P09 Manual
P09 Manual
P09 Manual
Installation Manual
Firmware version # - V1.18
CONTENTS
Section 1 – Overview................................................................................................................................. 3
1.1 Introduction................................................................................................................................... 3
Section 2 – Installation and Wiring............................................................................................................ 4
2.1 Introduction................................................................................................................................... 4
2.2 Initial Inspection........................................................................................................................... 4
2.3 Operating Environment................................................................................................................. 4
2.4 Installation Location..................................................................................................................... 5
2.5 Mounting Procedures................................................................................................................... 5
2.6 Wiring Procedures........................................................................................................................ 5
2.6.1 INCOMING POWER WITH DISTRIBUTION SYSTEM........................................................... 5
2.6.2 OUTGOING POWER WITH DISTRIBUTION SYSTEM.......................................................... 6
2.6.3 INCOMING/OUTGOING POWER WITHOUT DISTRIBUTION PANEL BOARD..................... 6
2.6.4 INCOMING RTD WIRING...................................................................................................... 7
2.6.5 CONNECTING THE RS-485 DEVICE NETWORK................................................................. 7
2.7 Connections for Remote Annunciation..................................................................................... 12
2.8 RS-232, RS-485, or Ethernet Remote Port Connections to a Host Computer......................... 14
2.8.1 RS-232 SERIAL CONNECTIONS........................................................................................ 14
2.8.2 RS-485 SERIAL CONNECTIONS........................................................................................ 14
2.8.3 ETHERNET CONNECTIONS............................................................................................... 14
2.9 Testing the nVent RAYCHEM NGC-30 System.......................................................................... 15
Section 3 – nVent RAYCHEM NGC-30 Components and Operation......................................................... 16
3.1 User Interface Terminal (NGC-UIT)............................................................................................ 16
3.1.1 MULTIPLE NGC-UIT MODELS............................................................................................ 16
3.1.2 NGC-UIT LOCAL AND REMOTE NETWORK CONNECTIONS............................................ 16
3.1.3 NGC-UIT LED STATUS........................................................................................................ 18
3.1.4 CONFIGURATION SWITCHES............................................................................................ 18
3.1.5 NGC-UIT RESET SWITCH................................................................................................... 18
3.2 Card Rack Module (NGC-30-CRM/-CRMS) and Current Transformer
Module (NGC-30-CTM).............................................................................................................. 19
3.3 Card Rack (NGC-30-CR)............................................................................................................. 20
3.4 Voltage Monitoring Module (NGC-30-CVM) – Optional........................................................... 20
3.5 Remote Monitoring Module (RMM2) – Optional...................................................................... 21
3.6 Power Line Carrier Interface Module (PLI) – Optional............................................................. 22
Section 4 – Appendices........................................................................................................................... 23
Appendix A – Replacement Component Ordering Guide............................................................... 23
Appendix B – Panel Specifications.................................................................................................. 24
Appendix C – NGC-30-CRM/-CRMS Specifications........................................................................ 27
Appendix D – NGC-UIT2 Specifications.......................................................................................... 28
Appendix E – Device Address.......................................................................................................... 30
2 | nVent.com
SECTION 1 – OVERVIEW
1.1 INTRODUCTION
The nVent RAYCHEM NGC-30 is a fully wired and tested control and monitoring system used
with electric heat tracing. This manual provides information pertaining to the installation,
operations, testing, adjustment, and maintenance of all components of the RAYCHEM NGC-30.
For information about how to program the RAYCHEM NGC-30, see the RAYCHEM NGC-30
Programming Guide (H58186)
A typical RAYCHEM NGC-30 is made up of at least a nVent RAYCHEM User Interface Terminal
(NGC-UIT), one Card Rack (NGC-30-CR), one Card Rack Module with connectors
(NGC-30-CRM or NGC-30-CRMS), and one Current Transformer Module (NGC-30-CTM).
Optional nVent RAYCHEM Remote Monitoring Module (RMM2), Power Line Carrier Interface
(PLI) and Voltage Monitoring Module (NGC-30-CVM) may be used.
The information in this document coincides with the specific releases of firmware
(listed in Table 1.1.) for the User Interface Terminal (NGC-UIT) and Card Rack Module
(NGC-30-CRM/-CRMS) components. As nVent releases new firmware to significantly modify
or enhance any of these components, new documentation will accompany these releases.
To ensure that the correct documentation is being used for your particular version of the
RAYCHEM User Interface Terminal (NGC-UIT), compare the firmware version number of each
component against the number listed in the table below. As subsequent changes are made,
supplements to this document will be included in manuals shipped after the firmware is
released. Supplements will make specific reference to the operation or functional change.
Copies of this manual and updates may be downloaded from the Literature section of
nVent.com
Table 1.1 Component versions
Component Version number
NGC-CRM/CRMS V1.0X
NGC-UIT V1.1X
RMM2 V1.0X
nVent.com | 3
SECTION 2 – INSTALLATION AND WIRING
2.1 INTRODUCTION
WARNING:
Electrical Hazard! Ensure all personnel involved in installation, servicing, and programming are
qualified and familiar with electrical equipment, their ratings, and proper practices and codes.
Multiple voltages and signal levels may be present during the installation, operation, and
servicing of this product. Do not power the product until the safety provisions outlined in this
section have been observed.
This section includes information regarding the initial inspection, preparation for use, and
wiring instructions for the components of the RAYCHEM NGC-30.
4 | nVent.com
2.4 INSTALLATION LOCATION
The wide Operating Temperature of the RAYCHEM NGC-30 permits installation in almost
any convenient location. Considerations should include: expected atmospheric conditions
(weather), accessibility for maintenance and testing, the location of existing conduits, and
hazardous location rating. Ambient temperature conditions may affect load current ratings.
CAUTION:
Always be sure that the intended location is classified as an area that the product is approved
for use in as defined by Article 500 of the National Electrical Code and/or Part I, Section 18 of
the Canadian Electrical Code.
ØA ØB ØC Main circuit
breaker
3-pole
Panelboard
neutral bus
Panelboard
ground bus
nVent.com | 5
2.6.2 OUTGOING POWER WITH DISTRIBUTION SYSTEM
Load Power Terminal Blocks
Locate the outgoing heater terminal blocks using the supplied elevation/layout drawing, and
connect per the associated schematic drawings. Depending upon the size of the branch circuit
breaker and voltage loss calculations, use the appropriate size and number of wires to connect
from the panel’s Load Power Terminal Blocks to the heat-trace power junction box.
TB*
CRM
X CTM
connector TB- (Y)
Cable-CT**
13
14
15
16
17
LP
L2 *–L2 *–T2 T2
Fig. 2.3 Single pole and two pole circuit breaker wiring diagrams
6 | nVent.com
2.6.4 INCOMING RTD WIRING
Nonhazardous and Hazardous Location Installations Wired to Terminal Block in Panel
The nVent RAYCHEM RTD wiring from the NGC-30-CRM/-CRMS have been pre-wired to
RTD terminals. The field RTD wiring (3-wire with shield) will be terminated by the installer at the
RTD terminal blocks. Refer to the Installation Drawings for the RTD Termination Schedule.
See Fig. 2.4 on page 8 for a typical RTD installation.
Note: To meet the requirements for hazardous location installations, a separate RTD terminal
block must be installed and wired to the NGC-30-CRM/-CRMS RTD terminal connector.
nVent.com | 7
Device must be mounted in series. Branching of the network is not allowed.
(Terminated devices are shown in gray) Connect no more than two RS-485 cables to any device.
RMM2
PLI
NGC-UIT S2 0 S1
6
6 0-9
110
.
220
.
S + S +
36
S
H N/H G A B C N Norm Mixed
NGC-UIT
NGC-
NGC-UIT
NGC-CRM/-CRMS
nVent
MSB LSB
TB 1 TB 2 TB 3 TB 4 TB 5
1 2 3
TB 19
TB 12 TB 7 TB 6
TB 13 TB 14 TB 15 TB 16 TB 17
NGC-CRM/-CRMS
NGC-CRM/-CRMS MSB LSB
MSB LSB
TB 1 TB 2 TB 3 TB 4 TB 5
1 2 3
TB 19
TB 12 TB 7 TB 6
TB 13 TB 14 TB 15 TB 16 TB 17
TB 1 TB 2 TB 3 TB 4 TB 5
1 2 3
TB 19
TB 12 TB 7 TB 6
TB 13 TB 14 TB 15 TB 16 TB 17
NGC-CRM/-CRMS
PLI
MSB LSB
S2 0 S1
6
6 0-9
TB 1 TB 2 TB 3 TB 4 TB 5
1 2 3
TB 19
TB 12 TB 7 TB 6
TB 13 TB 14 TB 15 TB 16 TB 17
110
.
220
.
S + S +
36
S
H N/H G A B C N Norm Mixed
NGC-CRM/-CRMS
RMM2 Jumper
MSB LSB
TB 1 TB 2 TB 3 TB 4 TB 5
1 2 3
TB 19
TB 12 TB 7 TB 6
TB 13 TB 14 TB 15 TB 16 TB 17
In order for the nVent RAYCHEM RS-485 network to work properly, you must enable the
termination resistor for the first and last device. The devices shown in gray in Fig. 2.5 represent
the devices for which you must enable the termination resistors. The devices that are not grayed
out represent the devices for which you should not enable the termination resistors.
