Catalog

Download as pdf or txt
Download as pdf or txt
You are on page 1of 71

Data sheet 6ES7515-2RN03-0AB0

SIMATIC S7-1500R, CPU 1515R-2 PN central processing unit with work memory 1
MB for program and 4.5 MB for data, 1st interface: PROFINET RT with 2-port
switch, 2nd interface: PROFINET, SIMATIC Memory Card required

General information
Product type designation CPU 1515R-2 PN
HW functional status FS04
Firmware version V3.1
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
● SysLog Yes
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V19 (FW V3.1) / V18 (FW V3.0); with older TIA Portal versions configurable as
6ES7515-2RM00-0AB0
Display
Screen diagonal [cm] 6.1 cm
Control elements
Number of keys 8
Mode buttons 2
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Mains buffering
● Mains/voltage failure stored energy time 5 ms
Input current
Current consumption (rated value) 0.65 A
Current consumption, max. 0.88 A
Inrush current, max. 1.15 A
I²t 0.6 A²·s
Power loss
Power loss, typ. 3.6 W
Memory
Number of slots for SIMATIC memory card 1
SIMATIC memory card required Yes
Work memory
● integrated (for program) 1 Mbyte
● integrated (for data) 4.5 Mbyte
Load memory
● Plug-in (SIMATIC Memory Card), max. 32 Gbyte
Backup

6ES75152RN030AB0 Subject to change without notice


5/22/2024
Page 1/6 © Copyright Siemens
WWTP-001
● maintenance-free Yes
CPU processing times
for bit operations, typ. 20 ns
for word operations, typ. 24 ns
for fixed point arithmetic, typ. 32 ns
for floating point arithmetic, typ. 128 ns
CPU-blocks
Number of elements (total) 8 000; Blocks (OB, FB, FC, DB) and UDTs
DB
● Number range Number range: 1 to 59 999
● Size, max. 4.5 Mbyte; For non-optimized block accesses, the max. size of the DB is 64 KB
FB
● Number range 0 ... 65 535
● Size, max. 1 Mbyte
FC
● Number range 0 ... 65 535
● Size, max. 1 Mbyte
OB
● Size, max. 1 Mbyte
● Number of free cycle OBs 100
● Number of time alarm OBs 20
● Number of delay alarm OBs 20
● Number of cyclic interrupt OBs 20; with minimum OB 3x cycle of 10 ms
● Number of process alarm OBs 50
● Number of DPV1 alarm OBs 3
● Number of startup OBs 100
● Number of asynchronous error OBs 4
● Number of synchronous error OBs 2
● Number of diagnostic alarm OBs 1
Nesting depth
● per priority class 24
Counters, timers and their retentivity
S7 counter
● Number 2 048
Retentivity
— adjustable Yes
IEC counter
● Number Any (only limited by the main memory)
Retentivity
— adjustable Yes
S7 times
● Number 2 048
Retentivity
— adjustable Yes
IEC timer
● Number Any (only limited by the main memory)
Retentivity
— adjustable Yes
Data areas and their retentivity
Retentive data area (incl. timers, counters, flags), max. 512 kbyte; Available retentive memory for bit memories, timers, counters, DBs,
and technology data (axes): 472 KB
Flag
● Size, max. 16 kbyte
● Number of clock memories 8; 8 clock memory bit, grouped into one clock memory byte
Data blocks
● Retentivity adjustable Yes
● Retentivity preset No
Local data
● per priority class, max. 64 kbyte; max. 16 KB per block
Address area
Number of IO modules 4 096; max. number of modules / submodules

6ES75152RN030AB0 Subject to change without notice


5/22/2024
Page 2/6 © Copyright Siemens
WWTP-002
I/O address area
● Inputs 32 kbyte; All inputs are in the process image
● Outputs 32 kbyte; All outputs are in the process image
per integrated IO subsystem
— Inputs (volume) 8 kbyte
— Outputs (volume) 8 kbyte
Subprocess images
● Number of subprocess images, max. 31
Hardware configuration
Number of distributed IO systems 16; A distributed I/O system is characterized not only by the integration of
distributed I/O via PROFINET, but also by the connection of I/O via IE/PB-
Links.
Number of IO Controllers
● integrated 1
Rack
● Modules per rack, max. 5; CPU + 2 PS + 2 CP
Time of day
Clock
● Type Hardware clock
● Backup time 6 wk; At 40 °C ambient temperature, typically
● Deviation per day, max. 10 s; Typ.: 2 s
Operating hours counter
● Number 16
Clock synchronization
● supported Yes
● on Ethernet via NTP Yes
Interfaces
Number of PROFINET interfaces 2
1. Interface
Interface types
● RJ 45 (Ethernet) Yes; X1
● Number of ports 2
● integrated switch Yes
Protocols
● IP protocol Yes; IPv4
● PROFINET IO Controller Yes
● PROFINET IO Device No
● SIMATIC communication Yes; Only Server
● Open IE communication Yes; Optionally also encrypted
● Web server Yes
● Media redundancy Yes
PROFINET IO Controller
Services
— Isochronous mode No
— IRT No
— PROFIenergy Yes; per user program
— Number of connectable IO Devices, max. 64
— Updating times The minimum value of the update time also depends on communication share
set for PROFINET IO, on the number of IO devices, and on the quantity of
configured user data
— PROFINET Security Class 1
Update time for RT
— for send cycle of 1 ms 1 ms to 512 ms
2. Interface
Interface types
● RJ 45 (Ethernet) Yes; X2
● Number of ports 1
● integrated switch No
Protocols
● IP protocol Yes; IPv4
● PROFINET IO Controller No
● PROFINET IO Device No

6ES75152RN030AB0 Subject to change without notice


5/22/2024
Page 3/6 © Copyright Siemens
WWTP-003
● SIMATIC communication Yes; Only Server
● Open IE communication Yes; Optionally also encrypted
● Web server Yes
● Media redundancy No
Interface types
RJ 45 (Ethernet)
● 100 Mbps Yes
● Autonegotiation Yes
● Autocrossing Yes
● Industrial Ethernet status LED Yes
Protocols
PROFIsafe No
Number of connections
● Number of connections, max. 256; via integrated interfaces of the CPU and connected CPs
● Number of connections reserved for ES/HMI/web 10
● Number of connections via integrated interfaces 128
● Number of S7 routing paths 16
Redundancy mode
● PROFINET system redundancy (S2) Yes
● PROFINET system redundancy (R1) No
Media redundancy
— MRP Yes; MRP Automanager according to IEC 62439-2 Edition 2.0
— MRP interconnection, supported Yes; as MRP ring node according to IEC 62439-2 Edition 3.0
— MRPD No
— Switchover time on line break, typ. 200 ms; PROFINET MRP
— Number of stations in the ring, max. 50; Only 16 are recommended, however
SIMATIC communication
● PG/OP communication Yes; encryption with TLS V1.3 pre-selected
● S7 routing Yes
● S7 communication, as server Yes
● S7 communication, as client No
Open IE communication
● TCP/IP Yes
— Data length, max. 64 kbyte
— several passive connections per port, supported Yes
● ISO-on-TCP (RFC1006) Yes
— Data length, max. 64 kbyte
● UDP Yes
— Data length, max. 2 kbyte; 1 472 bytes for UDP broadcast
— UDP multicast Yes; max. 118 multicast circuits
● DHCP No
● DNS Yes
● SNMP Yes
● DCP Yes
● LLDP Yes
● Encryption Yes; Optional
Web server
● HTTP No
● HTTPS Yes; only via Web API
● web API Yes
— Number of sessions, max. 100
— number of simultaneous HTTP calls, max. 4
— HTTP request body, max. 131 072 byte
OPC UA
● Runtime license required Yes; "Medium" license required per CPU
● OPC UA Client No
● OPC UA Server Yes; Data access (read, write, subscribe), method call, custom address space
— Application authentication Yes
— Security policies available security policies: None, Basic128Rsa15, Basic256Rsa15,
Basic256Sha256, Aes128Sha256RsaOaep, Aes256Sha256RsaPss
— User authentication "anonymous" or by user name & password

6ES75152RN030AB0 Subject to change without notice


5/22/2024
Page 4/6 © Copyright Siemens
WWTP-004
— GDS support (certificate management) No
— Number of sessions, max. 24
— Number of subscriptions per session, max. 25
— Sampling interval, min. 250 ms
— Publishing interval, min. 250 ms
— Number of server methods, max. 50
— Number of inputs/outputs per server method, max. 20
— Number of monitored items, recommended max. 2 000; for 1 s sampling interval and 1 s send interval
— Number of server interfaces, max. 10 of each "Server interfaces" / "Companion specification" type and 20 of the
type "Reference namespace"
— Number of nodes for user-defined server interfaces, 30 000
max.
● Alarms and Conditions No
Further protocols
● MODBUS Yes; MODBUS TCP
S7 message functions
Number of login stations for message functions, max. 64
number of subscriptions, max. 500
number of tags/attributes for subscriptions, max. 8 000
Program alarms Yes
Number of configurable program messages, max. 10 000; Program messages are generated by the "Program_Alarm" block,
ProDiag or GRAPH
Number of loadable program messages in RUN, max. 10 000
Number of simultaneously active program alarms
● Number of program alarms 1 000
● Number of alarms for system diagnostics 200
Test commissioning functions
Joint commission (Team Engineering) No
Status block Yes; up to 8 simultaneously
Single step No
Number of breakpoints 8; Breakpoints are only supported in RUN-Solo status
Status/control
● Status/control variable Yes
● Variables Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters
● Number of variables, max.
— of which status variables, max. 200; per job
— of which control variables, max. 200; per job
Forcing
● Forcing Yes
● Forcing, variables Peripheral inputs/outputs
● Number of variables, max. 200
Diagnostic buffer
● present Yes
● Number of entries, max. 3 200
— of which powerfail-proof 500
Traces
● Number of configurable Traces 4
● Memory size per trace, max. 512 kbyte
Interrupts/diagnostics/status information
Diagnostics indication LED
● RUN/STOP LED Yes
● ERROR LED Yes
● MAINT LED Yes
● STOP ACTIVE LED Yes
● Connection display LINK TX/RX Yes
Supported technology objects
Motion Control No
Controller
● PID_Compact Yes; Universal PID controller with integrated optimization
● PID_3Step Yes; PID controller with integrated optimization for valves
● PID-Temp Yes; PID controller with integrated optimization for temperature

6ES75152RN030AB0 Subject to change without notice


5/22/2024
Page 5/6 © Copyright Siemens
WWTP-005
Counting and measuring Yes
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -30 °C; No condensation
● horizontal installation, max. 60 °C; Display: 50 °C, at an operating temperature of typically 50 °C, the
display is switched off
● vertical installation, min. -30 °C; No condensation
● vertical installation, max. 40 °C; Display: 40 °C, at an operating temperature of typically 40 °C, the
display is switched off
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
configuration / header
configuration / programming / header
Programming language
— LAD Yes
— FBD Yes
— STL Yes
— SCL Yes
— CFC No
— GRAPH Yes
Know-how protection
● User program protection/password protection Yes
● Copy protection No
● Block protection Yes
Access protection
● protection of confidential configuration data Yes
● Password for display Yes
● Protection level: Write protection Yes
● Protection level: Read/write protection Yes
● Protection level: Write protection for Failsafe No
● Protection level: Complete protection Yes
● User administration Yes
programming / cycle time monitoring / header
● lower limit adjustable minimum cycle time
● upper limit adjustable maximum cycle time
Dimensions
Width 70 mm
Height 147 mm
Depth 129 mm
Weights
Weight, approx. 456 g

last modified: 5/22/2024

6ES75152RN030AB0 Subject to change without notice


5/22/2024
Page 6/6 © Copyright Siemens
WWTP-006
Data sheet 6ES7954-8LE03-0AA0

SIMATIC S7, MEMORY CARD FOR S7-1X00 CPU/SINAMICS, 3,3 V FLASH, 12


MBYTE

General information
Product type designation Memory card
Memory
Type of memory Flash-EPROM
Flash Yes
Memory size 12 Mbyte
Number of write/delete operations, min. 500 000
Data retention (after final programming action), min. 10 a; If the delete/write processes < 50 000 (1 a if the delete/write processes >
450 000)
Dimensions
Width 24 mm
Height 32 mm
Depth 2.1 mm
Weights
Weight, approx. 3g

last modified: 2/8/2021

6ES79548LE030AA0 Subject to change without notice


5/17/2024
Page 1/1 © Copyright Siemens
WWTP-007
Data sheet 6ES7590-1AB60-0AA0

SIMATIC S7-1500, mounting rail 160 mm (approx. 6.3 inch); incl. grounding screw,
integrated DIN rail for mounting of incidentals such as terminals, automatic circuit
breakers and relays

Mechanics/material
Surface design galvanically isolated
Material aluminum
Dimensions
Width 160 mm
Height 155 mm
Depth 16 mm
Weights
Weight, approx. 310 g

last modified: 12/18/2020

6ES75901AB600AA0 Subject to change without notice


5/30/2024
Page 1/1 © Copyright Siemens
WWTP-008
Data sheet 6ES7155-5AA00-0AC0

SIMATIC ET 200MP. PROFINET IO device Interface module IM 155-5 PN HF, for


ET 200MP electronic modules; Up to 12 IO modules without PS; Up to 30 IO
modules with additional PS; Integrated 2-port switch; RJ45 shared device; MRP;
IRT >=0.25 ms; Isochronous mode FW update; I&M0...3; Prioritized startup, S2
redundancy; Shared device with 4 controllers Suitable for operation with active
backplane bus (FW V4.4 or higher)

General information
Product type designation IM 155-5 PN HF
HW functional status From FS03
Firmware version V4.4
● FW update possible Yes
Vendor identification (VendorID) 002AH
Device identifier (DeviceID) 0X0312
Product function
● I&M data Yes; I&M0 to I&M3
● Module swapping during operation (hot swapping) Yes; In combination with active backplane bus
● Isochronous mode Yes
● Tool changer No
● Local coupling, IO data No
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V16
● STEP 7 configurable/integrated from version use GSD file
● PROFINET from GSD version/GSD revision GSDML V2.3
Configuration control
via dataset Yes
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Short-circuit protection Yes
Mains buffering
● Mains/voltage failure stored energy time 5 ms
Input current
Current consumption (rated value) 0.2 A; at 24 V DC and without load
Current consumption, max. 1.2 A
Inrush current, max. 9A
I²t 0.09 A²·s
Power
Infeed power to the backplane bus 14 W
Power available from the backplane bus 2.3 W; in case of operation with separate system power supply to the left of IM
Power loss
Power loss, typ. 4.5 W
Address area
Address space per module
● Address space per module, max. 256 byte; For input and output data respectively

