2.1 Preamble
in practice, any disturbance in the normal working conditions is termed as a FAULT. The
effect of fault is to load the device electrically by many times greater than its normal
rating and thus damage the equipment involved. Hence all the equipment in the fault line
should be protected from being overloaded. In general, overloading involves the increase
of current up to 10-15 times the rated value. In a few cases, like the opening or closing of
a circuit breaker, the transient voltages also may overload the equipment and damage
them.
In order to protect the equipment during faults, fast acting circuit breakers are put in the
lines. To design the rating of these circuit breakers or an auxiliary device, the fault
current has to be predicted. By considering the equivalent per unit reactance diagrams,
the various faults can be analyzed to determine the fault parameters. This helps in the
protection and maintenance of the equipment.
26
The line capacitance is negligible.
Thus the line can be modeled by a lumped R-L series circuit. Let the short circuit take
place at t=0. The parameter, controls the instant of short circuit on the voltage wave.
From basic circuit theory, it is observed that the current after short circuit is composed of
the two parts as under: i =is +it, Where, is is the steady state current and it is the transient
current. These component currents are determined as follows.
Consider, v = Vm sin (t+)
= iR + L (di/dt) (2.1)
and i = Im sin (t+-) (22.)
Where Vm = 2V; Im = 2I; Zmag = [R +(L) ]= tan (L/R)
2 2 -1
(2.3)
Thus is = [Vm/Z] sin (t+-) (2.4)
Consider the performance equation of the circuit of figure 1 under circuit as:
iR + L (di/dt) = 0
i.e., (R/L + d/dt)i = 0 (2.5)
In order to solve the equation (5), consider the complementary function part of the
solution as: CF = C1 e(-t/) (2.6)
Where (= L/R) is the time constant and C1 is a constant given by the value of steady
state current at t = 0. Thus we have,
C1 = -is(0)
= - [Vm/Z] sin (-)
= [Vm/Z] sin (-) (2.7)
Similarly the expression for the transient part is given by:
it = -is(0) e(-t/)
= [Vm/Z] sin (-) e(-R/L)t (2.8)
Thus the total current under short circuit is given by the solution of equation (1) as
[combining equations (4) and (8)],
27
i =is +it
= [2V/Z] sin (t+-) + [2V/Z] sin (-) e(-R/L)t (2.9)
Thus, is is the sinusoidal steady state current called as the symmetrical short circuit
current and it is the unidirectional value called as the DC off-set current. This causes the
total current to be unsymmetrical till the transient decays, as clearly shown in figure 2.
The maximum momentary current, imm thus corresponds to the first peak. Hence, if the
decay in the transient current during this short interval of time is neglected, then we have
(sum of the two peak values);
imm = [2V/Z] sin (-) + [2V/Z] (2.10)
now, since the resistance of the transmission line is very small, the impedance angle ,
can be taken to be approximately equal to 900. Hence, we have
imm = [2V/Z] cos + [2V/Z] (2.11)
28
This value is maximum when the value of is equal to zero. This value corresponds to
the short circuiting instant of the voltage wave when it is passing through zero. Thus the
final expression for the maximum momentary current is obtained as:
imm = 2 [2V/Z] (2.12)
Thus it is observed that the maximum momentary current is twice the maximum value of
symmetrical short circuit current. This is refered as the doubling effect of the short circuit
current during the symmetrical fault on a transmission line.
Immediately after the short circuit, the symmetrical short circuit current is limited only by
the leakage reactance of the machine. However, to encounter the demagnetization of the
armature short circuit current, current appears in field and damper windings, assisting the
rotor field winding to sustain the air-gap flux. Thus during the initial part of the short
circuit, there is mutual coupling between stator, rotor and damper windings and hence the
corresponding equivalent circuit would be as shown in figure 4. Thus the equivalent
reactance is given by:
Xd” = Xl +[1/Xa + 1/Xf + 1/Xdw]-1 (2.14)
29
Where Xd” is called as the sub-transient reactance of the synchronous machine. Here, the
equivalent resistance of the damper winding is more than that of the rotor field winding.
Hence, the time constant of the damper field winding is smaller. Thus the damper field
effects and the eddy currents disappear after a few cycles.