8 | nVent.com
Optional RMM2 Installed in the Field
Refer to the nVent RAYCHEM RMM2 Installation Instructions (H56848) for field installation
instructions. You must connect a RS-485 connection from the RMM2 to an open nVent
RAYCHEM RS-485 connector on the NGC-30-CRM/-CRMS board in the RAYCHEM NGC-30
panel. To make this connection, a pre-wired terminal block has been provided in the RAYCHEM
NGC-30 panel. Connect the RS-485 wire from the RMM2 to TB (per the panel drawing) while
maintaining the correct polarity. If the RMM2 is the first or last device in the RS-485 network,
connect the J17 termination jumper to pins 1 and 2.
If the RMM2 is not the first or last device in the RS-485 network, connect the J17 termination
jumper to pins 2 and 3.
NGC-30 Panel
5
* Reference panel drawing for terminal block number
4
TB*
S 3 1 1 1 1
S
4
S
S S S S S
+ + + +
(+) 2 2 2 2 2 5 BK
BK BK BK BK BK BK
– – – –
(–) 1 3 3 3 3 6 WH
WH WH WH WH WH WH
TB* TB* TB* TB*
RS-485 RS-485 NGC-30-CRM/-CRMS #8 RS-485
NGC-UIT NGC-30-CRM/-CRMS #1
RMM2
Jumper
RS-485
J17
0
1 2 3
Fig. 2.6 RMM2 RS-485 field wiring and termination jumper setting
nVent.com | 9
Optional PLI Installed in the Panel
Refer to the PLI Installation Instructions (H56850). You must connect a RS-485 connection
from the PLI to an open RS-485 connector on the NGC-30-CRM/-CRMS board in the RAYCHEM
NGC-30 panel. IF the PLI is the first or last device in the RS-485 network, remove the shorting
block jumper location J2 from 1 and 2 and place it across pins 2 and 3.
NGC-30 Panel
9
S2 5 S1
6 5
110
.
220
RS-485 connections
.
S + – S + –
S 3 1 1 1 1 36
S S S S S S
H N/H G A B C N Norm Mixed
+ +
(+) 2 2 2 2 2
BK BK BK BK BK
(–) 1 – –
3 3 3 3
WH WH WH WH WH
TB* TB* TB* TB*
RS-485 RS-485
NGC-UIT NGC-30-CRM/-CRMS #1 NGC-30-CRM/-CRMS #8 RS-485
J2
1 2 3
Default position (for all PLI Termination mode
units in network except first or last one) (first or last PLIin network)
J2 J2
1 2 3 1 2 3
Last PLI in network
Fig. 2.7 PLI RS-485 panel wiring and termination jumper setting
NGC-UIT Installation
The nVent RAYCHEM NGC-UIT-ORD and NGC-UIT-OUT will come pre-wired into any NGC-30 panel.
Exceptions exist when a remote mount NGC-UIT (NGC-UIT-ORD-12) is used or the NGC-30 panel
is wired to the NGC-UIT in another panel. Fig. 2.8 shows the wiring for the NGC-30-ORD-12 and
Fig. 2.10 shows the wiring between a separate panel and the NGC-UIT.
NGC-UIT-ORD-12 Installation
You must make an RS-485 connection from the NGC-UIT-ORD-12 to the NGC-30-CRM/-CRMS
board in the NGC-30 panel. To make this connection, a pre-wired terminal block has been
provided in the NGC-UIT-ORD-12 and in the NGC-30 panel. Connect the RS-485 wire from TB3
in the NGC-UIT-ORD-12 and the other end to TB* in the NGC-30 panel maintaining the correct
polarity. If the NGC-UIT-ORD-12 and/or the NGC-30-CRM/-CRMS is the first or last device in the
RS-485 network, see Fig. 2.9 and Table 3.2 for details on how to terminate the RS-485 network.
* Reference panel drawing for terminal block numbers.
10 | nVent.com
NGC-UIT-ORD-12
1 2 3 4 5 1 2 3 4 5 6 7 8 9 1 2 3 4 5 6
FU1
HHNN
– +
Grounding bar
RS-485
TB*
3 1 1 1 1
S S S S S
+ + + +
BK
2 BK
2 2 2 2
BK BK BK
– – – –
WH
1 WH
3 3 3 3
WH WH WH
TB* TB* TB* TB*
The following figure shows the RS-485 termination options for the NGC-30-CRM/-CRMS.
NGC-30-CRM/-CRMS
MSB LSB
TB 1 TB 2 TB 3 TB 4 TB 5
1 2 3
TB 19
TB 12 TB 7 TB 6
TB 13 TB 14 TB 15 TB 16 TB 17
NGC-30 Panel #1
6
* Reference panel drawing for terminal block number
5
4
TB*
S 3 1 1 1 1
S
4
S
S S S S S
+ + + +
(+) 2 2 2 2 2 5 BK
BK BK BK BK BK BK
– – – –
(–) 1 3 3 3 3 6 WH
WH WH WH WH WH WH
TB6 TB6 TB6 TB6
RS-485 RS-485
NGC-UIT NGC-30-CRM/-CRMS #1 NGC-30-CRM/-CRMS #8 RS-485
RS-485
NGC-30 Panel #2
without UIT installed
TB*
1 1 1 1 1
S S S S S
+ + + +
BK
2 BK
2 2 2 2
BK BK BK
– – – –
WH
3 WH
3 3 3 3
WH WH WH
TB6 TB6 TB6 TB6
RS-485 RS-485
NGC-30-CRM/-CRMS #1 NGC-30-CRM/-CRMS #8
Fig. 2.10 RS-485 field wiring between two RAYCHEM NGC-30 panels
NGC-UIT Relay 1
12 | nVent.com
The NGC-UIT has two other Form C alarm relays (configurable through the NGC-UIT program)
for external alarms. Each relay can be connected to an annunciator light or distributed control
system. Each relay’s contacts have been wired from the NGC-UIT to a terminal block in the
panel.
NGC-UIT Relay 2
Non-energized Energized without an Energized with an
alarm condition alarm condition
UIT-R2-NO TB* UIT-R2-NO TB* UIT-R2-NO TB*
5 5 5
6 6 6
7 7 7
UIT-R2-NC UIT-R2-NC UIT-R2-NC
6 6 6
NGC-UIT Relay 3
11 11 11
UIT-R3-NC UIT-R3-NC UIT-R3-NC
9 9 9
Note: An energized relay with no alarm condition will change state with loss of power or an
alarm condition.
nVent.com | 13
2.8 RS-232, RS-485, OR ETHERNET REMOTE PORT CONNECTIONS TO A HOST COMPUTER
The NGC-UIT can communicate with a distributed control system (DCS) or other host
computer through the NGC-UIT external communication ports. The NGC-UIT provides ports for
RS-232, RS-485, and Ethernet communication. All of these communication ports provide data
read access. However, only one port can be assigned read/write access. This is done using the
NGC-UIT.
2.8.1 RS-232 SERIAL CONNECTIONS
The RS-232 port can be used as a direct connection to a single PC located within 50 feet of the
panel. (Refer to Fig. 2.13 on page 15). For an RS-232 connection, a 3-foot long RJ11 to 9-pin
female D-connector (NGC-UIT-232, part number: 10332-005) has been provided with the
NGC-UIT. Plug the RJ11 connector into the RS-232 connector on the NGC-UIT and the other end
into the 9-pin male connector on the user’s computer.
PC Laptop
10/100
1 2 3 4 5 6 Ethernet 1 2 3 4
9-pin
male
RS-232 9-pin
Shield
Shield
SIG +
SIG +
SIG –
SIG –
(DCE) female
Local Relay 1
Field Remote
3-foot RJ11 to
9-pin female D connector
NGC-30 Panel
PC
TB*
6 3
S S
+ + RS-485 Converter
5 BK
2 BK
–
1
– 9-pin
4
WH WH male
S 3 RS-485 9-pin
S
female
(+) 2
BK
(–) 1 To NGC-30-CRM/-CRMS
WH
14 | nVent.com
Network node
10/100
1 2 3 4 5 6 Ethernet 1 2 3 4
RS-232
Shield
Shield
SIG +
SIG +
SIG –
SIG –
(DCE)
Local Relay 1
Field Remote
Ethernet cable
3. Confirm all NGC-30-CRM/-CRMS, RTDs and/or RMM2s and PLI modules have been scanned
into the Network database.