6ES71555AA000AC0 Subject to change without notice


5/31/2024
Page 1/3 © Copyright Siemens
WWTP-009
Address space per station
● Address space per station, max. 512 byte; For input and output data respectively
Hardware configuration
Integrated power supply Yes; 14 W
System power supply can be plugged in to left of IM Yes; only with design with U-connectors
Number of permissible power segments 3; incl. interface module
Rack
● Modules per rack, max. 30; I/O modules
Submodules
● Number of submodules per station, max. 256; 9 per I/O module
Interfaces
Number of PROFINET interfaces 1; 2 ports (switch)
1. Interface
Interface types
● RJ 45 (Ethernet) Yes
● Number of ports 2
● integrated switch Yes
● BusAdapter (PROFINET) No
Protocols
● PROFINET IO Device Yes
● Open IE communication Yes
● Media redundancy Yes; PROFINET MRP client / HRP client
PROFINET IO Device
Services
— IRT Yes; 250 µs to 4 ms in 125 µs frame
— PROFIenergy No
— Prioritized startup Yes
— Shared device Yes
— Number of IO Controllers with shared device, max. 4
Interface types
RJ 45 (Ethernet)
● Transmission procedure PROFINET with 100 Mbit/s full duplex (100BASE-TX)
● 100 Mbps Yes
● Autonegotiation Yes
● Autocrossing Yes
Protocols
Modbus TCP No
Redundancy mode
● PROFINET system redundancy (S2) Yes; NAP S2
— on S7-1500R/H Yes
— on S7-400H Yes; use GSD file
● PROFINET system redundancy (R1) No
● H-Sync forwarding Yes
Media redundancy
— MRP Yes
— MRPD Yes
Open IE communication
● TCP/IP Yes
● SNMP Yes
● LLDP Yes
Isochronous mode
Bus cycle time (TDP), min. 250 µs
Jitter, max. 1 µs
Interrupts/diagnostics/status information
Status indicator Yes
Alarms Yes
Diagnostics function Yes
Diagnostics indication LED
● RUN LED Yes; green LED
● ERROR LED Yes; red LED

6ES71555AA000AC0 Subject to change without notice


5/31/2024
Page 2/3 © Copyright Siemens
WWTP-010
● MAINT LED Yes; Yellow LED
● Connection display LINK TX/RX Yes; 2x green-yellow LEDs
Potential separation
between backplane bus and electronics No
between PROFINET and all other circuits Yes; 1500 V AC (type test)
between supply and all other circuits No
Permissible potential difference
between different circuits Safety extra low voltage SELV
Isolation
Isolation tested with 707 V DC (type test)
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -25 °C; from FS04
● horizontal installation, max. 60 °C
● vertical installation, min. -25 °C; from FS04
● vertical installation, max. 40 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
connection method
ET-Connection
● via BU/BA Send No
Dimensions
Width 35 mm
Height 147 mm
Depth 129 mm
Weights
Weight, approx. 350 g

last modified: 4/25/2024

6ES71555AA000AC0 Subject to change without notice


5/31/2024
Page 3/3 © Copyright Siemens
WWTP-011
Data sheet 6ES7590-1AB60-0AA0

SIMATIC S7-1500, mounting rail 160 mm (approx. 6.3 inch); incl. grounding screw,
integrated DIN rail for mounting of incidentals such as terminals, automatic circuit
breakers and relays

Mechanics/material
Surface design galvanically isolated
Material aluminum
Dimensions
Width 160 mm
Height 155 mm
Depth 16 mm
Weights
Weight, approx. 310 g

last modified: 12/18/2020

6ES75901AB600AA0 Subject to change without notice


5/30/2024
Page 1/1 © Copyright Siemens
WWTP-012
Data sheet 6ES7592-1AM00-0XB0

SIMATIC S7-1500, Front connector Screw-type connection system, 40-pole for 35


mm wide modules incl. 4 potential bridges, and cable ties

General information
Product type designation Front connector
connection method
Connection I/O signals
● Connection method Screw terminals
● Number of lines per connection 1; or combination of 2 conductors of up to 1.5 mm² (total) in a shared ferrule
Conductor cross-section in mm²
— Connectable cable cross-sections for massive 0.25 mm²
cables, min.
— Connectable cable cross-sections for massive 1.5 mm²
cables, min.
— Connectable cable cross-sections for flexible cables 0.25 mm²
without end sleeve, min.
— Connectable cable cross-sections for flexible cables 1.5 mm²
without end sleeve, max.
— Connectable cable cross-sections for flexible cables 0.25 mm²
with end sleeve, min.
— Connectable cable cross-sections for flexible cables 1.5 mm²
with end sleeve, max.
Conductor cross-section acc. to AWG
— Connectable cable cross-sections for massive 24
cables, min.
— Connectable cable cross-sections for massive 16
cables, min.
— Connectable cable cross-sections for flexible cables 24
without end sleeve, min.
— Connectable cable cross-sections for flexible cables 16
without end sleeve, max.
— Connectable cable cross-sections for flexible cables 24
with end sleeve, min.
— Connectable cable cross-sections for flexible cables 16
with end sleeve, max.
Wire end processing
— Stripped length of cables, min. 10 mm
— Stripped length of cables, max. 11 mm
— End sleeve acc. to DIN 46228 without plastic sleeve Form A, 10 mm and 12 mm long
— End sleeve acc. to DIN 46228 with plastic sleeve Form E, 10 mm and 12 mm long
Mounting
— Tool Screwdriver, conical design, 3 mm to 3.5 mm
— Tightening torque, min. 0.4 N·m
— Tightening torque, max. 0.7 N·m
Dimensions
Width 29.8 mm
Height 130.5 mm

6ES75921AM000XB0 Subject to change without notice


5/15/2024
Page 1/2 © Copyright Siemens
WWTP-013
Depth 46 mm
Weights
Weight, approx. 123 g

last modified: 3/12/2024

6ES75921AM000XB0 Subject to change without notice


5/15/2024
Page 2/2 © Copyright Siemens
WWTP-014
Data sheet 6ES7532-5HF00-0AB0

SIMATIC S7-1500, analog output module AQ8xU/I HS, 16-bit resolution accuracy
0.3%, 8 channels in groups of 8, diagnostics; substitute value 8 channels in 0.125
ms oversampling; the module supports the safety-oriented shutdown of load
groups up to SIL2 according to EN IEC 62061:2021 and Category 3 / PL d
according to EN ISO 13849-1:2015. delivery including infeed element, shielding
bracket and shield terminal: front connector (screw terminals or push-in) to be
ordered separately

General information
Product type designation AQ 8xU/I HS
HW functional status From FS01
Firmware version V2.1.0
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode Yes
● Prioritized startup No
● Output range scalable No
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V14 / -
● STEP 7 configurable/integrated from version V5.5 SP3 / -
● PROFIBUS from GSD version/GSD revision V1.0 / V5.1
● PROFINET from GSD version/GSD revision V2.3 / -
Operating mode
● Oversampling Yes
● MSO Yes
CiR - Configuration in RUN
Reparameterization possible in RUN Yes
Calibration possible in RUN Yes
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 320 mA; with 19.2 V supply
Power
Power available from the backplane bus 1.15 W
Power loss
Power loss, typ. 7W
Analog outputs
Number of analog outputs 8
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 45 mA
Current output, no-load voltage, max. 20 V
Cycle time (all channels), min. 125 µs; independent of number of activated channels
Output ranges, voltage

6ES75325HF000AB0 Subject to change without notice


5/15/2024
Page 1/3 © Copyright Siemens
WWTP-015
● 0 to 10 V Yes
● 1 V to 5 V Yes
● -5 V to +5 V No
● -10 V to +10 V Yes
Output ranges, current
● 0 to 20 mA Yes
● -20 mA to +20 mA Yes
● 4 mA to 20 mA Yes
Connection of actuators
● for voltage output two-wire connection Yes
● for voltage output four-wire connection Yes
● for current output two-wire connection Yes
Load impedance (in rated range of output)
● with voltage outputs, min. 1 kΩ
● with voltage outputs, capacitive load, max. 100 nF
● with current outputs, max. 500 Ω
● with current outputs, inductive load, max. 1 mH
Cable length
● shielded, max. 200 m
Analog value generation for the outputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
● Conversion time (per channel) 50 µs; independent of number of activated channels
Settling time
● for resistive load 30 µs; see additional description in the manual
● for capacitive load 100 µs; see additional description in the manual
● for inductive load 100 µs; see additional description in the manual
Errors/accuracies
Output ripple (relative to output range, bandwidth 0 to 50 kHz), 0.02 %
(+/-)
Linearity error (relative to output range), (+/-) 0.15 %
Temperature error (relative to output range), (+/-) 0.002 %/K
Crosstalk between the outputs, max. -100 dB
Repeat accuracy in steady state at 25 °C (relative to output 0.05 %
range), (+/-)
note regarding accuracy at temperatures below 0 °C, the figures for operating error and temperature
error are doubled
Operational error limit in overall temperature range
● Voltage, relative to output range, (+/-) 0.3 %
● Current, relative to output range, (+/-) 0.3 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to output range, (+/-) 0.2 %
● Current, relative to output range, (+/-) 0.2 %
Isochronous mode
Execution and activation time (TCO), min. 100 µs
Bus cycle time (TDP), min. 250 µs
Interrupts/diagnostics/status information
Diagnostics function Yes
Substitute values connectable Yes
Alarms
● Diagnostic alarm Yes
Diagnoses
● Monitoring the supply voltage Yes
● Wire-break Yes; Only for output type "current"
● Short-circuit Yes; Only for output type "voltage"
● Overflow/underflow Yes
Diagnostics indication LED
● RUN LED Yes; green LED
● ERROR LED Yes; red LED
● Monitoring of the supply voltage (PWR-LED) Yes; green LED
● Channel status display Yes; green LED

6ES75325HF000AB0 Subject to change without notice


5/15/2024
Page 2/3 © Copyright Siemens
WWTP-016
● for channel diagnostics Yes; red LED
● for module diagnostics Yes; red LED
Potential separation
Potential separation channels
● between the channels No
● between the channels, in groups of 8
● between the channels and backplane bus Yes
● Between the channels and load voltage L+ Yes
Permissible potential difference
between S- and MANA (UCM) 8 V DC
Isolation
Isolation tested with 707 V DC (type test)
Standards, approvals, certificates
Suitable for safety-related tripping of standard modules Yes; from FS04
Highest safety class achievable for safety-related tripping of standard modules
● Performance level according to ISO 13849-1 PL d
● Category according to ISO 13849-1 Cat. 3
● SIL acc. to IEC 62061 SIL 2
● remark on safety-oriented shutdown https://support.industry.siemens.com/cs/de/en/view/39198632
product functions / security / header
signed firmware update No
data integrity No
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -30 °C; From FS03
● horizontal installation, max. 60 °C
● vertical installation, min. -30 °C; From FS03
● vertical installation, max. 40 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Dimensions
Width 35 mm
Height 147 mm
Depth 129 mm
Weights
Weight, approx. 325 g

last modified: 3/12/2024

6ES75325HF000AB0 Subject to change without notice


5/15/2024
Page 3/3 © Copyright Siemens
WWTP-017
Data sheet 6ES7531-7NF10-0AB0

SIMATIC S7-1500 Analog input module AI 8xU/I HS, 16 bit resolution, Accuracy
0.3% 8 channels in groups of 8; Common mode voltage 10 V; Diagnostics;
Hardware interrupts 8 channels in 0.0625 ms Oversampling; Delivery including
infeed element, shield bracket and shield terminal: Front connector (screw
terminals or push-in) to be ordered separately

General information
Product type designation AI 8xU/I HS
HW functional status From FS01
Firmware version V2.1.0
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode Yes
● Prioritized startup Yes
● Measuring range scalable No
● Scalable measured values No
● Adjustment of measuring range No
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V14 / -
● STEP 7 configurable/integrated from version V5.5 SP3 / -
● PROFIBUS from GSD version/GSD revision V1.0 / V5.1
● PROFINET from GSD version/GSD revision V2.3 / -
Operating mode
● Oversampling Yes
● MSI Yes
CiR - Configuration in RUN
Reparameterization possible in RUN Yes
Calibration possible in RUN Yes
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 240 mA; with 24 V DC supply
Encoder supply
24 V encoder supply
● Short-circuit protection Yes
● Output current, max. 20 mA; Max. 47 mA per channel for a duration < 10 s
Power
Power available from the backplane bus 1.15 W
Power loss
Power loss, typ. 3.4 W
Analog inputs

6ES75317NF100AB0 Subject to change without notice


5/16/2024
Page 1/4 © Copyright Siemens
WWTP-018
Number of analog inputs 8
● For current measurement 8
● For voltage measurement 8
permissible input voltage for voltage input (destruction limit), 28.8 V
max.
permissible input current for current input (destruction limit), 40 mA
max.
Input ranges (rated values), voltages
● 0 to +5 V No
● 0 to +10 V No
● 1 V to 5 V Yes
— Input resistance (1 V to 5 V) 50 kΩ
● -10 V to +10 V Yes
— Input resistance (-10 V to +10 V) 100 kΩ
● -2.5 V to +2.5 V No
● -25 mV to +25 mV No
● -250 mV to +250 mV No
● -5 V to +5 V Yes
— Input resistance (-5 V to +5 V) 50 kΩ
● -50 mV to +50 mV No
● -500 mV to +500 mV No
● -80 mV to +80 mV No
Input ranges (rated values), currents
● 0 to 20 mA Yes
— Input resistance (0 to 20 mA) 41 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
● -20 mA to +20 mA Yes
— Input resistance (-20 mA to +20 mA) 41 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
● 4 mA to 20 mA Yes
— Input resistance (4 mA to 20 mA) 41 Ω; Plus approx. 42 ohms for overvoltage protection by PTC
Input ranges (rated values), thermocouples
● Type B No
● Type C No
● Type E No
● Type J No
● Type K No
● Type L No
● Type N No
● Type R No
● Type S No
● Type T No
● Type TXK/TXK(L) to GOST No
Input ranges (rated values), resistance thermometer
● Cu 10 No
● Cu 10 according to GOST No
● Cu 50 No
● Cu 50 according to GOST No
● Cu 100 No
● Cu 100 according to GOST No
● Ni 10 No
● Ni 10 according to GOST No
● Ni 100 No
● Ni 100 according to GOST No
● Ni 1000 No
● Ni 1000 according to GOST No
● LG-Ni 1000 No
● Ni 120 No
● Ni 120 according to GOST No
● Ni 200 No
● Ni 200 according to GOST No
● Ni 500 No
● Ni 500 according to GOST No

