. Refer to manufacturers’ data for heat
sensible heat (fan heat) to the airflow
released or efficiencies. The disposition of heat released is deter-
• Inefficiency of motor and drive dissipates sensible heat
mined by the drive’s location: in the conditioned space, in the return
The power required to provide airflow and static pressure can be air path, or in a nonconditioned equipment room. These drives, and
determined from the first law of thermodynamics with the following other electronic equipment such as building control, data process-
equation: ing, and communications devices, are temperature sensitive, so the
rooms in which they are housed require cooling, frequently year
PA = 0.000157Vp round.
where
PA = air power, hp
Duct Surface Heat Transfer
V = flow rate, cfm Heat transfer across the duct surface is one mechanism for
p = pressure, in. of water energy transfer to or from air inside a duct. It involves conduction
through the duct wall and insulation, convection at inner and outer
at standard air conditions with air density = 0.075 lb/ft3 built into the surfaces, and radiation between the duct and its surroundings.
multiplier 0.000157. The power necessary at the fan shaft must Chapter 4 presents a rigorous analysis of duct heat loss and gain,
account for fan inefficiencies, which may vary from 50 to 70%. This and Chapter 23 addresses application of analysis to insulated duct
may be determined from systems.
PF = PA / F
The effect of duct heat loss or gain depends on the duct routing,
duct insulation, and its surrounding environment. Consider the fol-
where lowing conditions:
PF = power required at fan shaft, hp
F = fan efficiency, dimensionless
• For duct run within the area cooled or heated by air in the duct,
heat transfer from the space to the duct has no effect on heating or
The power necessary at the input to the fan motor must account for cooling load, but beware of the potential for condensation on cold
fan motor inefficiencies and drive losses. Fan motor efficiencies ducts.
generally vary from 80 to 95%, and drive losses for a belt drive are • For duct run through unconditioned spaces or outdoors, heat
3% of the fan power. This may be determined from transfer adds to the cooling or heating load for the air transport
system but not for the conditioned space.
PM = (1 + DL) PF /EM ED
• For duct run through conditioned space not served by the duct,
where heat transfer affects the conditioned space as well as the air trans-
port system serving the duct.
PM = power required at input to motor, hp
ED = belt drive efficiency, dimensionless • For an extensive duct system, heat transfer reduces the effective
EM = fan motor efficiency, dimensionless supply air differential temperature, requiring adjustment through
PF = power required at fan shaft, hp air balancing to increase airflow to extremities of the distribution
DL = drive loss, dimensionless system.
Almost all the energy required to generate airflow and static pressure Duct Leakage
is ultimately dissipated as heat in the building and HVAC system; a Air leakage from supply ducts can considerably affect HVAC
small portion is discharged with any exhaust air. Generally, it is system energy use. Leakage reduces cooling and/or dehumidify-
assumed that all the heat is released at the fan rather than dispersed ing capacity for the conditioned space, and must be offset by
to the remainder of the system. The portion of fan heat released to the increased airflow (sometimes reduced supply air temperatures),
airstream depends on the location of the fan motor and drive: if they unless leaked air enters the conditioned space directly. Supply air
are within the airstream, all the energy input to the fan motor is leakage into a ceiling return plenum or leakage from uncondi-
released to the airstream. If the fan motor and drive are outdoor the tioned spaces into return ducts also affects return air temperature
airstream, the energy is split between the airstream and the room and/or humidity.
housing the motor and drive. Therefore, the following equations may
Determining leakage from a duct system is complex because of
be used to calculate heat generated by fans and motors:
the variables in paths, fabrication, and installation methods. Refer
If motor and drive are outside the airstream, to Chapter 21 and publications from the Sheet Metal and Air Con-
ditioning Contractors’ National Association (SMACNA) for meth-
qf s = 2545PF
ods of determining leakage. In general, good-quality ducts and
qfr = 2545(PM – PF ) post-installation duct sealing provide highly cost-effective energy
savings, with improved thermal comfort and delivery of ventilation
If motor and drive are inside the airstream, air.
qf s = 2545PM
Ceiling Return Air Plenum Temperatures
qf r = 0.0 The space above a ceiling, when used as a return air path, is a
where ceiling return air plenum, or simply a return plenum. Unlike a tra-
PF = power required at fan shaft, hp ditional ducted return, the plenum may have multiple heat sources
PM = power required at input to motor, hp in the air path. These heat sources may be radiant and convective
qf s = heat release to airstream, Btu/h loads from lighting and transformers; conduction loads from adja-