4. If a device or an RTD is installed but does not show up in the Network | Devices Screen,
turn the power off to the system and:
For Devices:
a. Confirm the device has a unique address (refer to section 3.2 on page 21)
b. Confirm the device is being powered
c. Confirm the RS-485 connection is in place with the correct polarity (refer to section 2.6.5)
For RTDs:
a. Confirm the RTD connection is in place with the correct polarity
b. Perform a resistance check of the RTD. The resistance should be in a range of
70–250 ohms
Turn the power on to all devices (NGC-30-CRMs/-CRMSs and optional RMM2s & PLI) and the
NGC-UIT. Once the NGC-UIT has booted up to the Main screen, Go to the Network | Device
Screen and press “Update Network.” Confirm all NGC-30-CRM s/-CRMSs, RTDs, and/or
RMM2s and PLI modules have been scanned into the Network database.
nVent.com | 15
SECTION 3 – RAYCHEM NGC-30 COMPONENTS AND OPERATION
The RAYCHEM NGC-30 heat-trace system is comprised of a number of modular components,
allowing the ultimate in design flexibility. This section describes the NGC-30 control and
monitoring components (excluding the optional distribution section). Appendix B, C, and D
includes the specifications for these components.
Fig. 3.1 Typical NGC-UIT model showing NGC-UIT-ORD-12 remote user interface terminal
The physical dimensions of each NGC-UIT model vary; the dimensions of the NGC-UIT-ORD-12
shown in the figure are the largest of all NGC-UITs:
• Width: 15" (381 mm)
• Height: 11.8" (300 mm)
• Depth: 6.1" (155 mm)
NGC-UIT LCD Touch-Screen Display
Each NGC-UIT has a 5 ¾ inch x 3 ¼ inch (14.61 cm X 8.26 cm) LCD color display with touch-
screen technology that provides an user interface easy and efficient programming with no
keyboards or cryptic labels.
3.1.2 NGC-UIT LOCAL AND REMOTE NETWORK CONNECTIONS
The NGC-UIT communicates to both a local field network and optionally to a remote
monitoring and control network.
16 | nVent.com
Local Field Network Connection
The local field network always uses an RS-485 serial connection running over shielded twisted-
pair cable. This network is used to connect the NGC-UIT to its control and monitoring modules:
• RAYCHEM Mechanical Contactors Controller - NGC-30-CRM
• RAYCHEM Solid State Relay Controller - NGC-30-CRMS
• RAYCHEM Current Transformer Module Controller - NGC-30-CTM
• RAYCHEM Voltage Monitoring Module - NGC-30-CVM
• RAYCHEM Remote Monitoring Module - RMM2
• RAYCHEM Power Line Carrier Interface Module - PLI
The local field network must follow configuration rules about topology and termination of
network end devices.
Remote Monitoring and Control Network Connection
The remote monitoring and control network communicates via a selectable network
connection port using either RS-485, RS-232, or 10/100Base-T Ethernet. This network is
used to connect to multiple NGC-UIT systems and communicate with a central PC running
RAYCHEM Supervisor software. The RAYCHEM Supervisor software provides centralized
status and alarm monitoring, data logging, and remote configuration control over all attached
NGC-UIT systems in the network. The remote monitoring and control network must also follow
configuration rules about topology and termination of the network end devices.
Side View
TX RX Field
TX RX Local/Remote
1 2 Output
relays
3
USB Status
Reset
USB
Front view
ON OFF TERM R-Field
Side view
10/100
1 2 3 4 5 6 Ethernet 1 2 3 4 5 6 7 8 9 10 11 1 2 3
Line/L1
RS-232
Shield
Shield
SIG +
SIG +
SIG –
SIG –
N/L2
(DCE)
Local Relay 1 Relay 2 Relay 3
Field Remote
Bottom view
nVent.com | 17
3.1.3 NGC-UIT LED STATUS
The LED Status lights are located on the side of the NGC-UIT. Refer to Table 3.1
for LED functions.
Table 3.1 LED Status Light Functions
Field Local/Remote
State Status USB RX TX RX TX Relays
TX RX Field
TX RX Local/Remote OFF No power No USB key No activity No activity No activity No activity Relay in
detected NO position
1 2 Output
relays Normal USB key Flicker on Flicker on Flicker on Flicker on Relay
3 Green
operation* inserted* receipt of transmission receipt of transmission energized
USB Status
data packet of data data packet of data contacts in
packet packet NC position
USB Status
TX
TX
1
3
USB Status
Reset Reset
USB
ON
USB ON
ON
18 | nVent.com
3.2 CARD RACK MODULE (NGC-30-CRM/-CRMS) AND CURRENT TRANSFORMER MODULE (NGC-30-CTM)
Each Card Rack Module (NGC-30-CRM and NGC-30-CRMS) and Current Transformer Module
(NGC-30-CTM) provide ground-fault and line current sensing, alarming, switching, and RTD
input for five Loops. The NGC-30-CRM is used with electromechanical relays. The
NGC-30-CRMS is used with solid-state relays. The NGC-30-CRM/-CRMS may be connected to
one User Interface Terminal (NGC-UIT).
Each NGC-30-CRM/-CRMS must have a unique communication address. The valid address
switch range for the NGC-UIT is 1–99. SW1 is the ones digit (0–9) and SW2 is the tens digit
(0–9). See Fig. 3.3.
Note: RMM2s use ModBus addresses 32 through 47 and PLIs use Modbus addresses 1-99.
When using RMM2s and PLI modules in an NGC-30 system, care must be taken to not assign
the same addresses to an RMM2, PLI module or an NGC-30-CRM/-CRMS board.
MSB LSB
3
SW2 SW1
Note: When adding an NGC-30-CRM/-CRMS to the system, power must be cycled to the board and a
network update on the NGC-UIT must be performed.
NGC-30-CRM/-CRMS 10
MSB LSB
9
TB 1 TB 2 TB 3 TB 4 TB 5
1 2 3
TB 19
TB 12 TB 7 TB 6
TB 13 TB 14 TB 15 TB 16 TB 17
1 2 3 4 5 6 7 8
Each NGC-30-CRM/-CRMS has a cluster of nine LED lights to advise the status of the board.
Number 3 in Fig. 3.4 shows the location of the LED lights.
nVent.com | 19
Table 3.3 LED Display
LED function LED description LED color
Relay 1
Relay 3
Power
Alarm Energized upon Alarm Red
Tx
Power Energizes upon power to unit Green
Relays 1, 2, 3, 4, 5 Energizes upon relay closed Red
RX & TX Energizes upon received and Amber
transmit of RS-485 data
Alarm
Relay 2
Relay 4
Relay 5
Rx
LED functions
20 | nVent.com
3.5 REMOTE MONITORING MODULE (RMM2) – OPTIONAL
The RAYCHEM Remote Monitoring Module (RMM2) provides additional temperature
monitoring capabilities. Each RMM2 accepts up to eight RTDs that measure pipe, vessel, or
ambient temperatures. The RMM2 can be installed in the RAYCHEM NGC-30 enclosure or
can be located in the field to reduce RTD field wiring.The RAYCHEM NGC-30 system supports
260 temperature inputs via the CRM/CRMs boards. Sixteen (16) RMM2s can be connected
via a single, twisted pair RS-485 cable to provide up to 128 additional RTD inputs into the
RAYCHEM NGC-30 system.
0
0
nVent.com | 21
3.6 POWER LINE CARRIER INTERFACE MODULE (PLI) – OPTIONAL
The RAYCHEM Power Line Carrier Interface Module (PLI) together with RAYCHEM temperature
transmitters provides remote temperature monitoring capability. The PLI module receives input
from temperature transmitters over the power wires for the heat-tracing circuits, which carry
the signals from special transmitters. The transmitters provide pipe temperatures from RTDs
and continuity confirmation. Per PLI module, the NGC-30 system can accept up to
127 temperature inputs from SES's/SPCs or 255 temperature inputs from 700-TTs.
Up to four PLIs can be connected to one NGC-30 UIT.
Set the RS-485 address for the PLI module using the rotary switches provided. Note the
orientation of the clear plastic cover, then remove the cover. Use a slotted screwdriver to rotate
the selector switches to the appropriate positions to select the RS-485 address. Each PLI
module must have a unique address, if two PLI modules, CRM or RMM are assigned the same
address, communication faults will result. The PLI module switch setting can be set from 1-99
0-9 0-9
110
.
220
RS-485 connections
.