6ES75317NF100AB0 Subject to change without notice


5/16/2024
Page 2/4 © Copyright Siemens
WWTP-019
● Pt 10 No
● Pt 10 according to GOST No
● Pt 50 No
● Pt 50 according to GOST No
● Pt 100 No
● Pt 100 according to GOST No
● Pt 1000 No
● Pt 1000 according to GOST No
● Pt 200 No
● Pt 200 according to GOST No
● Pt 500 No
● Pt 500 according to GOST No
Input ranges (rated values), resistors
● 0 to 150 ohms No
● 0 to 300 ohms No
● 0 to 600 ohms No
● 0 to 3000 ohms No
● 0 to 6000 ohms No
● PTC No
Cable length
● shielded, max. 800 m
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 16 bit
● Basic execution time of the module (all channels 62.5 µs; independent of number of activated channels
released)
Smoothing of measured values
● parameterizable Yes
● Step: None Yes
● Step: low Yes
● Step: Medium Yes
● Step: High Yes
Encoder
Connection of signal encoders
● for voltage measurement Yes
● for current measurement as 2-wire transducer Yes
— Burden of 2-wire transmitter, max. 820 Ω
● for current measurement as 4-wire transducer Yes
● for resistance measurement with two-wire connection No
● for resistance measurement with three-wire connection No
● for resistance measurement with four-wire connection No
Errors/accuracies
Linearity error (relative to input range), (+/-) 0.02 %
Temperature error (relative to input range), (+/-) 0.005 %/K
Crosstalk between the inputs, max. -60 dB
Repeat accuracy in steady state at 25 °C (relative to input 0.02 %
range), (+/-)
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-) 0.3 %
● Current, relative to input range, (+/-) 0.3 %
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-) 0.2 %
● Current, relative to input range, (+/-) 0.2 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Common mode voltage, max. 10 V
● Common mode interference, min. 50 dB at 400 Hz; 60 dB at 60 / 50 / 10 Hz
Isochronous mode
Filtering and processing time (TCI), min. 80 µs
Bus cycle time (TDP), min. 250 µs
Interrupts/diagnostics/status information
Diagnostics function Yes

6ES75317NF100AB0 Subject to change without notice


5/16/2024
Page 3/4 © Copyright Siemens
WWTP-020
Alarms
● Diagnostic alarm Yes
● Limit value alarm Yes; two upper and two lower limit values in each case
Diagnoses
● Monitoring the supply voltage Yes
● Wire-break Yes; only for 1 ... 5 V and 4 ... 20 mA
● Overflow/underflow Yes
Diagnostics indication LED
● RUN LED Yes; green LED
● ERROR LED Yes; red LED
● Monitoring of the supply voltage (PWR-LED) Yes; green LED
● Channel status display Yes; green LED
● for channel diagnostics Yes; red LED
● for module diagnostics Yes; red LED
Potential separation
Potential separation channels
● between the channels No
● between the channels, in groups of 8
● between the channels and backplane bus Yes
● between the channels and the power supply of the Yes
electronics
Permissible potential difference
between the inputs (UCM) 20 V DC
Between the inputs and MANA (UCM) 10 V DC
Isolation
Isolation tested with 707 V DC (type test)
product functions / security / header
signed firmware update No
data integrity No
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -25 °C; From FS02
● horizontal installation, max. 60 °C
● vertical installation, min. -25 °C; From FS02
● vertical installation, max. 40 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Dimensions
Width 35 mm
Height 147 mm
Depth 129 mm
Weights
Weight, approx. 300 g

last modified: 4/25/2024

6ES75317NF100AB0 Subject to change without notice


5/16/2024
Page 4/4 © Copyright Siemens
WWTP-021
Data sheet 6ES7522-1BL01-0AB0

SIMATIC S7-1500, digital output module DQ 32x24V DC/0.5A HF; 32 channels in


groups of 8; 4 A per group; single-channel diagnostics; substitute value, switching
cycle counter for connected actuators. the module supports the safety-oriented
shutdown of load groups up to SIL2 according to EN IEC 62061:2021 and
Category 3 / PL d according to EN ISO 13849-1:2015. front connector (screw
terminals or push-in) to be ordered separately

General information
Product type designation DQ 32x24VDC/0.5A HF
HW functional status From FS02
Firmware version V1.1.0
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode Yes
● Prioritized startup Yes
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V13 SP1 / -
● STEP 7 configurable/integrated from version V5.5 SP3 / -
● PROFIBUS from GSD version/GSD revision V1.0 / V5.1
● PROFINET from GSD version/GSD revision V2.3 / -
Operating mode
● DQ Yes
● DQ with energy-saving function No
● PWM No
● Cam control (switching at comparison values) No
● Oversampling No
● MSO Yes
● Integrated operating cycle counter Yes
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes; through internal protection with 7 A per group
Input current
Current consumption, max. 60 mA
output voltage / header
Rated value (DC) 24 V
Power
Power available from the backplane bus 1.1 W
Power loss
Power loss, typ. 3.5 W
Digital outputs
Type of digital output Transistor
Number of digital outputs 32
Current-sourcing Yes
Digital outputs, parameterizable Yes

6ES75221BL010AB0 Subject to change without notice


5/31/2024
Page 1/3 © Copyright Siemens
WWTP-022
Short-circuit protection Yes; Clocked electronically
● Response threshold, typ. 1A
Limitation of inductive shutdown voltage to L+ (-53 V)
Controlling a digital input Yes
Switching capacity of the outputs
● with resistive load, max. 0.5 A
● on lamp load, max. 5W
Load resistance range
● lower limit 48 Ω
● upper limit 12 kΩ
Output voltage
● for signal "1", min. L+ (-0.8 V)
Output current
● for signal "1" rated value 0.5 A
● for signal "1" permissible range, max. 0.5 A
● for signal "0" residual current, max. 0.5 mA
Output delay with resistive load
● "0" to "1", max. 100 µs
● "1" to "0", max. 500 µs
Parallel switching of two outputs
● for logic links Yes
● for uprating No
● for redundant control of a load Yes
Switching frequency
● with resistive load, max. 100 Hz
● with inductive load, max. 0.5 Hz; According to IEC 60947-5-1, DC-13
● on lamp load, max. 10 Hz
Total current of the outputs
● Current per channel, max. 0.5 A; see additional description in the manual
● Current per group, max. 4 A; see additional description in the manual
● Current per module, max. 16 A; see additional description in the manual
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Isochronous mode
Execution and activation time (TCO), min. 70 µs
Bus cycle time (TDP), min. 250 µs
Interrupts/diagnostics/status information
Diagnostics function Yes
Substitute values connectable Yes
Alarms
● Diagnostic alarm Yes
● Maintenance interrupt Yes
Diagnoses
● Monitoring the supply voltage Yes
● Wire-break Yes
● Short-circuit Yes
● Group error Yes
Diagnostics indication LED
● RUN LED Yes; green LED
● ERROR LED Yes; red LED
● MAINT LED Yes; Yellow LED
● Monitoring of the supply voltage (PWR-LED) Yes; green LED
● Channel status display Yes; green LED
● for channel diagnostics Yes; red LED
● for module diagnostics Yes; red LED
Potential separation
Potential separation channels
● between the channels No
● between the channels, in groups of 8

6ES75221BL010AB0 Subject to change without notice


5/31/2024
Page 2/3 © Copyright Siemens
WWTP-023
● between the channels and backplane bus Yes
Isolation
Isolation tested with 707 V DC (type test)
Standards, approvals, certificates
Suitable for safety functions No
Suitable for safety-related tripping of standard modules Yes; From FS02
Highest safety class achievable for safety-related tripping of standard modules
● Performance level according to ISO 13849-1 PL d
● Category according to ISO 13849-1 Cat. 3
● SIL acc. to IEC 62061 SIL 2
● remark on safety-oriented shutdown https://support.industry.siemens.com/cs/de/en/view/39198632
product functions / security / header
signed firmware update No
data integrity No
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -30 °C; From FS03
● horizontal installation, max. 60 °C
● vertical installation, min. -30 °C; From FS03
● vertical installation, max. 40 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Dimensions
Width 35 mm
Height 147 mm
Depth 129 mm
Weights
Weight, approx. 280 g

last modified: 3/12/2024

6ES75221BL010AB0 Subject to change without notice


5/31/2024
Page 3/3 © Copyright Siemens
WWTP-024
Data sheet 6ES7521-1BL00-0AB0

SIMATIC S7-1500, digital input module DI 32x24 V DC HF, 32 channels in groups


of 16; of which 2 inputs as counters can be used; input delay 0.05..20 ms input
type 3 (IEC 61131); diagnostics; hardware interrupts: front connector (screw
terminals or push-in) to be ordered separately

General information
Product type designation DI 32x24VDC HF
HW functional status from FS04
Firmware version V2.2.1
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode Yes
● Prioritized startup Yes
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V13 SP1 / -
● STEP 7 configurable/integrated from version V5.5 SP3 / -
● PROFIBUS from GSD version/GSD revision V1.0 / V5.1
● PROFINET from GSD version/GSD revision V2.3 / -
Operating mode
● DI Yes
● Counter Yes
● Oversampling No
● MSI Yes
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Input current
Current consumption, max. 40 mA; 20 mA per group with 24 V DC supply
Power
Power available from the backplane bus 1.1 W
Power loss
Power loss, typ. 4.2 W
Digital inputs
Number of digital inputs 32
Digital inputs, parameterizable Yes
Source/sink input P-reading
Input characteristic curve in accordance with IEC 61131, type 3 Yes
Digital input functions, parameterizable
● Gate start/stop Yes
● Freely usable digital input Yes
● Counter

6ES75211BL000AB0 Subject to change without notice


5/15/2024
Page 1/3 © Copyright Siemens
WWTP-025
— Number, max. 2
— Counting frequency, max. 6 kHz; FS04 and FW V2.2.1 or higher
— Counting width 32 bit
— Counting direction up/down Up
Input voltage
● Rated value (DC) 24 V
● for signal "0" -30 to +5 V
● for signal "1" +11 to +30V
Input current
● for signal "1", typ. 2.5 mA
Input delay (for rated value of input voltage)
for standard inputs
— parameterizable Yes; 0.05 / 0.1 / 0.4 / 1.6 / 3.2 / 12.8 / 20 ms
— at "0" to "1", min. 0.05 ms
— at "0" to "1", max. 20 ms
— at "1" to "0", min. 0.05 ms
— at "1" to "0", max. 20 ms
for interrupt inputs
— parameterizable Yes
for technological functions
— parameterizable Yes
Cable length
● shielded, max. 1 000 m
● unshielded, max. 600 m
Encoder
Connectable encoders
● 2-wire sensor Yes
— permissible quiescent current (2-wire sensor), max. 1.5 mA
Isochronous mode
Filtering and processing time (TCI), min. 80 µs; At 50 μs filter time
Bus cycle time (TDP), min. 250 µs
Interrupts/diagnostics/status information
Diagnostics function Yes
Alarms
● Diagnostic alarm Yes
● Hardware interrupt Yes
Diagnoses
● Monitoring the supply voltage Yes
● Wire-break Yes; to I < 350 µA
● Short-circuit No
Diagnostics indication LED
● RUN LED Yes; green LED
● ERROR LED Yes; red LED
● Monitoring of the supply voltage (PWR-LED) Yes; green LED
● Channel status display Yes; green LED
● for channel diagnostics Yes; red LED
● for module diagnostics Yes; red LED
Potential separation
Potential separation channels
● between the channels Yes
● between the channels, in groups of 16
● between the channels and backplane bus Yes
● between the channels and the power supply of the No
electronics
Isolation
Isolation tested with 707 V DC (type test)
Standards, approvals, certificates
Suitable for safety functions No
product functions / security / header
data integrity No

6ES75211BL000AB0 Subject to change without notice


5/15/2024
Page 2/3 © Copyright Siemens
WWTP-026
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -30 °C; From FS05
● horizontal installation, max. 60 °C
● vertical installation, min. -30 °C; From FS05
● vertical installation, max. 40 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
Dimensions
Width 35 mm
Height 147 mm
Depth 129 mm
Weights
Weight, approx. 260 g

last modified: 3/12/2024

6ES75211BL000AB0 Subject to change without notice


5/15/2024
Page 3/3 © Copyright Siemens
WWTP-027
stutvwxXkyz{Xo| lrqpenhX}mhfi~X€XgpehrjX|f~~X€X‚imƒmgX„„
2 K5+25L + XYX
Z[\]^_`a[bc
0 0 946672817873 defghihjX
0928!8273874649649!437449736"294! k Xk
6"29421427##$87464%4&' (826) limnm
97*4!8266!+8232346,4$4$9$46$7-,.)$9$/2$%-!404284 oppXhqXnfrh
717"649*492$17"69466728$
17"64939764!944944)29"2944567,5
+-
876974 )"39746
012346717829
9:;<=>?@AB@CD? )"39746
#22)447#E #"82
49*74F339, 2286$4977246$E G6HHH- #"82
01234328849&2229 5 #25 #,-,-
B@=I:D<
9784J149, 29%4E273J149- 2 K5+25L +
9#469737 0 0 9466728
178730928!8273
874649649!437449736"294!
6"29421427##$87464
%4&' (826)97*4!8266!+
8232346,4$4$9$46$7-,.)$9$/2$%-!
404284717"649*49
2$17"6
9466728$17"64939764!
944944)29"2944567,5
+-
92178& 9466728,0928-
9874&84,8 -  647*49
B@CD?AIM<M
4373477974N93O42P2949 2+2+
974N93
876974 )"39746
6149974 )"39746
9)293492" 2497286 J4
428E29 J4
Q?RCS?@TACUV=@>M<C=U
03998438276 84JJ4J
671247632)714,19%73#2&6- +#2&#2&6
J41473),%3- $72W3
2%2373#71467 K$02$06$7
2%23467.47142694 
G27&'7 744
2%2373G27& 
hh†yttƒf~~‡igpehrj‡imƒmg‡nqƒtƒf~~tmgt„„tˆfhf~q‰tlrqpenhtsŠ‚‹Œkz€{ˆˆks€zo{ ktv
WWTP-028
QRSRTUVWXYZ[W\] ^_`abcdWefdghijWkWlmabjd_nW]giiWkWohfpfmjWqq
0112324567941 35463245
 
