FAN FAIL DETECTION UNIT WITH TEMP.

MONITORING
Part No: UL02-FFTDU-ALM-4-20mA

Introduction:
The UL02-FFTDU-ALM-4-20mA is a micro-controller based AC Fan fail
detection unit with temperature indication offered in a highly compact,
rugged and reliable execution. The instrument has three keys on the
front panel, with which the operator can set the parameters and
configure the instrument as desired. A three digit 7-segment digital
display is provided on the front panel which indicates the ambient
cabinet temperature in real time. The display can indicate any scale
range between 000 to 099 units (temperature) value in degree Celsius
(°C). It has retransmission Analog Output of 4-20mA, can be
configurable to any temperature value.

In case of power failure, the set points are retained in memory.


The Fan detection module provides powered output contacts for wiring
the two AC Fans independently through internal control relays.

The instrument also senses the normal healthy current being drawn by
each fan and provides short-circuit and open-circuit protection by cutting
off the supply to the corresponding Fan in case any abnormality is
detected. All these updating of upper current limit for rotor block
detection is done automatically. The instrument operates on universal
SMPS AC power supply of 90 to 270 V AC, 50/60 Hz.

Technical Specifications :

Microcontroller based module for ambient temperature


Type
monitoring and control of two cooling Fans.
Number of Fans Two
Temperature Display Three 0.4” inch seven-segment red LED displays.
Temp Range 000 to 099 degrees Celsius.
Keys 3 nos.
Input Inbuilt Electronic temperature sensor.
Four built-in Relays
Relay 1 & 2 for AC Powered Contact for Fan 1 & 2 respectively
Control Outputs
Relay 3 for Temperature high alarm Relay
Relay 4 for fan failure Relay.
Contact Rating 10 Ampere @ 230 VAC.
Retransmission Analog Output 4-20mA (Configurable to any temperature value)
Two bicolor and one unicolor LED
Fan 1 : Red/Green LED for indication of Fan-1 status
Indications
Fan 2 : Red/Green LED for indication of Fan-2 status
PWR : Red LED for Power ON
Input Power Supply 90-270 V AC, 50/60 Hz.
Protection Short Circuit & Over Voltage Protection
Dimensions 75 x 55 x 110 mm [H x W x D].
Enclosure Polycarbonate.

www.ulepl.com UL02-FFTDU-ALM -4-20mA Rev.0

Page 1 of 4
FAN FAIL DETECTION UNIT WITH TEMP. MONITORING

Operations and Settings:

The Instrument has three keys on the front panel, the functions of which are as below:

The P or PROGRAM key is the central key to be used to access the settings of the instrument.
Pressing this Key allows the operator to view, change and save the parameters i.e. High alarm Set
point
The Incrementing key allows the operator to select the numeral on an increasing scale. The digit will
sequentially display 00, 01, 02 …. 99 on each pressing of the key. This may be used to set the HIGH
ALARM set point. The incrementing speed increases if the key is kept pressed.

This is Reset Key as well as Decrementing key allows the operator to select the numeral on a
decreasing scale. The digit will sequentially display 99, 98, 97….00 on each pressing of the key. This
may be used to set the HIGH ALARM set point. The decrementing speed increases if the key is kept
pressed. Reset Key is to be pressed in the event of fault condition.

On Power ON, the instrument takes approximately 30 seconds for initialization then the UL02-FFTDU-ALM display will
show the ambient temperature and the LEDs will indicate the Fan status and Alarm status. The fan monitoring is indicated
by dual-color LEDs with green color for healthy condition and RED color for fault. If the temperature sensor fails or
becomes “Open”, the display will show ‘TF’. The other notations for various menu options are as below:

Key Notifications:

Abbreviation
Explanation
on Display
FF Fan Fail
Tf Temperature Sensor Fault
E1 Enable Fan1
E2 Enable Fan2
HA High Alarm

Front Facia :

www.ulepl.com UL02-FFTDU-ALM -4-20mA Rev.0

Page 2 of 4
FAN FAIL DETECTION UNIT WITH TEMP. MONITORING
Working for Fan-1 & Fan-2:

Initial Alternating LED Indication and Relay


Key Pressed Conditions
Display Display Status
If both FANS are in healthy
condition bicolor LEDs for
(POWER ON) YYY = Ambient Temperature YYY - FAN1(F1) & FAN2 (F2) will show
GREEN color
If ambient temperature
reaches “HA” set point, the The Temperature Alarm will get
Initialization take display toggles between “HA” generated.
place for 10 and the current ambient HA XX
seconds(after temperature. (High Alarm
POWER ON) set point)

In the event of FAN 1 Failure Bicolor LED for FAN1 (F1) will
or open condition, the display show Red color as well as
- will toggle between F1 and FF YYY FAN fail Alarm Relay will get
current ambient temperature. energized

In the event of FAN 2 Failure Bicolor LED for FAN2 (F2) will
- or open condition, the display show Red color as well as
will toggle between F2 and FF YYY FAN fail Alarm Relay will get
current ambient temperature. energized.

In the event of faults in both Bicolor LED for both FAN will
- Fans, the display will toggle show Red color as well as
between Fb and the current FF YYY FAN fail Alarm Relay will get
ambient temperature. energized

Working of Single Fan Operation:

Key Initial Alternating


Conditions LED Indication and Relay Status
Pressed Display Display
(POWER YYY = Ambient If FAN is in healthy condition bicolor LEDs
-
ON) Temperature YYY for FAN1 (F1) will show GREEN color
If ambient temperature
reaches “HA” set point,
the display toggles XXX The temperature Alarm Relay will get
- between “HA” and the HA (High Alarm generated
current ambient set point)
temperature.
In the event of FAN 1
Failure or open condition, Bicolor LED for FAN1 (F1) will show red
the display will toggle FF YYY color as well as Fan fail alarm Relay will get
-
between F1 and current energized
ambient temperature.

www.ulepl.com UL02-FFTDU-ALM -4-20mA Rev.0

Page 3 of 4
FAN FAIL DETECTION UNIT WITH TEMP. MONITORING
Settings and Calibrations:

The following is the sequence of settings on this module. All settings to be done using Increment ( ) and Decrement
( ) keys.

Key Initial Alternating


Function
Pressed Display Display
(POWER Ambient Temperature
023 -
ON)
- Tf If Sensor Fails it shows error (Temperature failure)
INC and DEC Display will toggle between “HA” (i.e.; High Alarm Set Point) and previous
HA 035
(Together) set value.
Use Increment ( ) or decrement ( ) key to set High Alarm Point. Display
PROG HA 35 will toggle between HA and previous High Alarm Point value. Save the
value using PROG key.
PROG Tr Not Applicable (For Auto Sensing)
E1 YS YS=Enable Fan1, n0=Disable Fan1.Use Increment ( ) or decrement ( )
PROG
nO key to enable or disable Fan1. By selecting nO option user can skip Fan1
PROG H1 18 Not Applicable (Auto Sensing)
PROG E2 YS YS=Enable Fan2, n0=Disable Fan1.Use Increment ( ) or decrement ( )
nO key to enable or disable Fan1. By selecting nO option user can skip Fan2
PROG Not Applicable (Auto Sensing)
H2 18
PROG E3 nO n0=Disable Fan3.Fan 3 is Skipped.
PROG E4 nO n0=Disable Fan4.Fan 4 is Skipped.
PROG Here we set the value of Temperature for which output is 20mA using INC
CO 50
or DEC key
PROG Zr 176 Here we digitally set the counts for 4mA
PROG SP 462 Here we digitally set the counts for 20mA
PROG 24 Ambient Temperature

Fault Reset:

Another Use of Decrement key ( Key)

Key The Key must be used as a RESET key in the event of any fault condition.

Testing Procedure:

Once Powered ON the UNIT, it takes 30 sec to sense the fan’s current, and update the upper current limit automatically.
After 30 sec block the fan to check rotor block condition, Fan will get stopped in 4 to 5 seconds.
Note: User don’t have to change any configuration manually of L1, H1, L2, H2 as we use to do in OLD Model

*Note: Specifications are subject to change due to continuous development.

www.ulepl.com UL02-FFTDU-ALM -4-20mA Rev.0

Page 4 of 4