S + – S + –
36
S
H N/H G A B Norm Mixed
22 | nVent.com
SECTION 4 – APPENDICES
Replacement Components
Description Catalog Number Part Number
User Interface Terminal NGC-UIT-ORD 10332-001
- Nonhazardous (Unclassified) Locations/Indoors
- Panel Mounting
User Interface Terminal with NEMA 12 Enclosure NGC-UIT-ORD-12 10332-008
- Nonhazardous (Unclassified) Locations/Indoors
- Remote Mounting
User Interface Terminal NGC-UIT-OUT 10332-003
- Hazardous Locations/Outdoors
- Panel Mounting
UIT Adaptor Cable NGC-UIT-232 10332-005
Card Rack Module (CRM) (for EMRs) NGC-30-CRM 10720-001
Card Rack Module (CRMS) (for SSRs) NGC-30-CRMS 10720-004
Current Transformer Module (CTM) NGC-30-CTM 10720-002
Card Rack (CT) NGC-30-CR 10720-003
Voltage Monitoring Module NGC-30-CVM 10720-005
Remote Monitoring Module RMM2 051778
Remote Monitoring Module(RMM2-4X) with NEMA 4X RMM2-4X 523420
Enclosure
Power Line Carrier Interface Module PLI 488323
nVent.com | 23
APPENDIX B – PANEL SPECIFICATIONS
Panel Specifications
Table B.1 Panel Specifications
General
Area of use NGC-30-EMR for nonhazardous locations
NGC-30-EMR with Z purge for hazardous locations
NGC-30-SSR for hazardous locations
Approvals Áreas no peligrosas Áreas peligrosas (versión depurada de EMR) Áreas peligrosas (versión SSR)
ETL EN LISTA ETL EN LISTA ETL EN LISTA
CUMPLE CON CUMPLE CON CUMPLE CON
ANSI/UL STD. 508 ANSI/UL STD. 508 UL STD 508A
UL STD. 508A UL STD. 508A 9700701 ANSI/ISA STD 12.12.01
9700701 9700701
CERTIFICADO A
CERTIFICADO A CERTIFICADO A CSA STD C22.2 NO. 213
CAN/CSA C22.2 NO. 14 CAN/CSA C22.2 NO. 14 CSA STD C22.2 NO. 14
ETL EN LISTA
CUMPLE CON
NFPA STD 496
9700701
Supply voltage 100 – 240 Vac, +5% / –10%, 50/60 Hz common supply for controller and
heat-tracing circuit
Up to 600 Vac for heat-tracing circuit when controller is powered from a separate circuit
Enclosure
Protection/materials NEMA 12 (indoors painted steel)
NEMA 4/3R (outdoors, painted steel)
NEMA 4X/3RX (outdoors, stainless steel)
Operating Temperature Without distribution: –13°F to 140°F (–25°C to 60°C)
Below –13°F (–25°C), space heater and thermostat must be used
With distribution: 14°F to 140°F (–10°C to 60°C)
Below 14°F (–10°C), space heater and thermostat must be used
Storage Temperature –40°F to 167°F (–40°C to 75°C)
Relative humidity 0% to 90%, noncondensing
Control
Control points The RAYCHEM NGC-30 system can control up to 260 circuits.
Relay types 3-pole, electromechanical (EMR versions)
1-, 2-, or 3-pole solid-state relays (SSR versions)
Voltage, maximum 240 Vac nominal, 50/60 Hz (standard), 600 Vac nominal (optional)
Current, maximum per circuit* EMR: 30 A @ 104°F (40°C) or 60 A @ 104°F (40°C)
* Depending on panelboard amperage SSR: 30 A @ 104°F (40°C) or 60 A @ 104°F (40°C)
rating, the maximum current may not be
used on all circuits.
Control algorithms EMR: On/Off, Ambient on/off, PASC (proportional ambient sensing control)
SSR: On/Off, Ambient on/off, PASC (proportional ambient sensing control),
Proportional (includes soft start for all SSR control modes)
Control range –99°F to 900°F (–73°C to 482°C)
Dead band 1°F to 50°F (1°C to 50°C) (On/Off control only)
24 | nVent.com
Monitoring
Temperature
Low alarm range –99°F to 900°F (–73°C to 482°C) or OFF
High alarm range –99°F to 900°F (–73°C to 482°C) or OFF
Ground fault
Alarm range 10 mA to 200 mA
Trip range 10 mA to 200 mA or OFF
Current
Low alarm range 0 A to 100 A (where 0 equals OFF)
High alarm range 0 A to 100 A (where 0 equals OFF)
Voltage 100 – 277 Vac supply voltage to heat-tracing
(Note: Requires the loss of one circuit)
Autocycle Each loop can be programmed from 1 to 1000 hours or OFF
nVent.com | 25
Connection Terminals
Heating cable output Screw terminals, 20–6 AWG (30 A versions), 14–2 AWG (60 A versions)
Ground 14–4 AWG ground bar
RTD / alarm / communications 28–12 AWG spring clamp terminals
26 | nVent.com
APPENDIX C – NGC-30-CRM/-CRMS SPECIFICATIONS
nVent.com | 27
APPENDIX D – NGC-UIT2 SPECIFICATIONS
General
Approvals NGC-UIT2-ORD
Áreas no peligrosas
LR67275
NGC-UIT2-ORD-R
Áreas no peligrosas
28 | nVent.com
UIT status Three colors showing system status: Green = Normal condition
Red = Fault condition
Yellow = Loading software/configuration
LCD Display
Display LCD is a 6.5 inch QVGA, color TFT transflective device with integral CCFL backlight.
(For use indoors or when protected from direct sunlight)
Touch screen 4-wire resistive touch-screen interface for user entry. Usable with gloved fingers
nVent.com | 29
APPENDIX E – DEVICE ADDRESS
30 | nVent.com
North America Europe, Middle East, Africa Asia Pacific Latin America
Tel +1.800.545.6258 Tel +32.16.213.511 Tel +86.21.2412.1688 Tel +1.713.868.4800
Fax +1.800.527.5703 Fax +32.16.213.604 Fax +86.21.5426.3167 Fax +1.713.868.2333
[email protected] [email protected] [email protected] [email protected]
nVent.com
©2018 nVent. All nVent marks and logos are owned or licensed by nVent Services GmbH or its affiliates. All other trademarks are the property of their respective owners.
nVent reserves the right to change specifications without notice.
Raychem-IM-H57878-NGC30-EN-1805
NGC-30
Programming Guide
Document #H57402
NGC System
2 NGC-30 PROGRAMMING GUIDE
Table of Contents
Section 1 – Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1 DigiTrace® NGC-30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1.1 Product Overview. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1.2 Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1.3 Monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
1.1.4 Ground-Fault Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1.5 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1.6 Communications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1.7 Complete System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.1.8 The NGC-30 Operation Manual. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
1.2 Vital Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.3 License Agreement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
1.3.1 DigiTrace® NGC-30 Software – License Agreement . . . . . . . . . . . . . . . . . . . . . . . 7
1.4 User Responsibilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.5 Safety Warnings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.6 Warning, Error, and Alarm Messages. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.7 Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
1.8 Navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
1.8.1 Navigating Between Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Section 2 – Basic Configuration Quick Start. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.1 An Example of a Simple 4 Loop Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.2 Setting Up Additional Loops . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.3 Loops 1–4 Setup Complete Confirmation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.4 Starting NGC-30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.4.1 System Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
2.4.2 Initial Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Section 3 – Full Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.1 Initial Displays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.1.1 Main Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
3.2 Software Organization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
3.3 NGC-30 Screens – Detailed Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.3.1 Setup Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.3.2 Main Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
3.3.3 Setup|Loop Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
3.3.4 Control Modes Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
3.3.5 Setup|RTDs Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
3.3.6 Setup|Temp Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3.3.7 Setup|Ground-Fault Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
3.3.8 Setup |Current Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
3.3.9 Setup|PASC Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
3.3.10 Setup|Maint. Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3.3.11 Status|Loop Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
3.3.12 Status|RTDs Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
3.3.13 Status|PASC Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
3.3.14 Status|Min/Max Screen. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
3.3.15 Status |Maint. Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
3.3.16 Events Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
3.3.17 Network|Devices Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
3.3.18 Network|Relays Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
3.3.19 Network|RTDs Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
3.3.20 Network|Maint. Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
3.3.21 Network|Remove Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
3.3.22 System|Misc Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
3.3.23 System|Filters Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
3.3.24 System|Relays Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
3.3.25 System|Comm Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
The DigiTrace® NGC-30 is a multi-circuit electronic control, monitoring and power distribution
system for heat-tracing used in process-temperature maintenance and freeze-protection appli-
cations. The NGC-30 system can control up to 260 circuits with multiple networked panels. Each
panel can control up to 40 individual heat-tracing circuits and monitor up to 128 temperature
inputs, with optional power distribution. The NGC-30 is available with two output types: an Elec-
tromechanical Relay (EMR) or a Solid-State Relay (SSR). Both types allow circuit switching up
to 60 amps at 600 Vac with single or three-phase power. Up to four Resistance Temperature
Detector (RTD) sensor inputs for each heater circuit allow for a variety of combinations of tem-
perature control, monitoring, and alarming. Systems can be configured for nonhazardous and
hazardous areas. The ability to monitor and configure the controller is available both locally and
remotely with the DigiTrace Supervisor™ software.
NGC-30
Panel
Field located
NGC-UIT
RMM2
iTrace
Dig
To next
RMM2
RS-485
1.1.2 CONTROL
The DigiTrace NGC-30 measures temperatures with 3-wire, 100-ohm platinum RTDs connected
directly to the unit, or through optional Remote Monitoring Modules (RMM2). Each RMM2 accepts
up to eight RTDs. The RMM2s are typically located near the desired measurement location (RTDs).
Multiple RMM2s are networked over a single cable to the NGC-30, significantly reducing the cost
of RTD field wiring. The NGC-30 system supports 260 temperature inputs via the CRM/CRMS
boards. Using RMM’s an additional 128 temperature inputs can be supported for a maximum of
388 temperature inputs. With EMRs and SSRs, the NGC-30 can be configured for On/Off, ambient
sensing, and proportional ambient sensing modes. Additionally, with SSRs, the panel can be con-
figured for proportional, power limiting, and soft start modes.