 
 !! "#$%& "' 
()*+,-./&0$0123- 45647
8"9:$&;89< 
;89<& "' =
 9>$8%&?&8#2#> ;'8!0>%
 !<1#0>:'&@#$A&$A'&B9CB$0>:'&8'B$8#:$#>B
;#E'>
0::8"#>2&$&= D4&"#8':$#E'
8"9:$&:10BB F&4$0>"08"&<8"9:$&@A#:A&#B&0&B$:G&#$'!
:91"&C'&8'$98>'"&@#$A#>&$A'&8'$98>B
29#"'1#>'B/<'8#"H
7&I//J&50G'6.0:G&KC1#20$#> L'B
=D&8$H&&-9$%&$&#>?8!&0::8"#>2&$ ='0:A&3>?8!0$#>
$A'&:988'>$&1#B$&?&:0>"#"0$'B
43&>9!C'8  $&0E0#10C1'
M76NN2263245N
& O'8B#> 10BB#?#:0$#>
'10BB  666
'10BB  666
'10BB  666
'10BB H 666
'10BB  666
'10BB  666
'10BB H 666
53P  
53P  
53P  

rddsjYRRpgiithmabjd_ntjhfpfmjtc`pRpgiiRfmRqqRugdgìvR^_`abcdRQwoxyXZk[uuXQkZz\[ TRT
WWTP-029
GK0KW,//)C "!7#8715H-2"576C H18982500
I 98 37  -C)-301233K* 51!5 7 8 G)G0H&I/H)J/
G)G0H&I/H)J/
012335657895 7 8
 85271985 7 851281!825802"
" !98277122##1!8258$862%& 5'"1(8
3 55)2 85"88285178 58*58(8+"!7
88 58,5++ 712"5765189825!9-.8276-#,
/011111111111111111111111111111113 27827,8702##
32%&
41571!8 '
+1'
!85
56789:;<=><?@; +1!8#5 2 "
# 7'88712#A
8(1!8B++ 7C 2 538711!785 # 2 "
A)D5
-9 8 862"" 7 CH3)#2"UH3)#
><9E6@8
)71!8F9*8C $87A !12F9*8 G)G0H&I/H)J/
"!7#85!1+712 012335657895 7 8
 8 527198
5 7 851281!825802"
" !98277122##1!8258$862
%& 5'"1(83 55)2 85
"88285178 58*58(8+"!7
88 58,5++ 712"5765189825!9
-.8276-#,/0
11111111111111111111111111111113 27827,87
02##32%&
"!7 916 -C)-301233K* 51!5 7 8
"!7418!6!84C C0//,)!71(8"!7
><?@;=EL8L
812+8!11!1!8M+K GKG
I8 "N 781!8M+
41571!8 ' +1!85
357981!8 ' +1!85
!' 8  C 7815 F 28
C87A !7 F 28
O;P?Q;<R=?ST9<:L8?9S
U2+ 73 27 8 7125 )4,FKU33F,F
U5719 78""15+ 7!'71980 $12# 65 # 6K# 65
F87081'7$ /V
 !$12#1982512 W/2G/20/
 !$851X8217 98 58 3C
D 27176%217 18!8
 !$12D 27176 
YEE?8?9SLP=><9E6@8=ZST9<:L8?9S
U)F W/WGG0
%3 F 7(1*8
3 99 "1763 "8 0W/
4V[\A#&K3 7 -# /
"!7M+ WW
M+3 "8 W
3 276 112 M89 26
3 9+12!817'7'85*572!8
8571!7125!!"127 I"18!71(8 M1(82
"!7! 55 ),72" "+"!7'1!'1557!$1789
!"*88728"17'127'88725
1"81285K+81"
0UUU/KKU%$8H& !$ ]85
.*1 712
U)3I)700#76712 9!!"12 8 !'-2 9 712
77'8!827157 !2"1" 785
3-29*8 F 7(1*8
5PL77?T?@L8?9S7
'77+5,KK9 12"5765189825!9K9 K82K00K3 7 K"!7KG)G0H&I/H)J/ K
WWTP-030
$#$%& "36'( 2 5947'(43) 99!52*274++
1234567 894455 567
28944  
28944  
28944  
28944  
28944  
28944  
28944  
  8
  8
  8
  
 !"!8  ##

, -4&$$* 9957'(43)452*2746*$* 99$27$++$8 96.$"36'( $1#/01 $


WWTP-031
Data sheet 6EP1961-3BA21

SITOP PSE202U/Redundancy M./DC24V/40A

SITOP PSE202U redundancy module input/output: 24 V DC/40 A suitable for


decoupling two SITOP power supplies with maximal per 20 A output current

input
type of the power supply network DC voltage
supply voltage at DC 24 ... 24 V
input voltage at DC 24 ... 28.8 V
output
voltage curve at output Controlled, isolated DC voltage
output voltage at DC rated value 24 V
formula for output voltage Vin - approx. 0.5 V
output voltage
● at output 1 at DC rated value 24 V
output voltage adjustable No
display version for normal operation Green LED for "both Input voltages > switching threshold"; red LED: for "at
least one input voltage < switching threshold"
type of signal at output Isolated relay contact (changeover contacts, rating 8 A/240 V AC, 24 V DC):
Signals OK if both input voltages > switching threshold, setting range of
threshold 20 ... 25 V
output current
● rated value 40 A
● rated range 40 A; max. aggregate current 40 A; +60 ... +70 °C: derating 3%/K
efficiency
efficiency in percent 96.6 %
power loss [W]
● at rated output voltage for rated value of the output 34 W
current typical
● during no-load operation maximum 1.5 W
safety
galvanic isolation yes, SELV acc. to EN 60950-1 (relay contact)
operating resource protection class Class III
protection class IP IP20
standard
● for emitted interference EN 55022 Class B
● for interference immunity EN 61000-6-2
standards, specifications, approvals
certificate of suitability
● CE marking Yes
● UL approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
● CSA approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259
● EAC approval Yes
● NEC Class 2 No
type of certification
● CB-certificate No

6EP19613BA21 Subject to change without notice


5/24/2024
Page 1/3 © Copyright Siemens
WWTP-032
MTBF at 40 °C 6 471 654 h
standards, specifications, approvals hazardous environments
certificate of suitability
● IECEx No
● ATEX No
● ULhazloc approval No
● cCSAus, Class 1, Division 2 No
● FM registration No
standards, specifications, approvals marine classification
shipbuilding approval Yes
Marine classification association
● American Bureau of Shipping Europe Ltd. (ABS) Yes
● French marine classification society (BV) No
● Det Norske Veritas (DNV) Yes
● Lloyds Register of Shipping (LRS) No
ambient conditions
ambient temperature
● during operation -25 ... +60 °C; with natural convection
● during transport -40 ... +85 °C
● during storage -40 ... +85 °C
environmental category according to IEC 60721 Climate class 3K3, 5 ... 95% no condensation
connection method
type of electrical connection screw terminal
● at input Input, output and ground: 1 screw terminal each for 0.33 ... 10 mm² single-
core/finely stranded
● for auxiliary contacts Relay contact: 3 screw terminals for 0.5 ... 2.5 mm² single-core/finely stranded
mechanical data
width × height × depth of the enclosure 70 × 120
installation width × mounting height 70 mm
required spacing
● top 50 mm
● bottom 50 mm
● left 0 mm
● right 0 mm
fastening method Snaps onto DIN rail EN 60715 35x7.5/15
● standard rail mounting Yes
● S7 rail mounting No
● wall mounting No
housing can be lined up Yes
net weight 0.5 kg
further information internet links
internet link
● to website: Industry Mall https://mall.industry.siemens.com
● to web page: selection aid TIA Selection Tool https://siemens.com/tst
● to website: Industrial communication http://www.siemens.com/simatic-net
● to website: CAx-Download-Manager http://www.siemens.com/cax
● to website: Industry Online Support https://support.industry.siemens.com
additional information
other information Specifications at rated input voltage and ambient temperature +25 °C (unless
otherwise specified)
security information
security information Siemens provides products and solutions with industrial cybersecurity functions
that support the secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber
threats, it is necessary to implement – and continuously maintain – a holistic,
state-of-the-art industrial cybersecurity concept. Siemens’ products and
solutions constitute one element of such a concept. Customers are responsible
for preventing unauthorized access to their plants, systems, machines and
networks. Such systems, machines and components should only be connected
to an enterprise network or the internet if and to the extent such a connection is
necessary and only when appropriate security measures (e.g. firewalls and/or
network segmentation) are in place. For additional information on industrial
cybersecurity measures that may be implemented, please visit
www.siemens.com/cybersecurity-industry. Siemens’ products and solutions
undergo continuous development to make them more secure. Siemens strongly

6EP19613BA21 Subject to change without notice


5/24/2024
Page 2/3 © Copyright Siemens
WWTP-033
Data sheet 6EP1333-2BA20

SITOP PSU100S/1AC/24VDC/5A

SITOP PSU100S 24 V/5 A stabilized power supply input: 120/230 V AC output: 24


V DC/5 A

input
type of the power supply network 1-phase AC
supply voltage at AC Automatic range selection
supply voltage 120 V/230 V
input voltage 1 at AC 85 ... 132 V
input voltage 2 at AC 170 ... 264 V
wide range input No
overvoltage overload capability 2.3 × Vin rated, 1.3 ms
buffering time for rated value of the output current in the event of 20 ms
power failure minimum
operating condition of the mains buffering at Vin = 93/187 V
line frequency 50/60 Hz
line frequency 47 ... 63 Hz
input current
● at rated input voltage 120 V 2.34 A
● at rated input voltage 230 V 1.36 A
current limitation of inrush current at 25 °C maximum 40 A
I2t value maximum 1 A²·s
fuse protection type T 3,15 A/250 V (not accessible)
fuse protection type in the feeder Recommended miniature circuit breaker: from 6 A characteristic C
output
voltage curve at output Controlled, isolated DC voltage
output voltage at DC rated value 24 V
output voltage
● at output 1 at DC rated value 24 V

output voltage adjustable Yes; via potentiometer


adjustable output voltage 22.8 ... 28 V
relative control precision of the output voltage
● on slow fluctuation of input voltage 0.1 %
● on slow fluctuation of ohm loading 1%
residual ripple
● maximum 150 mV
● typical 30 mV
voltage peak
● maximum 240 mV
● typical 140 mV
display version for normal operation Green LED for 24 V OK
type of signal at output Relay contact (NO contact, rating 60 V DC/ 0.3 A) for "24 V OK"
behavior of the output voltage when switching on Overshoot of Vout < 3 %
response delay maximum 0.3 s

6EP13332BA20 Subject to change without notice


5/24/2024
Page 1/4 © Copyright Siemens
WWTP-034
voltage increase time of the output voltage
● typical 15 ms
output current
● rated value 5A
● rated range 0 ... 6 A; 6 A up to +45°C; +60 ... +70 °C: Derating 1.6%/K

supplied active power typical 144 W


short-term overload current
● on short-circuiting during the start-up typical 18 A
● at short-circuit during operation typical 18 A
duration of overloading capability for excess current
● on short-circuiting during the start-up 800 ms
● at short-circuit during operation 800 ms
bridging of equipment Yes
number of parallel-switched equipment resources for increasing 2
the power
efficiency
efficiency in percent 88 %
power loss [W]
● at rated output voltage for rated value of the output 16 W
current typical
closed-loop control
relative control precision of the output voltage with rapid 0.3 %
fluctuation of the input voltage by +/- 15% typical
relative control precision of the output voltage at load step of 3%
resistive load 10/90/10 % typical
setting time
● load step 10 to 90% typical 1 ms
● load step 90 to 10% typical 1 ms
protection and monitoring
design of the overvoltage protection protection against overvoltage in case of internal fault Vout < 33 V
property of the output short-circuit proof Yes
design of short-circuit protection Constant current characteristic
response value current limitation 6 ... 7.1 A
overcurrent overload capability
● in normal operation overload capability 150 % Iout rated up to 5 s/min
enduring short circuit current RMS value
● typical 7.1 A
safety
galvanic isolation between input and output Yes
galvanic isolation Safety extra-low output voltage Uout acc. to EN 60950-1 and EN 50178
operating resource protection class Class I
leakage current
● maximum 3.5 mA
● typical 0.4 mA
protection class IP IP20
standard
● for emitted interference EN 55022 Class B
● for mains harmonics limitation EN 61000-3-2
● for interference immunity EN 61000-6-2
standards, specifications, approvals
certificate of suitability
● CE marking Yes
● UL approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus
(CSA C22.2 No. 60950-1, UL 60950-1)
● CSA approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 107.1), File E197259; cCSAus
(CSA C22.2 No. 60950-1, UL 60950-1)
● EAC approval Yes
● NEC Class 2 No
type of certification
● BIS Yes; R-41188271
● CB-certificate Yes
MTBF at 40 °C 1 998 441 h