In other words, Xdw gets open circuited from the model of Figure 5 to yield the model as
shown in figure 4. Thus the equivalent reactance is given by:
Xd’ = Xl +[1/Xa + 1/Xf ]-1 (2.15)
Where Xd’ is called as the transient reactance of the synchronous machine.
Subsequently, Xf also gets open circuited depending on the field winding time constant
and yields back the steady state model of figure 3.
Thus the machine offers a time varying reactance during short circuit and this value of
reactance varies from initial stage to final one such that: Xd Xd’ Xd’
30
Figure 6. SC current Oscillogram of Armature Current.
The currents and reactances during the three zones of period are related as under in terms
of the intercepts on the oscillogram (oa, ob and oc are the y-intercepts as indicated in
figure 6):
RMS value of the steady state current = I = [oa/2] = [Eg/Xd]
RMS value of the transient current = I’ = [ob/2] = [Eg/Xd’]
RMS value of the sub transient current = I = [oc/2] = [Eg/Xd”] (2.16)
31
Also shown in figure 7, are the circuit models to be used for short circuit current
calculations when a fault occurs at the terminals of the generator, for sub-transient current
and transient current values. The induced emf values used in these models are given by
the expressions as under:
The synchronous motors will also have the terminal emf values and reactances. However,
then the current direction is reversed. During short circuit studies, they can be replaced by
circuit models similar to those shown in figure 7 above, except that the voltages are given
by the relations as under:
The circuit models shown above for the synchronous machines are also very useful while
dealing with the short circuit of an interconnected system.
2.6 Examples
32
Solution:
Figure P1.
Consider the expression for voltage applied to the transmission system given by
v = Vm sin(t+) = 100 sin (100t+150)
Thus we get: Vm = 100 volts; f = 50 Hz and = 150.
Consider the impedance of the circuit given by:
Z = R + jL = 5 + j (100) (0.1) = 5 + j 31.416 ohms.
Thus we have: Zmag=31.8113 Ohms; =80.9570 and =L/R=0.1/5=0.02 seconds.
The short circuit current is given by:
i(t) = [Vm/Z] sin (t+-) + [Vm/Z] sin (-) e-(R/L)t
= [100/31.8113] [sin (100t+150-80.9570) + sin(80.9570-150) e-(t/0.02)]
= 3.1435 sin(314.16 t – 65.96) +2.871 e–50t
Thus we have:
i) imm = 3.1435 + 2.871 e–50t
where t is the time instant of maximum of symmetrical short circuit current. This instant
occurs at (314.16 tc – 65.960) = 900 ; Solving we get, t = 0.00867 seconds so that imm = 5
Amps.
ii) imm = 2Vm/Z = 6.287 A; for =0, and =900 (Also, imm = 2 (3.1435) = 6.287 A)
iii) DC offset current = [Vm/Z] sin (-) e-(R/L)t
= zero, if (-) = zero, i.e., = , or = 80.9570
= maximum if (-) = 900, i.e., = - 900, or = - 9.0430.
33
Solution:
Consider the SLD with the data given in the problem statement. The base values are
selected as under:
Figure P2(a)
Selection of bases:
Sb = 25 MVA (common); Vb = 11 KV (Gen. circuit)- chosen so that then Vb = 66 KV
(line circuit) and Vb = 6.6 KV (Motor circuit).
Pu values:
Xg=j0.2 pu, Xt1=Xt2=j0.1 pu; Xm1=Xm2=Xm3=j0.25(25/5)=j1.25 pu; Xline=j0.15 pu.
Since the system is operating at no load, all the voltages before fault are 1 pu.
Considering the pu reactance diagram with the faults at P, we have:
Figure P2(b)
34
Problem #3: Two synchronous motors are connected to a large system bus through a
short line. The ratings of the various components are: Motors(each)= 1 MVA, 440 volts,
0.1 pu reactance; line of 0.05 ohm reactance and the short circuit MVA at the bus of the
large system is 8 at 440 volts. Calculate the symmetrical short circuit current fed into a
three-phase fault at the motor bus when the motors are operating at 400 volts.
Solution:
Consider the SLD with the data given in the problem statement. The base values are
selected as under:
Figure P3.