1.1.3 MONITORING
The DigiTrace NGC-30 can measure up to 12 control parameters including ground-fault, temper-
ature, and current variables to ensure system integrity. Configurable alarm settings provide
options for local or remote alarms. The system can be set to periodically check for heating cable
National electrical codes require ground-fault equipment protection on all heat-tracing circuits.
Heat-tracing circuits equipped with DigiTrace NGC-30 controllers do not require additional
ground-fault detection equipment, simplifying installation and reducing costs.
1.1.5 INSTALLATION
The DigiTrace NGC-30 system is configured with a User Interface Terminal (UIT) that has an LCD
color display with touch screen technology. This UIT provides an easy user interface for pro-
gramming without keyboards or cryptic labels. However, the specific UIT provided will depend
on the location of NGC-30 panel. If the panel is located in a nonhazardous, indoor location, the
NGC-UIT-ORD is installed locally (on the panel door). On the other hand, if the panel is located in
a hazardous, or outdoor location, the NGC-UIT-ORD-12 is mounted remotely in a nonhazardous,
indoor location. See Table 1.1 below.
NEMA 4X-P
(outdoors, mechanical relays
with Z purge option)
* Hazardous areas are defined by Article 500 of the National Electrical Code and Section 18 of
the Canadian Electrical Code.
1.1.6 COMMUNICATIONS
The NGC-30 units can be networked to a host PC running Windows®-based DigiTrace Supervi-
sor client-server software for central programming, status review, and alarm annunciation. NGC-
30 units support the ModBus™ protocol and are available with an RS-232, RS-485 or 10Base-T
Ethernet communication interface.
The NGC-30 is supplied as a complete system ready for field connections of power wiring and
temperature sensor input. Optional Power Distribution further enhances the reduction of field
wiring and labor to install.
This NGC-30 Programming Guide assists in the set up and operation of the DigiTrace NGC-30
system.
The NGC-30 Software, which is installed in the NGC-UIT (User Interface Terminal), is a Windows CE®-
based software application designed to configure various DigiTrace devices. This software ver-
sion supports the NGC-30 Heat Tracing Panels using NGC-30-CRM/-CRMS (5GF-C) card rack
modules with or without multiplexed RTD inputs via the DigiTrace RMM2.
Periodic updates to the NGC-UIT software may be available for download from www.tycother-
mal.com. Users should verify the software version of the unit being installed and update to the
most current version. Instructions for uploading will be included within the update download.
Tyco Thermal Controls’ only obligations are those in the Tyco Thermal Controls Standard Terms
and Conditions of Sale for this product, and in no case will Tyco Thermal Controls or its distrib-
utors be liable for any incidental, indirect, or consequential damages arising from the sale,
resale, use, or misuse of the product. Specifications are subject to change without notice. In
addition, Tyco Thermal Controls reserves the right to make changes—without notification to
Buyer—to processing or materials that do not affect compliance with any applicable specification.
This agreement is a legal agreement between you, “the end user” and Tyco Thermal Controls,
LLC (“Tyco Thermal Controls”). BY INSTALLING OR OTHERWISE ACCESSING THIS PROGRAM,
YOU ARE AGREEING TO BECOME BOUND BY THE TERMS OF THIS AGREEMENT. IF YOU DO
NOT AGREE TO THE TERMS OF THIS AGREEMENT, DO NOT INSTALL OR ACCESS THIS PRO-
GRAM. IF INSTALLING OR OTHERWISE ACCESSING THIS PROGRAM BY OPENING A SEALED
DISK PACKAGE, PROMPTLY RETURN THE UNOPENED DISK PACKAGE AND THE OTHER ITEMS
(INCLUDING WRITTEN MATERIALS OR OTHER CONTAINERS) TO THE PLACE WHERE YOU
OBTAINED THEM.
1. GRANT OF LICENSE. The DigiTrace NGC-30 Software (the “Software”) is licensed, not
sold, to you for use only under the terms of this Agreement, and Tyco Thermal Controls
reserves any rights not expressly granted to you. Subject to the terms and conditions of
this Agreement, Tyco Thermal Controls grants to you a non-exclusive, nontransferable, lim-
ited license (without the right to sublicense others) to use the one copy, including written
materials if any, of the Software on a single computer at the location (company and
address) to which Tyco Thermal Controls issued this copy of the DigiTrace NGC-30 Soft-
ware. The Software is owned by Tyco Thermal Controls LLC and is protected by United
States copyright laws and international treaty provisions. All copies made by you are sub-
ject to the terms and conditions of this Agreement. The structure, organization and code of
the Software are valuable trade secrets and confidential information of Tyco Thermal Con-
trols. You agree not to modify, alter, merge, adapt, duplicate, distribute, translate, decom-
pile, disassemble, reverse engineer, create derivative works, copy for use on any other
computer or at any other location, or otherwise make this software available to any person
or entity outside this location. The Software is licensed only to you. In no event may you
transfer, sell, sublicense, rent, assign or transfer rights, lease, or otherwise dispose of the
Software on a temporary or permanent basis without the prior written consent of Tyco
Thermal Controls. You agree to use reasonable efforts to protect against the unauthorized
YOU FURTHER AGREE THAT REGARDLESS OF ANY STATUTE OR LAW TO THE CON-
TRARY, ANY CLAIM OR CAUSE OF ACTION ARISING OUT OF OR RELATED TO USE OF THE
SOFTWARE OR THE TERMS AND CONDITIONS MUST BE FILED WITHIN ONE (1) YEAR
AFTER SUCH CLAIM OR CAUSE OF ACTION AROSE OR BE FOREVER BARRED.
Should you have any questions concerning this Agreement, or if you desire to contact
Tyco Thermal Controls for any reason, please write to:
The top row of the screen contains the main menu buttons, and the bottom row contains sub-
sets of those main menu buttons.
When asked to navigate between screens in this manual, simply press a combination of a Main
Menu|Submenu buttons.
For example in Step 1, the System |Misc screen must be accessed. To perform this action, press
the System button on the top row. On the bottom row, press the Misc button.
On Setup and Status screens, a Status legend displays. This information shows what Device
address and Relay address have been assigned to a particular Loop.
Main
Menu
Navigational
Header
Shortcut: If a Loop number is associated with an Event or Alarm, selecting it automatically sends
you to that Loop’s Status/Loop screen. This will help in troubleshooting.
When in the Main or Events/Alarms screens, press on any data field for a Loop to see the Status
screen for that Loop.
Navigational Header
At the top of the Setup and Status screens, a navigational header displays the following data
(from left to right):
A. Loop Number (27)
B. Loop’s ID tag (Boiler Feed Line)
C. Relay output device address (01)
D. Relay output number (3)
The following gives an overview of how to implement a simple 4 Loop system. For greater detail,
please go to Section 3.
This is the first screen that appears when the program loads.
Press “Update Network” and confirm all that NGC-30-CRM/-CRMS (5GF-C) and/or RMM2s have
been scanned into the Network database.
At first start-up, the program scans for the Device Addresses for the NGC-30-CRM/-CRMS
(5GF-C) and RMM2, and a database is created. Once the database exists, no further scanning is
done. A device address is the number assigned via the rotary switches on the NGC-30-CRM/-
CRMS (5GF-C) or RMM2 board. See the DigiTrace NGC-30 Installation Manual (H57878) for
more information.
For this example, the only device address found is 1 (an NGC-30-CRM board), with four RTDs
installed at positions 1, 2, 3 and 4. (RTD #5 was not installed; therefore it is not listed).
• The pop-up window is a text-editing screen that works similar to cell phone text messaging.
There are selection keys for Upper Case Letters, Lower Case Letters, and Special Characters.
The keypad portion allows you to enter text by pushing the appropriate keys.
• A numeric entry pop-up window appears. Type in the device address (in this case, 1) for this
Loop and press Enter. (See page 27 for more on device addresses.)
Step 4D continued: This screen shows the pop-up window prior to any Relay assignment
• Press on the word “Available” to the right of #1 to assign Relay 1 as the output device for
Loop 1.
Note: The screen will always display which Relays are still available on this device for Loop
assignment.
• Press Enter.
Step 4E: Press on the Mode field and a pop-up window appears, showing all available con-
trol modes
• This pop-up window lets you select a Loop’s basic operating mode. The NGC-30-CRM (5GF-
C), used in this example, has the following Control modes available: On/Off, Always On,
Always Off, PASC, and Voltage.
• Press On/Off to select this control mode and return to the Setup Loop screen.
• Pressing the Fail Safe toggle button alternates the Fail Safe mode between Power Off and
Power On. This selection tells the NGC-30-CRM/-CRMS (5GF-C) if the heater should be
turned on or off if all of the RTD(s) for this Loop fail.
• If the main concern is to prevent pipes from freezing, then Power On is a good choice. How-
ever, if the heater is oversized and overheating is a concern, then Power Off could be a better
choice.
• The NGC-30 program first checks to see if the default RTD is available. On any NGC-30-CRM/
-CRMS (5GF-C) board, the first RTD input is automatically coupled with the first relay output;
the second RTD is linked with the second output relay, etc.
• Here an RTD has been connected to the RTD 1 terminal block, so the RTD set-up screen
indicates the default assignment is already completed.