6EP13332BA20 Subject to change without notice


5/24/2024
Page 2/4 © Copyright Siemens
WWTP-035
standards, specifications, approvals hazardous environments
certificate of suitability
● IECEx No
● ATEX No
● ULhazloc approval No
● cCSAus, Class 1, Division 2 No
● FM registration No
standards, specifications, approvals marine classification
shipbuilding approval Yes
Marine classification association
● American Bureau of Shipping Europe Ltd. (ABS) No
● French marine classification society (BV) Yes
● Det Norske Veritas (DNV) Yes
● Lloyds Register of Shipping (LRS) No
standards, specifications, approvals Environmental Product Declaration
Environmental Product Declaration Yes
Global Warming Potential [CO2 eq]
● total 513.7 kg
● during manufacturing 12.9 kg
● during operation 500.4 kg
● after end of life 0.35 kg
ambient conditions
ambient temperature
● during operation -25 ... +70 °C; with natural convection
● during transport -40 ... +85 °C
● during storage -40 ... +85 °C
environmental category according to IEC 60721 Climate class 3K3, 5 ... 95% no condensation
connection method
type of electrical connection screw terminal
● at input L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm² single-core/finely stranded
● at output +, -: 2 screw terminals each for 0.5 ... 2.5 mm²
● for auxiliary contacts Alarm signals: 2 screw terminals for 0.5 ... 2.5 mm²
● for signaling contact 2 screw terminals for 0.5 ... 2.5 mm²
mechanical data
width × height × depth of the enclosure 50 × 120
installation width × mounting height 50 mm
required spacing
● top 50 mm
● bottom 50 mm
● left 0 mm
● right 0 mm
fastening method Snaps onto DIN rail EN 60715 35x7.5/15
● standard rail mounting Yes
● S7 rail mounting No
● wall mounting No
housing can be lined up Yes
net weight 0.5 kg
accessories
electrical accessories Buffer module
mechanical accessories Device identification label 20 mm × 7 mm, pale turquoise 3RT1900-1SB20
further information internet links
internet link
● to website: Industry Mall https://mall.industry.siemens.com
● to web page: selection aid TIA Selection Tool https://siemens.com/tst
● to website: Industrial communication http://www.siemens.com/simatic-net
● to website: CAx-Download-Manager http://www.siemens.com/cax
● to website: Industry Online Support https://support.industry.siemens.com
additional information
other information Specifications at rated input voltage and ambient temperature +25 °C (unless
otherwise specified)

6EP13332BA20 Subject to change without notice


5/24/2024
Page 3/4 © Copyright Siemens
WWTP-036
security information
security information Siemens provides products and solutions with industrial cybersecurity functions
that support the secure operation of plants, systems, machines and networks.
In order to protect plants, systems, machines and networks against cyber
threats, it is necessary to implement – and continuously maintain – a holistic,
state-of-the-art industrial cybersecurity concept. Siemens’ products and
solutions constitute one element of such a concept. Customers are responsible
for preventing unauthorized access to their plants, systems, machines and
networks. Such systems, machines and components should only be connected
to an enterprise network or the internet if and to the extent such a connection is
necessary and only when appropriate security measures (e.g. firewalls and/or
network segmentation) are in place. For additional information on industrial
cybersecurity measures that may be implemented, please visit
www.siemens.com/cybersecurity-industry. Siemens’ products and solutions
undergo continuous development to make them more secure. Siemens strongly
recommends that product updates are applied as soon as they are available
and that the latest product versions are used. Use of product versions that are
no longer supported, and failure to apply the latest updates may increase
customer’s exposure to cyber threats. To stay informed about product updates,
subscribe to the Siemens Industrial Cybersecurity RSS Feed under
https://www.siemens.com/cert. (V4.7)
Classifications
Version Classification

eClass 14 27-04-07-01
eClass 12 27-04-07-01
eClass 9.1 27-04-07-01
eClass 9 27-04-07-01
eClass 8 27-04-90-02
eClass 7.1 27-04-90-02
eClass 6 27-04-90-02
ETIM 9 EC002540
ETIM 8 EC002540
ETIM 7 EC002540
IDEA 4 4130
UNSPSC 15 39-12-10-04

Approvals Certificates
General Product Approval

Manufacturer Declara- Declaration of Con-


tion formity

General Product Approval Marine / Shipping Environment

Miscellaneous BIS CRS

last modified: 5/22/2024

6EP13332BA20 Subject to change without notice


5/24/2024
Page 4/4 © Copyright Siemens
WWTP-037
recommends that product updates are applied as soon as they are available
and that the latest product versions are used. Use of product versions that are
no longer supported, and failure to apply the latest updates may increase
customer’s exposure to cyber threats. To stay informed about product updates,
subscribe to the Siemens Industrial Cybersecurity RSS Feed under
https://www.siemens.com/cert. (V4.7)
Classifications
Version Classification

eClass 14 27-04-07-01
eClass 12 27-04-07-01
eClass 9.1 27-04-07-01
eClass 9 27-04-07-01
eClass 8 27-04-90-02
eClass 7.1 27-04-90-02
eClass 6 27-04-90-02
ETIM 9 EC002540
ETIM 8 EC002540
ETIM 7 EC002540
IDEA 4 4130
UNSPSC 15 39-12-10-04

Approvals Certificates
General Product Approval Marine / Shipping

Manufacturer Declara- Declaration of Con-


tion formity

Marine / Shipping

last modified: 5/22/2024

6EP19613BA21 Subject to change without notice


5/24/2024
Page 3/3 © Copyright Siemens
WWTP-038
Data sheet 6EP1332-4BA00

SIMATIC PM1507/1AC/24VDC/3A

SIMATIC PM 1507 24 V/3 A Stabilized power supply for SIMATIC S7-1500 input:
120/230 V AC, output: 24 V DC/3 A

input
type of the power supply network 1-phase AC
supply voltage at AC Automatic range selection
supply voltage 120 V/230 V
input voltage 1 at AC 85 ... 132 V
input voltage 2 at AC 170 ... 264 V
wide range input No
overvoltage overload capability 2.3 × Vin rated, 1.3 ms
buffering time for rated value of the output current in the event of 20 ms
power failure minimum
operating condition of the mains buffering at Vin = 93/187 V
line frequency 50/60 Hz
line frequency 45 ... 65 Hz
input current
● at rated input voltage 120 V 1.4 A
● at rated input voltage 230 V 0.8 A
current limitation of inrush current at 25 °C maximum 23 A
duration of inrush current limiting at 25 °C
● maximum 3 ms
I2t value maximum 1.3 A²·s
fuse protection type T 3,15 A/250 V (not accessible)
fuse protection type in the feeder Recommended miniature circuit breaker: 10 A characteristic B or 6 A
characteristic C
output
voltage curve at output Controlled, isolated DC voltage
output voltage at DC rated value 24 V
output voltage
● at output 1 at DC rated value 24 V
output voltage adjustable No
relative overall tolerance of the voltage 1%
relative control precision of the output voltage
● on slow fluctuation of input voltage 0.1 %
● on slow fluctuation of ohm loading 0.1 %
residual ripple
● maximum 50 mV
voltage peak
● maximum 150 mV
display version for normal operation LED green for 24 V OK; LED red for error; LED yellow for stand-by
behavior of the output voltage when switching on No overshoot of Vout (soft start)
response delay maximum 1.5 s
voltage increase time of the output voltage

6EP13324BA00 Subject to change without notice


5/30/2024
Page 1/4 © Copyright Siemens
WWTP-039
● typical 10 ms
output current
● rated value 3A
● rated range 0 ... 3 A
supplied active power typical 72 W
short-term overload current
● on short-circuiting during the start-up typical 12 A
● at short-circuit during operation typical 12 A
duration of overloading capability for excess current
● on short-circuiting during the start-up 70 ms
● at short-circuit during operation 70 ms
bridging of equipment Yes
number of parallel-switched equipment resources for increasing 2
the power
efficiency
efficiency in percent 87 %
power loss [W]
● at rated output voltage for rated value of the output 11 W
current typical
closed-loop control
relative control precision of the output voltage with rapid 0.1 %
fluctuation of the input voltage by +/- 15% typical
relative control precision of the output voltage load step of 1%
resistive load 50/100/50 % typical
relative control precision of the output voltage at load step of 3%
resistive load 10/90/10 % typical
setting time
● load step 10 to 90% typical 5 ms
● load step 90 to 10% typical 5 ms
● maximum 5 ms
protection and monitoring
design of the overvoltage protection Additional control loop, limitation (closed loop control) at < 28.8 V
property of the output short-circuit proof Yes
design of short-circuit protection Electronic shutdown, automatic restart
response value current limitation 3.15 ... 3.6 A
● typical 3.4 A
display version for overload and short circuit -
safety
galvanic isolation between input and output Yes
galvanic isolation Safety extra-low output voltage Vout acc. to EN 60950-1 and EN 50178 and EN
61131-2
operating resource protection class Class I
leakage current
● maximum 3.5 mA
● typical 0.4 mA
protection class IP IP20
standard
● for emitted interference EN 55022 Class B
● for mains harmonics limitation EN 61000-3-2
● for interference immunity EN 61000-6-2
standards, specifications, approvals
certificate of suitability
● CE marking Yes
● UL approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289
● CSA approval Yes; cULus-Listed (UL 508, CSA C22.2 No. 142), File E143289
● EAC approval Yes
● NEC Class 2 No
type of certification
● BIS Yes; R-41183539
● CB-certificate Yes
MTBF at 40 °C 1 611 993 h
standards, specifications, approvals hazardous environments

6EP13324BA00 Subject to change without notice


5/30/2024
Page 2/4 © Copyright Siemens
WWTP-040
certificate of suitability
● IECEx Yes; IECEx Ex nA nC IIC T4 Gc
● ATEX Yes; ATEX (EX) II 3G Ex nA nC IIC T4 Gc
● ULhazloc approval Yes
● cCSAus, Class 1, Division 2 No
● FM registration Yes; Class I, Div. 2, Group ABCD, T4
standards, specifications, approvals marine classification
shipbuilding approval Yes
Marine classification association
● American Bureau of Shipping Europe Ltd. (ABS) Yes
● French marine classification society (BV) Yes
● Det Norske Veritas (DNV) Yes
● Lloyds Register of Shipping (LRS) No
ambient conditions
ambient temperature
● during operation 0 ... 60 °C; with natural convection
● during transport -40 ... +85 °C
● during storage -40 ... +85 °C
environmental category according to IEC 60721 Climate class 3K3, 5 ... 95% no condensation
connection method
type of electrical connection Screw-/spring clamp connection
● at input L, N, PE: 1 screw terminal each for 0.5 ... 2.5 mm²
● at output L+, M: 2 spring-loaded terminals each for 0.5 to 2.5 mm²
removable terminal at input Yes
removable terminal at output Yes
mechanical data
width × height × depth of the enclosure 50 × 147 × 129 mm
installation width × mounting height 50 mm × 205 mm
required spacing
● top 40 mm
● bottom 40 mm
● left 0 mm
● right 0 mm
fastening method Can be mounted onto S7-1500 rail
● standard rail mounting No
● S7 rail mounting Yes
● wall mounting No
housing can be lined up Yes
net weight 0.45 kg
additional information
other information Specifications at rated input voltage and ambient temperature +25 °C (unless
otherwise specified)
Classifications
Version Classification

eClass 14 27-04-07-01
eClass 12 27-04-07-01
eClass 9.1 27-04-07-01
eClass 9 27-04-07-01
eClass 8 27-04-90-02
eClass 7.1 27-04-90-02
eClass 6 27-04-90-02
ETIM 9 EC002540
ETIM 8 EC002540
ETIM 7 EC002540
IDEA 4 4130
UNSPSC 15 39-12-10-04

Approvals Certificates
General Product Approval

6EP13324BA00 Subject to change without notice


5/30/2024
Page 3/4 © Copyright Siemens
WWTP-041
Manufacturer Declara- Miscellaneous
tion

General Product Ap-


For use in hazardous locations
proval

BIS CRS FM

For use in hazardous locations Marine / Shipping

CCC-Ex

last modified: 5/22/2024

6EP13324BA00 Subject to change without notice


5/30/2024
Page 4/4 © Copyright Siemens
WWTP-042
Data sheet 6GK5206-2GS00-2AC2

SCALANCE XC206-2SFP G manageable Layer 2 IE switch; IEC 62443-4-2


certified; 6x 10/100/1000 Mbps RJ45 ports; 2x 1000 Mbps SFP; 1x console port;
diagnostics LED; redundant power supply; temperature range -40 °C to +70 °C;
assembly: DIN rail/S7 mounting rail/wall; redundancy functions; office features
(RSTP, VLAN,...); PROFINET IO device; Ethernet/IP-compliant; C-PLUG slot;
IEEE 1588v2 PTP

product type designation


product brand name SCALANCE
product type designation XC206-2SFP G
transfer rate
transfer rate 10 Mbit/s, 100 Mbit/s, 1000 Mbit/s
interfaces / for communication / integrated
number of electrical connections
● for network components or terminal equipment 6; RJ45
number of 10/100/1000 Mbit/s RJ45 ports
● with securing collar 6
interfaces / for communication / plug-in
number of electrical connections
● for SFP 2
interfaces / other
number of electrical connections
● for operator console 1
● for signaling contact 1
● for power supply 1
type of electrical connection
● for operator console RJ11
● for signaling contact 2-pole terminal block
● for power supply 4-pole terminal block
design of the removable storage
● C-PLUG Yes
operating voltage / of the signaling contacts
● at DC / rated value 24 V
operational current / of the signaling contacts
● at DC / maximum 0.1 A
supply voltage, current consumption, power loss
product component / connection for redundant voltage supply Yes
type of voltage / 1 / of the supply voltage DC
● supply voltage / 1 / rated value 24 V
● power loss [W] / 1 / rated value 6W
● consumed current / 1 / at rated supply voltage / maximum 0.25 A
● supply voltage / 1 / rated value 9.6 ... 31.2 V
● consumed current / 1 / maximum 0.5 A
● type of electrical connection / 1 / for power supply 4-pole terminal block
● product component / 1 / fusing at power supply input Yes
● fuse protection type / 1 / at input for supply voltage 2.5 A / 125 V
ambient conditions

