HDTD Active Passive Signal Distribution Isolator

Input two-, three-, or four-wire current signals, and output


active / passive current signals after conversion. Three-terminal
isolation between input, output, and power, and provide isolated
24VDC working power to the transmitter in the field.

This product is intelligently designed and uses many advanced


technologies such as digital adjustment, potentiometer, and
automatic zero calibration. It can be used with various types of
instruments and DCS, PLC and other equipment. It is widely used
in major projects in the petroleum, petrochemical, manufacturing,
power, metallurgy and other industries.
Technical Parameters
Input signal Current:0(4)mA~20mA;
Input
≤60Ω
impedance
Output signal Current:0(4)mA~20mA;
Can be OEM, pls see below selection table.
Output load Active:0(4)mA~20mA:≤500Ω;
capacity Passive:R ≤[(U-3)/0.02]Ω;U is loop power Panel indicator
Output ripple ≤5mVrms(Overload 250Ω)
Distribution
Voltage at full load 20mA output ≥24V
output voltage PWR: Power indicator (green).
Accuracy ±0.1%F.S(25℃±2℃) OUT1, OUT2: Channel input signal status indicator (red),
corresponding to channel 1 and channel 2 respectively.
Response time ≤0.5s
This indicator is off during normal working status;
Dielectric strength (leakage current 1mA, test time 1 minute): This indicator flashes when the input signal of the
≥1500 V AC (between input / output / power)
corresponding channel fails;
Insulation
resistance ≥100MΩ,(between input / output / power) When the input signal of the corresponding channel is out
Electromagnetic of range, this indicator is on.
IEC 61326-3-1
Compatibility
Ambient Selection Table
-20℃~+60℃
temperature
Power DC18~32V(Standard 24VDC) HDTD- X X X X

1 One in one out


Channels
Wiring Diagram 2 One in two out

1 4~20mA

Input 2 0~20mA

S Other
4~20mA Active
1HR
Passive in one
0~20mA Active
Output 2HR
Passive in one
S Other

Power DC 18-32V

Sample:
HDTD-211HR,One in two out,Input 4-20mA、Output two
channels 4-20mA Active Passive in one , DC 18-32V power

[键入文字]
Huaibei Huadian Automation Technology Co,.ltd http://www.hd-a.cn