• There are three blank slots available so you can assign additional RTDs to this output relay.
You may desire additional RTDs if you need a more exact temperature sampling for a
temperature-sensitive fluid. If you assign additional RTDs, the lowest RTD value from the list
will be used for control temperature.
• See page 30 and page 45 for information on how to set up additional RTDs. For this simple
Loop Quick Start example, the default set-up RTD is used.
• Input the Setpoint, Dead Band, High Temp Alarm, and Low Temp Alarm by pressing on each
of the four numeric windows in turn.
• Input the Ground Fault Current Alarm and Ground Fault Current Trip by pressing each of the
two numeric windows in turn.
• For this example, the Ground Fault Current Alarm and Ground Fault Current Trip levels are set
to 20 mA and 30 mA respectively.
– At less than 20 mA, the NGC-30 program takes no action. At 20 mA or more leakage, an
alarm is indicated and logged to the Events List.
– At 30 mA the output relay assigned to this Loop is tripped off.
WARNING: Fire Hazard. A ground-fault alarm means the heating cable has been damaged or
improperly installed and must not be ignored. Disabling the ground-fault trip function reduces
safety and could result in sustained electrical arcing or fire. To minimize the risk of fire if the
alarm activates, shut off the power and repair the system immediately.
Note: Setting 0 for both High and Low Current Alarms completely deactivates the Current Alarm
function.
• Input Power Limit – This input is enabled only when SSR control devices are detected
(NGC-30-CRMS panel). A Power Limit setting less than 100% will limit the “on-time” of a
constant wattage heater to the percentage indicated in the entry window. This has the effect
of lowering the amount of power that the heater can produce.
• By default, once you program a Loop, it immediately begins to control the heater based on
the input information.
• If you do not want this Loop to activate until all Loops are programmed, go to Setup|Loop
screen and press the Enabled toggle button once, which then takes the Loop Disabled. To
re-Enable, press the Disable button.
The NGC-30 software is designed to run only on the DigiTrace NGC-UIT hardware platform. Prior
to shipment, the NGC-30 software is installed into a nonvolatile area of the UIT memory. During
the initial power-up, you will see a blue background “splash” screen for approximately 30 sec-
onds as the system software is loaded and initializes. The NGC-30 program runs automatically
beginning with a scan for all connected sensing and control devices.
Verify that all of the expected hardware has been found by checking the Network|Devices
display. If a device appears to be missing, manually initiate a new scan by pressing the Network
Update button. If an expected device does not appear on the list after several scans, it is most
likely physically disconnected from the RS-485 network wiring, or is not powered. Troubleshoot
and verify all network and power.
Note: If a new external hardware device is added after the initial power-up scan, you must initiate
a manual scan by going to the Network|Devices screen and pressing the “Network Update” button.
After the first system scan has been completed, the main screen appears.
Channel
LC
Local GF
1 Output
RTD Relay 1
LC
Local GF
2 Output
RTD Relay
LC
Local GF
3 Output
RTD Relay
LC
Local GF
4 Output
RTD Relay
LC
Local GF
5 Output
RTD Relay
LC = Line current
NGC-30-CRM/-CRMS Board GF = Ground fault
The NGC-30 software can manage up to 260 Loops similar to that depicted above. The control
Loop concept is not limited to the simple arrangement shown above. Multiple input Loops and
“monitor only” Loops are possible as depicted on the following page.
Channel
LC
Local/A GF
1 Output
RTD Relay 1
LC
Local GF
2 Output
RTD Relay
LC
Local GF
3 Output
RTD Relay
LC
Local GF
4 Output
RTD Relay
LC
Local GF
5 Output
RTD Relay
NGC-30-CRM/-CRMS
NGC-UIT Board
RS-485 LC = Line current
GF = Ground fault
B #1
C 2
D 3
4
Additional RTDs
5
6
7
8
RMM2
Fig. 3.4 Multiple input control loop
RS-485
B #1
C 2
D 3
4
5
6
7
8
RMM2
To input any device address, the NGC-30-CRM/-CRMS (5GF-C), RTDs and optional RMM2 must
be connected and powered during startup of the NGC-30 program. The program scans for the
device number(s) on the network during startup. The Network|Devices screen will list all the
device address(es) found. The addresses listed are the only device addresses that the program
recognizes as valid.
If a device is added after the NGC-30 program has started, go to the Network screen and select
“Network Update.”
Each device must have a unique device address number. For example, if the design requires both
NGC-30-CRM and RMM2s, and 32 is chosen for device address number for the NGC-30-CRM,
then the RMM2 cannot also use address 32. (See Available Device Address Table on page 43 for
device address restrictions).
The main screen displays the status of all Loops that have been setup. For each Loop, the main
screen displays:
Note: A Configuration Spreadsheet has been developed to assist in the collection of specific
circuit (loop) details. This spreadsheet is located in Appendix E.
Loop entry window The Loop # is assigned when setting up a Loop in the NGC-30 program. It
is the primary reference for all screens. Once a Loop is added, you cannot change its Loop
number; however you can delete the loop (except for Loop 1). This window is also where you
can select an existing Loop.
If a relay output has been assigned to the Loop, the relay output turns on or off based upon
set-up parameters and RTD inputs, and the selected control mode.
Delete action button Deletes the Loop that is currently being displayed and removes it from the
main screen. Any Loop can be deleted EXCEPT for Loop 1. The program asks for confirmation
before deleting.
ID Entry Window The Loop ID is a tag that the user can define. The default is “ID xxx” (where
xxx is the Loop number).
Limit: 40 characters (character strings are truncated on the Main Screen after 16 characters but
displayed in full on Status and Setup screens)
Relay Output Section This section defines the device/relay and the operating mode assigned to
the Loop.
Device Address Entry Window The device address is the number assigned to a NGC-30-CRM/-
CRMS (5GF-C) board via the rotary selector switches. Each NGC-30-CRM/-CRMS (5GF-C) must
be assigned a unique number (no other device can share a device address whether it’s a Relay
Output device or RTD input device). All device addresses are scanned on initial startup. If
devices are added after initial startup, the user must perform a system re-scan. (See
Network|Devices screen, see page 43).
Device Address Range: 0–99 (See Network|Devices screen, page 43 for specific limits)
Note: If no device address is entered (0), the Loop is limited to temperature-monitoring and
temperature- alarming only.
Relay Number Entry Window The relay number defines which of the 5 control channels on the
NGC-30-CRM/-CRMS (5GF-C) board controls the heater’s switching device. When the display
shows dashes (---) rather than an address, no switching device has been assigned to the Loop.
Mode Entry List The modes are the various control schemes that control a Loop. There are four
different control modes associated with a NGC-30-CRM panel plus one voltage monitoring
mode, and five with a NGC-30-CRMS panel plus one voltage monitoring mode.
On/Off
The NGC-UIT monitors the control temperature and compares it to the setpoint. If the control
temperature is above the setpoint by more than the Dead Band value (see page 27) the relay out-
put is turned off. If the control temperature falls below the setpoint temperature, the output is
turned on. The control temperature is defined as the lowest RTD temperature input value for that
Loop.
Proportional
This algorithm monitors the control temperature of the Loop and compares it to the setpoint
temperature. If the control temperature is at or below the setpoint temperature, then power is
applied to the heater with a duty cycle of 100%. If the control temperature is equal to or greater
than the control setpoint temperature +4°F, then the relay output will have a duty cycle of 0%.
The control temperature is constantly monitored, and the output duty cycle is adjusted propor-
tionally once per second. See Appendix A for additional information on Proportional Control.
Soft-Start Feature
This feature is a time-ramped soft start that reduces surge current produced by heaters at star-
tup. When a solid state output relay is first turned on, the duty cycle is ramped from 0 to 100%
in 2.5% (25 millisecond) increments over a 40 second period. The update rate for each step is
fixed at 1 second.
This automatic feature is included only when using SSRs as an output device. It is incorporated
into all control modes (On-Off, Proportional, PASC, Always On). If an output has been off for
more than 10 minutes, the soft-start algorithm will reset and be activated the next time the SSR
turns on. The soft-start algorithm will also reactivate whenever the NGC-30-CRMS boards loses
power or is reset.
The NGC-30-CRM/-CRMS (5GF-C) has a control algorithm that uses the measured ambient tem-
perature, desired maintain temperature, minimum ambient temperature assumption used during
design, and size of the smallest pipe diameter to calculate how long the heater should be on or
off to maintain a near-constant pipe temperature.
Always On
The relay output is switched on (user override), turns on the power to the heater and leaves it on.
Note: Monitor the pipe temperatures to avoid overheating. Alarms are still active.
Always OFF
The relay output is switched off (user override), turns off the power to the heater, and leaves it
off.
Note: Monitor the pipe temperatures for low temperature alarms. Alarms are still active.
Monitor Only
This is the default mode that allows temperature monitoring for the Loop. This means no output
device has been selected.
When the sensor for control is returned to service, the NGC-30 controller signals the alarm has
been cleared, returns the Loop to its normal control mode, and records both of these events.