6GK52062GS002AC2 Subject to change without notice


5/24/2024
Page 1/5 © Copyright Siemens
WWTP-043
ambient temperature
● during operation -40 ... +70 °C
● during storage -40 ... +85 °C
● during transport -40 ... +85 °C
relative humidity
● at 25 °C / without condensation / during operation / 95 %
maximum
protection class IP IP20
design, dimensions and weights
design compact
width 60 mm
height 147 mm
depth 125 mm
net weight 0.52 kg
material / of the enclosure Polycarbonate (PC-GF10) / pressure die cast aluminum
fastening method
● 35 mm top hat DIN rail mounting Yes
● wall mounting Yes
● S7-300 rail mounting Yes
● S7-1500 rail mounting Yes
product features, product functions, product components / general
cascading in the case of a redundant ring / at reconfiguration 50
time of <\~0.3\~s
cascading in cases of star topology any (depending only on signal propagation time)
product function
● QoS according to DSCP Yes
product feature
● Cut Through switching method No
● Store & Forward switching method Yes
product functions / management, configuration, engineering
product function
● CLI Yes
● web-based management Yes
● MIB support Yes
● TRAPs via email Yes
● configuration with STEP 7 Yes
● RMON Yes
● SMTP server No
● port mirroring Yes
● multiport mirroring Yes
● CoS Yes
● PROFINET IO diagnosis Yes
● switch-managed Yes
PROFINET conformity class B
network load class / according to PROFINET 3
telegram length / for Ethernet / maximum 10240 byte
protocol / is supported
● Telnet Yes
● HTTP Yes
● HTTPS Yes
● TFTP Yes
● BOOTP No
● GMRP Yes
● DCP Yes
● LLDP Yes
● EtherNet/IP Yes
● SNMP v1 Yes
● SNMP v2 Yes
● SNMP v3 Yes
● IGMP (snooping/querier) Yes
identification & maintenance function

6GK52062GS002AC2 Subject to change without notice


5/24/2024
Page 2/5 © Copyright Siemens
WWTP-044
● I&M0 - device-specific information Yes
● I&M1 - higher level designation/location designation Yes
product functions / diagnostics
product function
● port diagnostics Yes
● statistics Packet Size Yes
● statistics packet type Yes
● error statistics Yes
● SysLog Yes
product functions / VLAN
product function
● VLAN - port based Yes
● VLAN - protocol-based No
● VLAN - IP-based No
number of VLANs / maximum 257
number of VLANs - dynamic / maximum 257
number of VLANs / at ring redundancy (HRP; MRP; standby 257
link)
product functions / DHCP
product function
● DHCP server Yes
● DHCP client Yes
● DHCP Option 82 Yes
● DHCP Option 66 Yes
● DHCP Option 67 Yes
product functions / redundancy
protocol / is supported / Media Redundancy Protocol (MRP) Yes
product function
● media redundancy protocol (MRP) with redundancy Yes
manager
● Media Redundancy Protocol Interconnection (MRP-I) Yes
● of the PROFINET IO device / is supported / H-Sync Yes
forwarding
● of the PROFINET IO device / is supported / PROFINET Yes
system redundancy
● ring redundancy Yes
● high speed redundancy protocol (HRP) with redundancy Yes
manager
● high speed redundancy protocol (HRP) with standby Yes
redundancy
● redundancy procedure STP Yes
● redundancy procedure RSTP Yes
● redundancy procedure RSTP+ Yes
● redundancy procedure MSTP Yes
● Parallel Redundancy Protocol (PRP)/operation in the Yes
PRP-network
● Parallel Redundancy Protocol (PRP)/Redundant Network No
Access (RNA)
● passive listening Yes
protocol / is supported
● LACP Yes
system modification during operation
product function / configuration in RUN via CiR/H-CiR Yes
product functions / security
product function
● IEEE 802.1x (radius) Yes
● broadcast/multicast/unicast limiter Yes
● broadcast blocking Yes
protocol / is supported
● SSH Yes
● SSL Yes
product functions / time
product function

6GK52062GS002AC2 Subject to change without notice


5/24/2024
Page 3/5 © Copyright Siemens
WWTP-045
● SICLOCK support Yes
● NTP-client Yes
● SNTP client Yes
protocol / is supported
● NTP Yes
● SNTP Yes
● IEEE 1588 profile default Yes
standards, specifications, approvals
certificate of suitability
● CE marking Yes
● Regulatory Compliance Mark (RCM) Yes
product conformity / according to EMC-guideline 2014/30/EU
standard
● for EMC interference emission EN 61000-6-4, EN 50121-4
● for immunity to EMC EN 61000-6-2, EN 50121-4
● for safety / from CSA and UL UL 60950-1 E115352, UL-61010-2 E85972
standards, specifications, approvals / hazardous environments
certificate of suitability
● ATEX Yes
● UKEX Yes
● IECEx Yes
● ULhazloc approval Yes
● CCC / for hazardous zone according to GB standard Yes
● FM registration Yes
standards, specifications, approvals / other
certificate of suitability
● railway application in accordance with EN 50121-4 Yes
● RoHS conformity Yes
IT security for industrial automation systems / according to IEC Yes
62443-4-2:2019
standards, specifications, approvals / marine classification
Marine classification association
● American Bureau of Shipping Europe Ltd. (ABS) Yes
● French marine classification society (BV) Yes
● Chinese Classification Society (CCS) Yes
● DNV GL Yes
● Korean Register of Shipping (KRS) Yes
● Lloyds Register of Shipping (LRS) Yes
● Polski Rejestr Statkow (PRS) Yes
● Royal Institution of Naval Architects (RINA) Yes
standards, specifications, approvals / Environmental Product Declaration
Environmental Product Declaration Yes
Global Warming Potential [CO2 eq]
● total 153.7 kg
● during manufacturing 28.4 kg
● during operation 125.2 kg
● after end of life 0.02 kg
product functions / general
MTBF 55 a
reference code
● according to IEC 81346-2 KF
● according to IEC 81346-2:2019 KFE
Warranty period 5a
product function / is supported / identification link Yes; according to IEC 61406-1:2022
further information / internet links
internet link
● to website: Selection guide for cables and connectors https://support.industry.siemens.com/cs/ww/en/view/109766358
● to web page: selection aid TIA Selection Tool https://www.siemens.com/tstcloud
● to website: Industrial communication https://www.siemens.com/simatic-net
● to website: Image database https://www.automation.siemens.com/bilddb
● to website: CAx-Download-Manager https://www.siemens.com/cax

6GK52062GS002AC2 Subject to change without notice


5/24/2024
Page 4/5 © Copyright Siemens
WWTP-046
DKLD?! )6235A 587940123456&!89907% 14UU
DEFGHH? 
0123456789 5 61 584511 593937111 56
!"754#$75 63 2% 58919436 81211 5714&45%'60 ()8"9*
+8"935958,-31754.
/745)67 67
0 $
123456789:8;<7 04$
0 6=7 >0365!813894 657'7854 674
?@4...# A$1982
0%8 8996&8122858'6!?A812 ?A##
:85B2<4
?6579C3%" 6!86,5871C3%" 6# DEFGHH? 
)6235A 467571 0123456789 5 61 584511 5
93937111 56
!"754#$75 63 2% 589
19436 81211 5714&45%'6
0 ()8"9*+8"93595
8,-31754.
)6235'8%79& )IJ)C
)6235/7'&9)/!# )!KL?57= )6235
:8;<79BM4M
 710 7'7)67E63 F F
J 82N38656)67 E63
/745)67 0 $674
345% 6)67 0 $674
03686 '68$!8567894 C1
! 589856 C1
O7P;Q78R9;ST586M4;5S
651569 3985714 ?/LC CL ?GGJ
457%85227485 57% U6,71A8&4# A8&A8&4
C 5U 7 5,# KF
)8,871A7% 1471 GKKVDK
)8,8 47W 3175'% 8436 !
@381575&I175 )8,8
)8,871@381575& 
XBB;4;5SMP9:85B2<49YST586M4;5S
?C GDG
I) DDDKV
%%275&2 KDDGG
/FZ[AH 85890A 0F
)6235E63 K
E632 KK
3156&'6771 )9812
554L%899.7123456&.47% 14.% %8991UU 8589)6235DEFGHH?  
WWTP-047
?".">D? A 18/9654*270A644*59297##
0123456789 5 96789
958517688157 1159859 5789
18846 676318 58 5618!592
8149979 557 997
594579"3951
#$$$%"&"$'()6!9*+68! -1
,456517
$ 0 ../0157112 688157 B960 *-1>.&*&*CDE % " (
1 9897 4511867569
02729 -1 6654649
3456678795:7;<6
=9517 04651586517
9046  *>>**.
9046 > *>>**.
9046 ? *?**.
9046  *>>**
9046 @ *>>**
9046 & *>>**
9046 & *>>**
$)2A  $0?.?
$)2A @ $0?.?
$)2A & $0?.?
2/$ > >?&
'-0  .&**>*?

3""264457059297812"2644"97"##"06641"18"?FG&*++* $ "
WWTP-048
AKHK$I*%; 6!235= 58794'0123456;899'7( 14SS
ABCDE$*'FD*
0123456789 5 61 55812862890  7145899857!1
89"!6!11 57!15!0 #$%"!6317&648934$'!64792 2% 4!92
5 ( 562 97&63175(8)$***( (717(3( !62 6+381575*()
,74567 67
 !-
./012345675894 4!-
 6&7 :3!65;813894 657"7854 674
<4))) =!-19!82
0(8@ @89968122858"!6;'=812 '= 
752>/91
65793( 6;86?5871@3( 6 ABCDE$*'FD*
6!235= 46757!1 0123456789 5 61 55812862
890  
7145899857!189"!6!11 57!15!0 
#$%"!6317&648934$'!6
4792 2% 4!925 ( 56
2 97&63175(8)$***( (717(3( !62 6
+381575*()
6!235"8(79 GD%DEF'$
6!235,7"9,; ;H**I57& 6!235
758946>J1J
 @7!1 7"7676!3K %LDK%LD
F 82+3865667 6!3
,74567  !-674
345!( 667  !-674
3686@ "!68-;8567894 !1
; 58985!6 !1
M4N8O45P68QR253J182Q
!65!156!9 @39857!14 ,IK I
457(85227485 57( S!6?71@=84 D=8K=84
 5S 7@ 5?@ **ADL@
8?8@71@=7( 147!1 D*****TD**
8?8@ 47U 3175!"( 8436 ;
<381575G175 D; 56
8?8@71@<381575 D
;717(3( !62 6+381575 *
V>>8182QJN6752>/916WQR253J182Q
 $*DXDAX$**$TH
G AAA$HDE%EX
!((!275!2 E%$$$X*
,LYZ=[K8589!@0= 0L
6!2356!3 $T
6!3!2 HH
554IKK(899)7123456)47( 14)!(K(899K1KSSK8589!@K6!235KABCDE$*'FD* DK
WWTP-049
"0"A#C/B !5124149$232456B$93%%
01234561815993 19
0193944243
545949131593 411 9549 93
!5124 05124328425"51241
155#9331452155$
24991554253 934594
%&&&'"("&)*+$, .
-94913
&/0/5400124641938151593 238154913
414255349418394
02!325 3149
45677898:6;8<=7
 >5913 09894913
0  ?$ $@$
0 A ?$ $@$
0 ?$ $@$
0 ? ?$ $@$
0 @ ?$ $@$
0 ( ?$ $@$
0 ( ?$ $@$
&+2B ? &00A(
&+2B @ &00A(
&+2B ( &00A(
21&/ A ?
)3 ! 0 C  $$ $(

44""932456931""3"%%"041 "!5124"D>@A$/ "


WWTP-050
Data sheet 6ES7515-2RN03-0AB0

SIMATIC S7-1500R, CPU 1515R-2 PN central processing unit with work memory 1
MB for program and 4.5 MB for data, 1st interface: PROFINET RT with 2-port
switch, 2nd interface: PROFINET, SIMATIC Memory Card required

General information
Product type designation CPU 1515R-2 PN
HW functional status FS04
Firmware version V3.1
● FW update possible Yes
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
● SysLog Yes
Engineering with
● STEP 7 TIA Portal configurable/integrated from version V19 (FW V3.1) / V18 (FW V3.0); with older TIA Portal versions configurable as
6ES7515-2RM00-0AB0
Display
Screen diagonal [cm] 6.1 cm
Control elements
Number of keys 8
Mode buttons 2
Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes
Mains buffering
● Mains/voltage failure stored energy time 5 ms
Input current
Current consumption (rated value) 0.65 A
Current consumption, max. 0.88 A
Inrush current, max. 1.15 A
I²t 0.6 A²·s
Power loss
Power loss, typ. 3.6 W
Memory
Number of slots for SIMATIC memory card 1
SIMATIC memory card required Yes
Work memory
● integrated (for program) 1 Mbyte
● integrated (for data) 4.5 Mbyte
Load memory
● Plug-in (SIMATIC Memory Card), max. 32 Gbyte
Backup

6ES75152RN030AB0 Subject to change without notice


5/22/2024
Page 1/6 © Copyright Siemens
WWTP-051
● maintenance-free Yes
CPU processing times
for bit operations, typ. 20 ns
for word operations, typ. 24 ns
for fixed point arithmetic, typ. 32 ns
for floating point arithmetic, typ. 128 ns
CPU-blocks
Number of elements (total) 8 000; Blocks (OB, FB, FC, DB) and UDTs
DB
● Number range Number range: 1 to 59 999
● Size, max. 4.5 Mbyte; For non-optimized block accesses, the max. size of the DB is 64 KB
FB
● Number range 0 ... 65 535
● Size, max. 1 Mbyte
FC
● Number range 0 ... 65 535
● Size, max. 1 Mbyte
OB
● Size, max. 1 Mbyte
● Number of free cycle OBs 100
● Number of time alarm OBs 20
● Number of delay alarm OBs 20
● Number of cyclic interrupt OBs 20; with minimum OB 3x cycle of 10 ms
● Number of process alarm OBs 50
● Number of DPV1 alarm OBs 3
● Number of startup OBs 100
● Number of asynchronous error OBs 4
● Number of synchronous error OBs 2
● Number of diagnostic alarm OBs 1
Nesting depth
● per priority class 24
Counters, timers and their retentivity
S7 counter
● Number 2 048
Retentivity
— adjustable Yes
IEC counter
● Number Any (only limited by the main memory)
Retentivity
— adjustable Yes
S7 times
● Number 2 048
Retentivity
— adjustable Yes
IEC timer
● Number Any (only limited by the main memory)
Retentivity
— adjustable Yes
Data areas and their retentivity
Retentive data area (incl. timers, counters, flags), max. 512 kbyte; Available retentive memory for bit memories, timers, counters, DBs,
and technology data (axes): 472 KB
Flag
● Size, max. 16 kbyte
● Number of clock memories 8; 8 clock memory bit, grouped into one clock memory byte
Data blocks
● Retentivity adjustable Yes
● Retentivity preset No
Local data
● per priority class, max. 64 kbyte; max. 16 KB per block
Address area
Number of IO modules 4 096; max. number of modules / submodules

