03-PAS-Design & Config - C264 Device Configuration

Download as pdf or txt
Download as pdf or txt
You are on page 1of 16

EcoStruXure Power Automation System –

Design & Configuration


C264 Device configuration
EcoStruxureTM Power Automation System
Power Solutions Global Training
2021

Confidential Property of Schneider Electric


Internal
Chapter Objectives
By the completion of this chapter, you will be able to:

• configure C264 in system part of SCE


application

Confidential Property of Schneider Electric | Page 2


Internal
Safety Information
This is training presentation, reference information is in Official Technical Guides.

▪ It is advisable to read all the Safety


Information, all the time before trying to
Install, Operate, Service or Maintain it.
▪ Electrical equipment should be installed,
operated, serviced and maintained only
by qualified personnel.
▪ Work with facility IT System
Administrators to ensure that the system
adheres to the site-specific cybersecurity
policies.

Failure to follow these instructions can result


in death, serious injury, or equipment
damage.

Confidential Property of Schneider Electric | Page 3

Internal
Agenda
• C264 object attributes
• C264 sons
• Multi-rack configuration
• Redundant configuration

Confidential Property of Schneider Electric | Page 4


Internal
• Add / Configure MiCOM C264
▪ Under SCS / IEDs
Add from Object Entry window

Note1 : use C264 configured in starting database

Note2 : create new C264 by copy/paste of existing one

Confidential Property of Schneider Electric | Page 5


Internal
• MiCOM C264 Attributes
▪ General Tab

Computer Name

80TE=C264 / 40TE=C264C /60 TE

Network name
(IP v4 set on AP)

Confidential Property of Schneider Electric | Page 6


Internal
• MiCOM C264 Attributes
▪ BI Filtering Tab

Debouncing / Filtering => signal


validation

Toggling parameters
Note : used for SPS, DPS and MPS acquisition on DI board

Filtering time Debouncing / Filtering => signal validation


Deboucing Timetag => t0 or t2 (configurable for each Datapoint )
time

t0 t1 t2

SPS :

DPS :

Toggling applied on validated signal

Confidential Property of Schneider Electric | Page 7


Internal
• MiCOM C264 Attributes
▪ Measurements Tab

Debouncing / Filtering => signal


validation for Digital Measurements
AI board acquisition cycle

CT/VT board acquisition frequency


(neighbourhood of 0)

MV transmission cycle on SBUS and


LHMI
Long period = N x short period
Transmission periods are used if MV is declared as “periodic”
• too small transmission periods values has impact on size of SQL Historian database (in case of too many
values stored)
• Start configuration with few MV sent ( and add more only on customer request)
• Check first with long cycles how MVs are changing then later configure MVs to be sent on modification
according to deadband …
Confidential Property of Schneider Electric | Page 8
Internal
• MiCOM C264 Attributes
▪ Counter Tab

Debouncing / Filtering => signal


validation for counted Digital Input

Note : Applicable for single or double counters

▪ Miscellaneous Tab

Avoid endless C264 reboot on fault detection, define


a number of faults acceptable during a period.

Example : after 5 major faults during one hour , the


C264 will stop (and not reboot)

Confidential Property of Schneider Electric | Page 9


Internal
• MiCOM C264 Sons
▪ Basic = System Infos + 3 boards (CPU,BIU,GHU) + AP (Network and IEC configuration)

I/O Boards :
Naming Good Practice :
Slot#_<board type>_<board nb>

Access Point with IEC 61850


Mapping
Created by Automatic Addressing
function

PLC Object
C264 Automations

Confidential Property of Schneider Electric | Page 10


Internal
• MiCOM C264 Sons
▪ Basic = System Infos + 3 boards (CPU,BIU,GHU) + IEC Mapping

List of System Information :


Operating Mode, Synchronisation Status, ...

Note : don’t use C264 / System Info / L/R


DPS in graphic views (but use bay L/R
datapoint defined in electric part under bay
definition)

Note : use C264 configured in starting database,


all system information are already configured

Confidential Property of Schneider Electric | Page 11


Internal
• MiCOM C264 Sons
▪ Possible sons = Object Entry Window

Hardware

LBUS per protocol

TBUS (scada network)

Local C264 printer

▪ Add / Configure I/O board


Note : another method is to copy/paste existing board

Physical Board Number Relation made by automatic @


Confidential Property of Schneider Electric | Page 12 (to remove when duplication)
Internal
• MiCOM C264 redundant & Multi-racks
▪ Refer to PACiS SCE2 Overview .ppt / use of Application type
▪ Select Application Type = c264-Standalone
▪ Create New database from scratch using sequence of popups windows

… and so on …

Confidential Property of Schneider Electric | Page 13


Internal
• Redundant MiCOM C264
▪ Create Redundant C264
• Select BCU_xx (= C264) + Right click and “Create Backup”

• Configure Redundant C264 parameters

• Set new values for


• short & long name
• IP address on AP
• IED and Network name

Confidential Property of Schneider Electric | Page 14


Internal
Internal
Internal