By default, each channel of the NGC-30-CRM/-CRMS (5GF-C) has an associated RTD input. On
any NGC-30-CRM/-CRMS (5GF-C) board, the first RTD input is automatically coupled with the
first relay output; the second RTD is linked with the second output relay, etc.
The Setup|RTDs screen displays the default relay assignment in the Local/A window (as shown
in Figure 3.9). This selection is grayed out because you cannot alter this default selection. In the
event of a communications failure or UIT failure, the Loop reverts to this default RTD for control
purposes.
In general, up to three additional RTDs can be associated with this Loop. When the system is
fully functional, the lowest RTD value from the list of four will be used for control temperature.
If no RTD is connected to the input terminals for this Loop, then all four lines can be used to
assign RTDs from elsewhere in the system. However, in the event of a communications or UIT
failure, no RTD input is available and the relay output for this Loop goes to the failsafe mode
established in the Setup|Loop screen.
Example: Loop 1 is assigned Relay Output 1-1, and an RTD is plugged into the number 1 slot.
This screen contains all temperature parameters for control and monitoring of Loops.
Setpoint Entry Window Use with On/Off, Proportional, and PASC control modes. The Setpoint
is the desired maintain temperature.
Based on the measured control temperature, the NGC-30 switches the relay output to maintain
the system at the desired set point.
Range: –99°F (–72°C) to 900°F (482°C)
Default: 50°F
Dead Band Entry Window Use with On/Off Control.
If the control temperature is above the Setpoint temperature plus Dead Band, the relay output is
turned off. If the control temperature is below the Setpoint temperature, the output is turned on.
Range: 1°F (1°C) to 50°F (50°C)
Default: 5°F
This screen configures ground fault alarm and trip values for the Loop. These alarms are latch-
ing alarms and must be reset.
If the Ground Trip is disabled, the relay output will continue to function normally but without
ground fault safeguards.
WARNING: Fire Hazard. A ground-fault alarm means the heating cable has been damaged or
improperly installed and must not be ignored. Disabling the ground-fault trip function reduces
safety and could result in sustained electrical arcing or fire. To minimize the risk of fire if the
alarm activates, shut off the power and repair the system immediately.
This screen configures the current alarm values for Loops. The high current is a latching alarm
and requires user action to reset.
Power Limit Entry Window Use with SSR (DigiTrace NGC-30-CRMS) only
This feature limits the average power available at the output, by allowing the user to set a
maximum duty cycle for the Loop.
Note: The heater is switched on and off over a time base of several seconds. For example, an
80% power output is achieved by switching the heater on at 100% for 8 seconds then off for 2
seconds. Instantaneous power consumption is not limited when the heater is on.
Range: 10–100%
Default: 100%
This screen configures the PASC setup if the PASC control mode is selected for a Loop.
IMPORTANT: If improperly used, the Power Adjust parameter can cause the piping to get too
cold or too hot. If unsure, leave at 100%. Do not change this value unless an engineer calculates
the temperature impact on the system and determines that it is safe to do so. Be particularly
cautious if the circuit has more than one diameter of pipe or type of heat tracing. Contact a Tyco
Thermal Controls representative for assistance with this factor.
Range: 10–200%
Default: 100%
Relay Cycle Alarm Entry Window (For EMR type devices only)
This entry is used to create a contactor inspection maintenance schedule. Enter the number of
times that contactors can be cycled on/off before inspection and testing is desired. The NGC-30
UIT tracks the accumulated number of on/off switches for each contactor and generates an
alarm message to advise that contactor maintenance is due.
Range: 1–10,000,000
Note: The heater “on” time and contactor cycle count alarm thresholds established on this
screen are global values that apply to all heaters and contactors controlled by this NGC-UIT unit.
However, you can maintain the count of heater hours or contactor cycles for each Loop indepen-
dently. Alarm messages are generated for each Loop on an individual basis. If a heater or con-
The status loop screen displays the status information for individual Loops. Data in the status
menus cannot be changed; it is informational only.
The data in the Control Temp, G.F. and Current windows are displayed in color to identify their
state:
ID Window
Displays the ID tag defined in Setup/Loop screen.
Relay Window
Displays the Relay device and number defined in the Setup/Loop screen.
G.F. Window
Displays the ground-fault current for the Loop.
Current Window
Displays the heater amperage of the Loop when the relay output is on.
Mode Window
Displays the Control Mode selected in Setup|Loop screen.
Note: A special voltage monitoring mode is available with the use of the optional NGC-30-CVM
(voltage monitoring module). When the module is installed and the mode selection is Voltage,
the Status|Loop screen shows the supply voltage as seen below.
The Status|RTD screen lists the RTD devices and numbers assigned to the selected Loop, along
with the last reported temperature from each RTD.
The Status|PASC screen displays the current status of Loop switching PASC algorithm. Data
displayed in this status screen cannot be changed.
On Count
The duration (in seconds) an EMR or SSR is on during one on/off cycle.
Off Count
The duration (in seconds) an EMR or SSR is off during one on/off cycle.
This screen displays an historical record of minimum and maximum values recorded since the
last Reset time. Data in this status screen is “read-only” information. Pressing reset releases all
values and starts another period of accumulation for minimum or maximum values.
Reset Button
Immediately resets all Min/Max values and begins updating Min./Max. fields with new values.
This screen displays the cumulative time in hours the heater has been On and the number of
cycles the EMR has turned on and off for the selected Loop. Data displayed in the counter
windows is read only. Pressing the Reset buttons resets the appropriate counter.
The Events screen displays a chronological history of all events and alarms. It retains the most
recent 2000 entries; after 2000 entries are recorded, the oldest entries are discarded as new
entries are added.
This screen summarizes the device addresses and resources (output devices/ relays and RTD
inputs) that have been found by the system and can be used for setup.
Note: The first scan for resources occurs automatically when power is first applied and the
results are saved in memory. If expected devices or RTDs are not discovered on the first scan,
Update Network can be pressed as many times as desired. If a known device or RTD is not dis-
covered, check for proper connection to the RS-485 wiring, power at the peripheral device, and
possible address conflicts (no two peripheral devices can have the same address setting).
Use the Update Network button whenever a new device or RTD is added to the system.
The table below shows the available device addresses for Relay Outputs and RTDs. If RMM2(s)
are installed either in the field or in the NGC-30 panel, they must NOT share the same address as
an NGC-30-CRM/-CRMS (5GF-C).
This status screen lists all the available output devices and relay numbers, as well as the relays
that have already been setup.
This screen lists all the available RTD addresses. If an RTD has been assigned to a Loop, the
right side of the screen shows where the RTD has been used.
This password-protected status screen shows the communication success rate with all of the
devices connected to the RS-485 network. This is helpful in debugging the RS-485 network.
This screen lets you create system-wide global parameters for all Loops.
IMPORTANT: Using the screen saver enhances the lifetime of the screen.
Range: 1–300 minutes
Default: 20 minutes
Note: This time entry also determines how long a password entry will remain valid (see
System|Password section)
Range: 1–100 minutes
Default: 10 minutes
The entries on this screen determine how long an alarm condition must exist before the
NGC-UIT records and signals an alarm condition.
This minimizes nuisance alarms by forcing the NGC-UIT to verify that the alarm condition con-
tinually exists over the selected period of time before alarming.
Note: Choosing the 15 sec option may not allow the NGC-UIT time to verify that the alarm condi-
tion exists
There are three independent alarm relays in the NGC-UIT that can be used for remote annuncia-
tion of alarms. Each relay can be programmed for a specific alarm type, multiple alarm types, or
none. If Any Alarm is chosen for a relay, any alarm condition will activate that relay.
The NGC-UIT can be connected to a distributed control system (DCS) or host computer using an
RS-485, RS-232, or Ethernet connection. All data and setup options are accessed with commu-
nications that follow the Modbus (RTU/Modbus/TCP) protocol. To enable DCS communications,
please refer to the DigiTrace NGC-UIT Modbus Protocol document (H57880).
Note: The above set-up parameters should be provided by your network administrator. The
“Name Server” tab is not applicable for this application.
This screen lets you set up passwords for Level 1 and Level 2.
Level 1
Allows setup of all configuration screens except for the System|Maint. screen. This Level 1
password is left “blank” from the factory; however, it can be set to a new designated password.
If a Level 1 password is chosen, the “Main Menu” timer value determines how long the pass-
word remains active before it has to be re-entered. The password is limited to 40 characters.
Level 2
Allows access to System|Maintenance screen, which permits clearing of Events and program exit.
The default password is LOOP (all capitals).
Note: Save and protect the Level 2 password in a secure location. Contact a Tyco Thermal Controls
representative for lost password recovery.
(Level 2 Password Required) This screen allows for clearing the Events List and to exit the program.
OS Version
Displays OS Version number and build date.
Note: By clearing the event, all the Events and Alarms history information for all Loops is lost. If
the program exit is chosen, heaters are no longer monitored.
For any measured ambient between “minimum design ambient” and “maintain temperature,” the
heaters will be on a percentage of the time equal to (maintain temperature – measured ambient)
/ (maintain temperature – minimum design temperature).