6ES75152RN030AB0 Subject to change without notice


5/22/2024
Page 2/6 © Copyright Siemens
WWTP-052
I/O address area
● Inputs 32 kbyte; All inputs are in the process image
● Outputs 32 kbyte; All outputs are in the process image
per integrated IO subsystem
— Inputs (volume) 8 kbyte
— Outputs (volume) 8 kbyte
Subprocess images
● Number of subprocess images, max. 31
Hardware configuration
Number of distributed IO systems 16; A distributed I/O system is characterized not only by the integration of
distributed I/O via PROFINET, but also by the connection of I/O via IE/PB-
Links.
Number of IO Controllers
● integrated 1
Rack
● Modules per rack, max. 5; CPU + 2 PS + 2 CP
Time of day
Clock
● Type Hardware clock
● Backup time 6 wk; At 40 °C ambient temperature, typically
● Deviation per day, max. 10 s; Typ.: 2 s
Operating hours counter
● Number 16
Clock synchronization
● supported Yes
● on Ethernet via NTP Yes
Interfaces
Number of PROFINET interfaces 2
1. Interface
Interface types
● RJ 45 (Ethernet) Yes; X1
● Number of ports 2
● integrated switch Yes
Protocols
● IP protocol Yes; IPv4
● PROFINET IO Controller Yes
● PROFINET IO Device No
● SIMATIC communication Yes; Only Server
● Open IE communication Yes; Optionally also encrypted
● Web server Yes
● Media redundancy Yes
PROFINET IO Controller
Services
— Isochronous mode No
— IRT No
— PROFIenergy Yes; per user program
— Number of connectable IO Devices, max. 64
— Updating times The minimum value of the update time also depends on communication share
set for PROFINET IO, on the number of IO devices, and on the quantity of
configured user data
— PROFINET Security Class 1
Update time for RT
— for send cycle of 1 ms 1 ms to 512 ms
2. Interface
Interface types
● RJ 45 (Ethernet) Yes; X2
● Number of ports 1
● integrated switch No
Protocols
● IP protocol Yes; IPv4
● PROFINET IO Controller No
● PROFINET IO Device No

6ES75152RN030AB0 Subject to change without notice


5/22/2024
Page 3/6 © Copyright Siemens
WWTP-053
● SIMATIC communication Yes; Only Server
● Open IE communication Yes; Optionally also encrypted
● Web server Yes
● Media redundancy No
Interface types
RJ 45 (Ethernet)
● 100 Mbps Yes
● Autonegotiation Yes
● Autocrossing Yes
● Industrial Ethernet status LED Yes
Protocols
PROFIsafe No
Number of connections
● Number of connections, max. 256; via integrated interfaces of the CPU and connected CPs
● Number of connections reserved for ES/HMI/web 10
● Number of connections via integrated interfaces 128
● Number of S7 routing paths 16
Redundancy mode
● PROFINET system redundancy (S2) Yes
● PROFINET system redundancy (R1) No
Media redundancy
— MRP Yes; MRP Automanager according to IEC 62439-2 Edition 2.0
— MRP interconnection, supported Yes; as MRP ring node according to IEC 62439-2 Edition 3.0
— MRPD No
— Switchover time on line break, typ. 200 ms; PROFINET MRP
— Number of stations in the ring, max. 50; Only 16 are recommended, however
SIMATIC communication
● PG/OP communication Yes; encryption with TLS V1.3 pre-selected
● S7 routing Yes
● S7 communication, as server Yes
● S7 communication, as client No
Open IE communication
● TCP/IP Yes
— Data length, max. 64 kbyte
— several passive connections per port, supported Yes
● ISO-on-TCP (RFC1006) Yes
— Data length, max. 64 kbyte
● UDP Yes
— Data length, max. 2 kbyte; 1 472 bytes for UDP broadcast
— UDP multicast Yes; max. 118 multicast circuits
● DHCP No
● DNS Yes
● SNMP Yes
● DCP Yes
● LLDP Yes
● Encryption Yes; Optional
Web server
● HTTP No
● HTTPS Yes; only via Web API
● web API Yes
— Number of sessions, max. 100
— number of simultaneous HTTP calls, max. 4
— HTTP request body, max. 131 072 byte
OPC UA
● Runtime license required Yes; "Medium" license required per CPU
● OPC UA Client No
● OPC UA Server Yes; Data access (read, write, subscribe), method call, custom address space
— Application authentication Yes
— Security policies available security policies: None, Basic128Rsa15, Basic256Rsa15,
Basic256Sha256, Aes128Sha256RsaOaep, Aes256Sha256RsaPss
— User authentication "anonymous" or by user name & password

6ES75152RN030AB0 Subject to change without notice


5/22/2024
Page 4/6 © Copyright Siemens
WWTP-054
— GDS support (certificate management) No
— Number of sessions, max. 24
— Number of subscriptions per session, max. 25
— Sampling interval, min. 250 ms
— Publishing interval, min. 250 ms
— Number of server methods, max. 50
— Number of inputs/outputs per server method, max. 20
— Number of monitored items, recommended max. 2 000; for 1 s sampling interval and 1 s send interval
— Number of server interfaces, max. 10 of each "Server interfaces" / "Companion specification" type and 20 of the
type "Reference namespace"
— Number of nodes for user-defined server interfaces, 30 000
max.
● Alarms and Conditions No
Further protocols
● MODBUS Yes; MODBUS TCP
S7 message functions
Number of login stations for message functions, max. 64
number of subscriptions, max. 500
number of tags/attributes for subscriptions, max. 8 000
Program alarms Yes
Number of configurable program messages, max. 10 000; Program messages are generated by the "Program_Alarm" block,
ProDiag or GRAPH
Number of loadable program messages in RUN, max. 10 000
Number of simultaneously active program alarms
● Number of program alarms 1 000
● Number of alarms for system diagnostics 200
Test commissioning functions
Joint commission (Team Engineering) No
Status block Yes; up to 8 simultaneously
Single step No
Number of breakpoints 8; Breakpoints are only supported in RUN-Solo status
Status/control
● Status/control variable Yes
● Variables Inputs/outputs, memory bits, DBs, distributed I/Os, timers, counters
● Number of variables, max.
— of which status variables, max. 200; per job
— of which control variables, max. 200; per job
Forcing
● Forcing Yes
● Forcing, variables Peripheral inputs/outputs
● Number of variables, max. 200
Diagnostic buffer
● present Yes
● Number of entries, max. 3 200
— of which powerfail-proof 500
Traces
● Number of configurable Traces 4
● Memory size per trace, max. 512 kbyte
Interrupts/diagnostics/status information
Diagnostics indication LED
● RUN/STOP LED Yes
● ERROR LED Yes
● MAINT LED Yes
● STOP ACTIVE LED Yes
● Connection display LINK TX/RX Yes
Supported technology objects
Motion Control No
Controller
● PID_Compact Yes; Universal PID controller with integrated optimization
● PID_3Step Yes; PID controller with integrated optimization for valves
● PID-Temp Yes; PID controller with integrated optimization for temperature

6ES75152RN030AB0 Subject to change without notice


5/22/2024
Page 5/6 © Copyright Siemens
WWTP-055
Counting and measuring Yes
Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -30 °C; No condensation
● horizontal installation, max. 60 °C; Display: 50 °C, at an operating temperature of typically 50 °C, the
display is switched off
● vertical installation, min. -30 °C; No condensation
● vertical installation, max. 40 °C; Display: 40 °C, at an operating temperature of typically 40 °C, the
display is switched off
Ambient temperature during storage/transportation
● min. -40 °C
● max. 70 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see manual
configuration / header
configuration / programming / header
Programming language
— LAD Yes
— FBD Yes
— STL Yes
— SCL Yes
— CFC No
— GRAPH Yes
Know-how protection
● User program protection/password protection Yes
● Copy protection No
● Block protection Yes
Access protection
● protection of confidential configuration data Yes
● Password for display Yes
● Protection level: Write protection Yes
● Protection level: Read/write protection Yes
● Protection level: Write protection for Failsafe No
● Protection level: Complete protection Yes
● User administration Yes
programming / cycle time monitoring / header
● lower limit adjustable minimum cycle time
● upper limit adjustable maximum cycle time
Dimensions
Width 70 mm
Height 147 mm
Depth 129 mm
Weights
Weight, approx. 456 g

last modified: 5/22/2024

6ES75152RN030AB0 Subject to change without notice


5/22/2024
Page 6/6 © Copyright Siemens
WWTP-056
Industrial Automation

G2R-2-SN 24VDC (S)


Relay, plug-in, 8-pin, DPDT, 5 A, mech & LED indicators, label facility, 24 VDC

WWTP-057
Specifications

Mounting method With plug-in socket

Usage General purpose, Interface

Poles 2

Coil voltage 24 V

Rated carry current 5A

Operation voltage DC

Contact material AgSnIn

Contact description DPDT

Features LED, Transparent case, With mechanical indicator

Terminal Plug-in

Fits to

P2RF-08-PU P2RF-08-S
Socket, DIN rail/surface Socket, DIN rail/surface
mounting, 15.5 mm, 8-pin, mounting, 8-pin, screwless
Push-in terminals terminals

G2R-2-SN 24VDC (S) | OMRON EUROPE 2


WWTP-058
4818& &%!4": !&&0124;06 <68=8 799 6
0124 

567689868799
66 86879 86
68 7 77674!"#68
$7767%&
'868# ( !&&
)*+6 0124
5),#-."#/ !0!41 
2*( !+-/(
167 797 6
16+ 4(3
16+-76/ !(1!7
16+7 71,#89 4
56 4
56-76/ &(14&7
0  4(0
0 -76/ (1!!7
#66 !&(43
)6+68986
8966+68986 &367(((3367
 8+68976+68986897666.7
'+68976+689868976 167)6768$968,.7.9
768$96$7 7$8*
7 77 +68976+(7( 467
+%8899 (6 668(8+898=8 =87=96(>+?>6 7 @"1.373"13! 17341!A!A"1304A . !80
WWTP-059
4&&99A4' 99.4B94 C9?15*30 31 59
0123425156189 342 39 8  0
 394 3
 394 9 4
0115  949
 443 342 !"
# 342  3$%0%&'(%)
09344*39+1,'(%)- .%/0'(%)1
09344*39+1,$%0%)- $%0%).2
 313 9,'(%)- 4!
05 923,'(%)- '
49*16669*3412 ,'(%)- 4 5
 313 9,$%0%)- 4!
05 923,$%0%)- '
49*16669*3412 ,$%0%)- 4 5
61189 342 39 89 359 2 9699%0
089 342 39 89 359 2 9 .9642(96309344*39&$%0%"
09344*3910121 43
 42 %+47"7 %9$$08
%9&&%9 $$98.
: 639 689*44*34126
!96412 :*9;*1229*341216*9; 9*166"
*1229*341202992;43<153*1229*31
%2*1398399=549 >96
+5 9181392346 
+5 919396 
+5 91* 842 81423689939 9
+5 918139234689349 
9396*166"*1229*3942392  +1
?%*1229*3412 +1
# 4 (:2
+"52*3412 +1
?%52*3412 +1
?%+52*3412 +1
9* 8 9*125*316,@2!&@7!-;43<9=5 *166"69*3412, 39
*1229*3412-
0166"69*34121*1229*39;49614 92 5
3;1* 8 9;496 
0166"69*34121*1229*39;49614 2 5
3;1* 8 9;496 42
<3386A&&*31 ;94 599*1 &81*3&?15*3?423? 9D68ED69664124F'.%202'612.027GG'241G%6 9&
WWTP-060
0:%; $$$$$$$08<031=32>2658-86*3
01235677358167526999358167173
98273181233732239 !"#
531239!
01235677358167526999358167173
98273181233732239 $!"#
53123917!
01235677358167526999358167173 $!"#
982738653123917!
0123526999358167173 9827386 !"#
531239!
%181678357158
& 6916783983'329167 (39
3269112832179 
)379139 21*8
+3667817* ,767
-,%2817*8
-328115836!.-,%/ $$$01$"22
-223789133-.-,%/ "$%
468*39133-.-,%/ $$4
0123526999358167!.-,%/ %05
012352699935816717!.-,%/ %05
-675862962517*.181675677358167/
-67735816783181675677358167 ,5235677358167
-675862962517*.2835677358167/
639133 $!!$
-35675862 -6773581679351158167 ,5235677358167
+3 961
7$".$2/48
-2699935816762
56758625677358167 1 !
7! $!"#
$#
7617 #
17! 
,82117* ! 
37*8 
123373223 7617

$!
+1*83717* 17! 
86293 !!