Sb = 1 MVA; Vb = 0.44 KV (common)- chosen so that Xm(each)=j0.1 pu, Em = 1.000,
Xline=j0.05 (1/0.442) = j 0.258 pu and Xlarge-system -= (1/8) = j 0.125 pu.
Thus the prefault voltage at the motor bus; Vt = 0.4/0.44 = 0.90900,
Short circuit current fed to the fault at motor bus (If = YV);
If = [0.125 + 0.258]-1 + 2.0 }0.909 = [20.55 pu] [1000/(3(0.4))]
= 20.55 (1.312) KA = 26.966 KA.
35
Consider the base values selected as 10 MVA, 6.6 KV (in the generator circuit) and
6.6(33/6.9) = 31.56 KV(in the transformer circuit). Thus the base current is:
Ib = 10 / [3(31.56)] = 0.183 KA
The pu values are: Xd” = 0.1 pu, Xd’ = 0.2 pu and Xd = 0.8 pu; and XTr = 0.08 (6.9/6.6)2
= 0.0874 pu; Vt = (30/31.6) = 0.9500 pu.
Initial symmetrical RMS current = 0.9500 / [0.1 + 0.0874] = 5.069 pu = 0.9277 KA;
Maximum possible DC off-set current = 2 (0.9277) = 1.312 KA;
Momentary current rating = 1.6(0.9277) = 1.4843 KA; (assuming 60% allowance)
Current to be interrupted by the breaker (5 Cycles) = 1.1(0.9277) = 1.0205 KA;
Interrupting MVA = 3(30) (1.0205) = 53.03 MVA;
Sustained short circuit current in the breaker = 0.9500 (0.183) / [0.8 + 0.0874]
= 0.1959 KA.
PROBLEMS
1. The one line diagram for a radial system network consists of two generators, rated 10
MVA, 15% and 10 MVA, 12.5 % respectively and connected in parallel to a bus bar A at
11 KV. Supply from bus A is fed to bus B (at 33 KV) through a transformer T 1 (rated: 10
MVA, 10%) and OH line (30 KM long). A transformer T2 (rated: 5 MVA, 8%) is used in
between bus B (at 33 KV) and bus C (at 6.6 KV). The length of cable running from the
bus C up to the point of fault, F is 3 KM. Determine the current and line voltage at 11 kV
bus A under fault conditions, when a fault occurs at the point F, given that Zcable = 0.135
+ j 0.08 ohm/ kM and ZOH-line = 0.27 + j 0.36 ohm/kM. [Answer: 9.62 kV at the 11 kV
bus]
2. A generator (rated: 25MVA, 12. KV, 10%) supplies power to a motor (rated: 20 MVA,
3.8 KV, 10%) through a step-up transformer (rated:25 MVA, 11/33 KV, 8%),
transmission line (of reactance 20 ohms) and a step-down transformer (rated:20 MVA,
33/3.3 KV, 10%). Write the pu reactance diagram. The system is loaded such that the
motor is drawing 15 MW at 0.9 leading power factor, the motor terminal voltage being
3.1 KV. Find the sub-transient current in the generator and motor for a fault at the
generator bus. [Answer: Ig” = 9.337 KA; Im” = 6.9 KA]
3. A synchronous generator feeds bus 1 and a power network feed bus 2 of a system.
Buses 1 and 2 are connected through a transformer and a line. Per unit reactances of the
components are: Generator(bus-1):0.25; Transformer:0.12 and Line:0.28. The power
network is represented by a generator with an unknown reactance in series. With the
generator on no-load and with 1.0 pu voltage at each bus, a three phase fault occurring on
bus-1 causes a current of 5 pu to flow into the fault. Determine the equivalent reactance
of the power network. [Answer: X = 0.6 pu]
4. A synchronous generateor, rated 500 KVA, 440 Volts, 0.1 pu sub-transient reactance is
supplying a passive load of 400 KW, at 0.8 power factor (lag). Calculate the initial
symmetrical RMS current for a three-phase fault at the generator terminals.
[Answer: Sb=0.5 MVA; Vb=0.44 KV; load=0.8–36.90; Ib=0.656 KA; If=6.97 KA]
36