100%
Duty cycle
0%
Ambient temperature
Minimum Pipe
ambient maintain
temperature temperature
MONITOR-ONLY MODE
Select one to four RTDs to monitor the temperature of a pipe, vessel etc. An RTD can be used
from another Relay/RTD or from a RMM2 mounted in the panel or remotely.
If the local RTD is installed, up to three additional RTDs can be used to monitor the temperature
of the pipe, vessel, etc. An RTD can be used from another Relay/RTD or from a RMM2 mounted
in the panel or remotely. If more than one RTD is assigned to a Loop, the NGC-UIT will display
the lowest temperature detected on the main screen. However, it will alarm (high and low tem-
perature) based upon all RTDs assigned to that Loop.
If the local RTD is not installed, up to four additional RTDs can be used to monitor the tempera-
ture of the pipe, vessel, etc. An RTD can be used from another Relay/RTD or from a RMM2
mounted in the panel or remotely. If more than one RTD is assigned to a Loop, the NGC-UIT will
display the lowest temperature detected on the main screen. However, it will alarm (high and low
temperature) based upon all RTDs assigned to that Loop.
Note: If an address entered is lower than any NGC-30-CRM/-CRMS (5GF-C) board found on the
system, the NGC-30 software defaults to 0. Since 0 is not a valid address for any board, select-
ing 0 tells the program that this Loop will not be used for any output control; by default, it will be
a “Monitoring Only” Loop. This is the method for setting up a Loop as an “Alarm Only” channel.
Note: The NGC-UIT displays the parameters of heaters. It also is a means to input information to
the NGC-30-CRM/-CRMS. Once the system is set up, the NGC-30-CRM/-CRMS controls the
heater Loops, and even if the NGC-UIT display loses communications between the
NGC-30-CRM/-CRMS and the NGC-UIT, the heaters are still being controlled by the
NGC-CRM/-CRMS. A feature of the -CRM/-CRMS is that if it is hardwired to the system, the sys-
tem still continues to work.
Control Temperature The lowest temperature from the RTDs assigned to a Loop
DB Dead Band
Device Address Network address for specific hardware devices attached to the NGC-UIT
Loop Short for ‘Control Loop’, the basic organizing structure of the NGC-30
RTD Number This is the number of the RTD determined by the physical point of con-
nection to a networked device
Table D.1
Data Entry Type Description
Entry Window In Setup Screens, any white entry box will populate via a pop-up entry
window
Entry List Allows choices from a list of data
A printed copy of the spreadsheet is available for use on the following page. However, informa-
tion will have to be manually entered into the NGC-30 User Interface Terminal.
Regardless of which medium you use, retain a copy for future reference or backup.
Screen Page
Events 40
Events (Alarm Heading) 41
Main 26
Network|Devices 43
Network|Relays 44
Network|RTDs 45
Network|Maint 45
Network|Remove 46
Setup|Current 33
Setup|G.F. 32
Setup|Loop 27
Setup|Maint 35
Setup|PASC 34
Setup|RTDs 30
Setup|Temp 31
Status|Loop 36
Status|Maint. 39
Status|Min/Max 39
Status|PASC 38
Status|RTDs 38
System|Clock 49
System|Comm 48
System|Filters 47
System|Maint. 50
System|Misc 46
System|Password 50
System|Relays 48
Tyco, DigiTrace, and DigiTrace Supervisor are trademarks of Tyco Thermal Controls LLC
or its affiliates.
U.S.A. Canada Important: All information, including illustrations, is believed to be reliable. Users, however, should
Tyco Thermal Controls Tyco Thermal Controls independently evaluate the suitability of each product for their particular application. Tyco Thermal
2415 Bay Road 250 West Street Controls makes no warranties as to the accuracy or completeness of the information, and disclaims
Redwood City, CA 94063-3032 Trenton, Ontario any liability regarding its use. Tyco Thermal Controls' only obligations are those in the Tyco Thermal
USA Canada KBV 5S2 Controls Standard Terms and Conditions of Sale for this product, and in no case will Tyco Thermal
Tel (800) 545-6258 Tel (800) 545-6258 Controls or its distributors be liable for any incidental, indirect, or consequential damages arising from
Tel (650) 216-1526 Fax (800) 527-5703 the sale, resale, use, or misuse of the product. Specifications are subject to change without notice. In
Fax (800) 527-5703 addition, Tyco Thermal Controls reserves the right to make changes-without notification to Buyer-to
Fax (650) 474-7711 processing or materials that do not affect compliance with any applicable specification.
[email protected]
www.tycothermal.com
NGC-UIT
ModBus ® Protocol Interface Mapping
for NGC-30 Systems
For Firmware Version 1.1x
Document # H57880
Contents
Section I – Introduction 1
ModBus Communications 1
Contents — i
Section I – Introduction
The DigiTrace® NGC-UIT is the primary user interface terminal for the DigiTrace NGC-30
heat trace controller system. The DigiTrace NGC-UIT maintains an extensive internal
database including details of the system’s current configuration, available resources, set-up
parameters, current conditions, alarm status and numerous other fixed and variable data
points. The ModBus Register Map is exhaustive and extensive. Most ModBus programmers
and system integrators will only require limited access to some of the available data.
CAUTION: The DigiTrace NGC-30 ModBus register can be accessed by DCS systems.
However, this should only be done by expert users who understand that the system makes
use of extensive semaphore fields to assure synchronization between the possibility of
multiple users and conflicting instructions. Tyco Thermal Controls has tested the system
performance and synchronization when changes are made using the UIT touch screen and
DigiTrace Supervisor. System Integrators should not attempt to make set-up changes via
the UIT ModBus Interface unless they are prepared to re-validate system performance with
their own resources.
The DigiTrace NGC-30 system has the capability to monitor and control up to 247 external
hardware devices using an RS-485 network reserved for the system. The external ModBus
user cannot directly access the internal network. All ModBus functions discussed in the
following sections are interactions with the database maintained within the DigiTrace
NGC-UIT.
The DigiTrace NGC-UIT can monitor and control up to 260 Circuits. Although the ModBus
map has space for 500 Circuits, these additional Circuits should not be employed as they
have not been qualified and the system performance will be reduced. A Circuit can be a
simple one to one association between an input sensor and an output device. A Circuit may
have up to 4 temperature sensors but never more than one output. Some Circuits will be
established as “monitor only” Circuits. This type of Circuit does not control an output device,
but it retains the capability to monitor one or several temperature or current inputs and
compare current values to alarm thresholds.
Most ModBus applications will be satisfied by READ ONLY access to the sections of the
database highlighted on pages 15 and 19 (Circuit Status and Circuit Control Data). These
portions of the ModBus register map provide access to the current set-up and real time
values being measured by the system. A snap shot of current conditions, data for trending,
alarm status, the current setting for alarm thresholds and set-points can be easily read
without any risk to the system performance.
The entire ModBus register map is included in this document for completeness. Writing to
the database is within the capability of most ModBus host devices. However, we strongly
recommend that system integrators who write to the database must thoroughly test their
system to ensure it is working properly and that there are no unintended consequences.
ModBus Communications
The DigiTrace NGC-UIT external communications serial port can be configured for use as
an RS-232, RS-485 or Ethernet.
The host defaults are:
x Port Mode: RS-485
x ModBus Address: 1
x Baud Rate: 9600
x Transmit Delay: 0
Section I – Introduction — 1
x Receive Timeout: 50 milliseconds
The DigiTrace NGC-UIT mode of transmission is Remote Terminal Unit (RTU). The
standard configuration is 8 data bits, no parity and 2 stop bits. To change the defaults listed
above, refer to the DigiTrace NGC-30 Programming Guide (H58186)
Section I – Introduction — 2
Section II – ModBus Register Map
ModBus
Address Description Comments
1 NGC-UIT Type NGC-UIT = 0x300
2 NGC-UIT Firmware Version Major Range 0-255
3 NGC-UIT Firmware Version Minor Range 0-255
4 Build Number Range 0-999
.... Spare
99 Spare
100 Spare
Tyco and DigiTrace are trademarks of Tyco Thermal Controls LLC or its affiliates.
ModBus is a trademark of Schneider Automation Inc.
U.S.A. Canada Important:: All information, including illustrations, is believed to be reliable. Users, however, should independently
Tyco Thermal Controls Tyco Thermal Controls evaluate the suitability of each product for their particular application. Tyco Thermal Controls makes no warranties
307 Constitution Drive 250 West Street as to the accuracy or completeness of the information, and disclaims any liability regarding its use. Tyco Thermal
Controls' only obligations are those in the Tyco Thermal Controls Standard Terms and Conditions of Sale for this
Menlo Park, CA 94025-1164 Trenton, Ontario
product, and in no case will Tyco Thermal Controls or its distributors be liable for any incidental, indirect, or
USA Canada KBV 5S2 consequential damages arising from the sale, resale, use, or misuse of the product. Specifications are subject to
Tel (800) 545-6258 Tel (800) 545-6258 change without notice. In addition, Tyco Thermal Controls reserves the right to make changes—without notification
Tel (650) 216-1526 Fax (800) 527-5703 to Buyer—to processing or materials that do not affect compliance with any applicable specification.
Fax (800) 527-5703
Fax (650) 474-7711
[email protected]
www.tycothermal.com