-6773581679351158167 ,5235677358167
889:586*!31332!562658>2658>2178>*3!?9@?93991671A%&"-"%0B"-"2066%0"16&B 01
WWTP-061
6-6$2$73, $$859:858;51<12 67072" 5
5 3719 5 
4
0123343567829 21 89 
629 67216299567829  
9289 
89  $
!71889"  $
59"7# 
81559 5115 9289 $

8 9  &
8"#75989" '
721% 5 
'
02995678293568867829 !615 6299567829
5 58(5
)*4+
0123343567829 21
629 67216299567829 8 9



9289 
89  $
!71889"  $
59"7# 
81559 5115 9289 $
&
8"#75989" 89 '
721% 5 
'
089"19"5 
089"19"589 $$
089"3615 , -
029956782961233435678293719 5 
029956782961233435678293719 5 89 
0299567829 81567829 29385
. "572/00124 3
' (512 62995678293 $
!71889"59"7# $
8"#75989"721% 5 '
8"#75989"721% 589 &'
21% 5545 87#5,!5567186 -
3615 18451
 89 815459 51153 2
 89 815459 5115389 
#773766672"58 55162612676<12 67<1897<"5=3>=35338298?35003-@&250-AA3-1&A20@ 261
WWTP-062
')'&45 #6738335"79+95."3
012356758837958 73 758837958
 37588379587537958
 375883795875379588 
 375883795875379586831 
983
 375883795875379586831 
9838
 375883795875379586831
983 9! 33863 "3#$% 
&'
 375883795875379586831
983 9! 33863 "3#$% 
&'8
 375883795875379586831
983 9! 33863 "3#$% 
&'&
 375883795875379586831
983 9! 33863 "3#$% 
&'&8
 375883795875379585753

 375883795875379585753
8
383
( 0 )
98 $*+,&--
 37588379587537958
 375883795875379588 
(98.9
(937537958 
(93/59.3 0
(93#+/59.3 0
(937" 389 &
+" 3899" 3 -
98 $*+,&--
05"3398737758.95$*+ -1
,&--
(932"3 9!98/59.3 20
35 358775873 9!$*+ )
,&--
35"9583/3 91 )

!9924''795.3"3375'2579'35"793 893.392:9358;#*+)<&#+-)==),=&*< ',


WWTP-063
,,%no%pm"j m%%#)0q# 69r&&3_395454&8
013456789454
3566450 
795364536367840 !"#$
7953645363678670 %%"#$
795366&96367840 !"#$
795366&963678670 %%"#$
337560 '"
(&548 60 (
)7&49
-../0.1.234536573463892.:
;<7<=57/8.262>1./
?@7-5<=5-../0.1.234536573463892.:
7A5B/0.8/C38.
7A57/8.262>1./
DEFGH5>/8.262>1./
"**3+4&, 356645,) 75 E<I@J5>/8.262>1./
7365 HK3:L05M/N20./857/8.262>1./
OJHP@;M<Q5>/8.262>1./
?@7-5<=57/8.262>1./
7<5D/>K181.234536573463892.:
-B<R57/8.262>1./
?@7-5L/>K181.2345365>3463892.:
73462891.2345365P.14L18L05<E5STTSTU
VWVXVXUYX
7867 3678)454 7-D5L1.15UU5PB<O
7867 3678)454 Z[\/45<]^P
*&47)454_354& <CK145L1.1
")"` "a"1b$ 7-R5L1.1
#` ")076+3 cP7-D5L1.1
03) 754567 EB;5cD?dcO<5e
P.381N/734L2.2340B/89241KAK3>\0
454&8  71.1K3N[/05245ODfU63891.
g3h3
&4664567
aij  !k
aijk  !k
aij!  !k
aij  !k
 1"`` %klmnlmml%
 1"``m %klmnlmml%
 1"``m %klmnlmml%
 1"``mm %klmnlmml%
 1"``m% %klmnlmml%
 1"``m %kl%'lmlm

h55*p,,454&8 69 &&3,*345,_395_3675_48 s*ts6769u")' '"!'mn) 'kmgmg"'!gn ,


WWTP-064
PSREF
Product Specifications
Lenovo Legion 5 15ACH6H Reference

OVERVIEW

1. E-camera shutter switch 6. HDMI 2.1


2. USB 3.2 Gen 1 7. USB 3.2 Gen 1 (Always On)
3. Ethernet (RJ-45) 8. Power connector
4. USB-C 3.2 Gen 2 9. USB-C 3.2 Gen 2 (data transfer / DP 1.4 only)
5. 2x USB 3.2 Gen 1 10. Headphone / microphone combo jack (3.5mm)

Lenovo Legion 5 15ACH6H - March 22 2022 1 of 7

WWTP-065
PSREF
Product Specifications
Lenovo Legion 5 15ACH6H Reference

Lenovo Legion 5 15ACH6H - March 22 2022 7 of 7

WWTP-066
PSREF
Product Specifications
Lenovo Legion 5 15ACH6H Reference

PERFORMANCE
Processor
Processor Family
AMD Ryzen™ 5 / 7 Processor
Processor**
Base Max Memory
Processor Name Cores Threads Cache Processor Graphics
Frequency Frequency Support
AMD Ryzen 5 3MB L2 / 16MB AMD Radeon™
6 12 3.3GHz 4.2GHz DDR4-3200
5600H L3 Graphics
AMD Ryzen 7 4MB L2 / 16MB AMD Radeon
8 16 3.2GHz 4.4GHz DDR4-3200
5800H L3 Graphics

Operating System
Operating System**
• Windows® 11 Pro 64
• Windows 11 Home 64
• Windows 10 Pro 64
• Windows 10 Home 64
• No operating system

Graphics
Graphics**[1]
Graphics Type Memory Boost Clock TGP Key Features
NVIDIA® GeForce RTX™ 6GB 1425 MHz / Advanced Optimus, Resizable BAR, Dynamic
Discrete 130W
3060 Laptop GPU GDDR6 1702 MHz Boost 2.0, VR ready, DirectX® 12 Ultimate
NVIDIA GeForce RTX 8GB Advanced Optimus, Resizable BAR, Dynamic
Discrete 1560 MHz 130W
3070 Laptop GPU GDDR6 Boost 2.0, VR ready, DirectX 12 Ultimate

Notes:
1. Free-Sync via integrated graphics; G-Sync via discrete graphics

Monitor Support
Monitor Support
Supports up to 4 independent displays (native display and 3 external monitors via HDMI® and USB-C®)
• HDMI supports up to 7680x4320@60Hz
• USB-C supports up to 5120x3200@60Hz

Chipset
Chipset
AMD SoC (System on Chip) platform

Memory
Max Memory[1]
Up to 32GB DDR4-3200 offering
Memory Slots
Two DDR4 SO-DIMM slots, dual-channel capable
Memory Type
DDR4-3200

Notes:
1. The max memory is based on the test results with current Lenovo® memory offerings. The system may support more memory as the
technology develops.

Storage

Lenovo Legion 5 15ACH6H - March 22 2022 2 of 7

WWTP-067
PSREF
Product Specifications
Lenovo Legion 5 15ACH6H Reference

Storage Support[1]
Up to two drives, 2x M.2 SSD
• M.2 2242 SSD up to 512GB
• M.2 2280 SSD up to 1TB
Storage Type***
Disk Type Interface RPM Security
M.2 2242 SSD PCIe® NVMe®, PCIe 3.0 x4 - -
M.2 2280 SSD PCIe NVMe, PCIe 3.0 x4 - -

Notes:
1. The storage capacity supported is based on the test results with current Lenovo storage offerings. The system may support larger
storage as the technology develops.

Removable Storage
Optical
None
Card Reader
No card reader

Multi-Media
Audio Chip
High Definition (HD) Audio, Realtek® ALC3306 codec
Speakers
Stereo speakers, 2W x2, Nahimic Audio
Microphone
Dual array microphone
Camera
HD 720p, with E-camera shutter, fixed focus

Battery
Battery**
• Integrated Li-Polymer 60Wh battery, supports Rapid Charge Pro (charge up to 50% in 30min)
• Integrated Li-Polymer 80Wh battery, supports Rapid Charge Pro (charge up to 50% in 30min)
Max Battery Life[1]
• MobileMark® 2018: 7 hr (60Wh)
• MobileMark 2018: 9.2 hr (80Wh)

Notes:
1. All battery life claims are approximate maximum and based on results using the MobileMark 2014, MobileMark 2018, JEITA 2.0,
continuous 1080p video playback (with 150nits brightness and default volume level) or Google Power Load Test (PLT) battery-life
benchmark tests. Actual battery life will vary and depends on many factors such as product configuration and usage, software use,
wireless functionality, power management settings, and screen brightness. The maximum capacity of the battery will decrease with
time and use.

Power Adapter
Power Adapter**[1]
• 230W slim tip (3-pin) AC adapter, 100-240V, 50-60Hz
• 300W slim tip (3-pin) AC adapter, 100-240V, 50-60Hz

Notes:
1. AC adapter offerings depend on the country.

DESIGN
Display

Lenovo Legion 5 15ACH6H - March 22 2022 3 of 7

WWTP-068
PSREF
Product Specifications
Lenovo Legion 5 15ACH6H Reference

Display**[1]
Aspect Contrast Color Viewing
Size Resolution Touch Type Brightness Surface Key Features
Ratio Ratio Gamut Angle
FHD Anti- 45% Refresh rate 120Hz, Free-
15.6" None IPS 250 nits 16:9 800:1 170°
(1920x1080) glare NTSC Sync, DC dimmer
Refresh rate 165Hz,
FHD Anti- 100% Dolby® Vison, Free-Sync,
15.6" None IPS 300 nits 16:9 1000:1 170°
(1920x1080) glare sRGB DC dimmer, Advanced
Optimus support
FHD Anti- 100% Refresh rate 60Hz, Free-
15.6" None IPS 300 nits 16:9 1200:1 170°
(1920x1080) glare sRGB Sync, DC dimmer
Refresh rate 165Hz, Dolby
WQHD Anti- 100%
15.6" None IPS 300 nits 16:9 1000:1 178° Vision™, Free-Sync, G-
(2560x1440) glare sRGB
Sync, DC dimmer
Touchscreen
Non-touch

Notes:
1. California Electronic Waste Recycling Fee
In California, per state law, Lenovo charges an electronic waste recycling fee on this covered device at the time of sale of the product.
For more information, go to https://www.calrecycle.ca.gov/Electronics/Consumer

Input Device
Keyboard**
• Phantom blue model: 6-row, multimedia Fn keys, numeric keypad, black keycap
• Stingray model: 6-row, multimedia Fn keys, numeric keypad, moon white keycap
Keyboard Backlight**
• Blue backlight
• White backlight
• 4-Zone RGB backlight
Touchpad
Buttonless Mylar® surface multi-touch touchpad, 69 x 104 mm (2.72 x 4.09 inches)

Mechanical[1]
Dimensions (WxDxH)
362.56 x 260.61 x 22.5-25.75 mm (14.27 x 10.26 x 0.89-1.01 inches)
Weight
2.4 kg (5.3 lbs)
Case Color**
• Phantom blue (top), shadow black (bottom)
• Stingray (top), dove grey (bottom)
Surface Treatment
Painting
Case Material
PC + ABS (top), PC + ABS (bottom)
System Lighting
No system lighting

Notes:
1. The system dimensions and weight vary depending on configurations.

CONNECTIVITY
Network
Lenovo Legion 5 15ACH6H - March 22 2022 4 of 7

WWTP-069
PSREF
Product Specifications
Lenovo Legion 5 15ACH6H Reference

Onboard Ethernet
Gigabit Ethernet, 1x RJ-45
WLAN + Bluetooth®**[1][2]
• 802.11ac 2x2 Wi-Fi® + Bluetooth 5.1, M.2 Card
• Wi-Fi 6, 802.11ax 2x2 Wi-Fi + Bluetooth 5.1, M.2 card

Notes:
1. Bluetooth 5.2 is hardware ready but may run at a lower version due to OS limitation
2. Wi-Fi 6 full features might be limited by country-level restrictions.

Ports[1]
Standard Ports
• 3x USB 3.2 Gen 1
• 1x USB 3.2 Gen 1 (Always On)
• 1x USB-C 3.2 Gen 2 (support data transfer and DisplayPort™ 1.4)
• 1x USB-C 3.2 Gen 2 (support data transfer, Power Delivery and DisplayPort 1.4)
• 1x HDMI 2.1
• 1x Ethernet (RJ-45)
• 1x Headphone / microphone combo jack (3.5mm)
• 1x Power connector

Notes:
1. The transfer speed of following ports will vary and, depending on many factors, such as the processing speed of the host device, file
attributes and other factors related to system configuration and your operating environment, will be slower than theoretical speed.
USB 2.0: 480 Mbit/s;
USB 3.2 Gen 1 (SuperSpeed USB 5Gbps, formerly USB 3.0 / USB 3.1 Gen 1): 5 Gbit/s;
USB 3.2 Gen 2 (SuperSpeed USB 10Gbps, formerly USB 3.1 Gen 2): 10 Gbit/s;
USB 3.2 Gen 2x2 (SuperSpeed USB 20Gbps): 20 Gbit/s;
Thunderbolt™ 3/4: 40 Gbit/s

SECURITY & PRIVACY


Security
Security Chip
Firmware TPM 2.0 integrated in SoC
Fingerprint Reader
No fingerprint reader
BIOS Security
• Power-on password
• Supervisor password
• Hard disk password
Other Security
E-Camera shutter

SERVICE
Warranty
Base Warranty**[1]
• 1-year depot service
• 1-year depot with 2-year system board service (Korea only)
• 2-year (1-yr battery) depot service
• 3-year (1-yr battery) depot service

Notes:
1. More information of warranty policy, please access https://pcsupport.lenovo.com/warranty

ENVIRONMENTAL
Lenovo Legion 5 15ACH6H - March 22 2022 5 of 7

WWTP-070
PSREF
Product Specifications
Lenovo Legion 5 15ACH6H Reference

Operating Environment
Temperature[1]
• At altitudes up to 2438 m (8,000 ft)
- Operating: 5°C to 35°C (41°F to 95°F)
- Storage: 5°C to 43°C (41°F to 109°F)
• At altitudes above 2438 m (8,000 ft)
- Maximum temperature when operating under the unpressurized condition: 31.3°C (88°F)
Humidity
• Operating: 8% to 95% at wet-bulb temperature 23°C (73°F)
• Storage: 5% to 95% at wet-bulb temperature 27°C (81°F)
Altitude
Maximum altitude (without pressurization): 3048 m (10,000 ft)

Notes:
1. When you charge the battery, its temperature must be no lower than 10°C (50°F).

ACCESSORIES
Bundled Accessories
Bundled Accessories
• Lenovo Legion™ M300 RGB Gaming Mouse (USB connector)
• None

CERTIFICATIONS
Green Certifications
Green Certifications
• ErP Lot 3
• RoHS compliant

• Feature with ** means that only one offering listed under the feature is configured on selected models.

• Feature with *** means that one or more offerings listed under the feature could be configured on selected
models.

• Lenovo reserves the right to change specifications or other product information without notice. Lenovo is not
responsible for photographic or typographical errors. LENOVO PROVIDES THIS PUBLICATION “AS IS,”
WITHOUT WARRANTY OF ANY KIND, EITHER EXPRESS OR IMPLIED, INCLUDING THE IMPLIED WARRANTIES
OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some jurisdictions do not allow
disclaimer of express or implied warranties in certain transactions, therefore this disclaimer may not apply to
you.

• The specifications on this page may not be available in all regions, and may be changed or updated without
notice.

Lenovo Legion 5 15ACH6H - March 22 2022 6 of 7