E&P-

E&P-01(
01(02)
02)-CONTROLLER MANUAL (150512)
150512)

1 LAYOUT

E&P-01 FRONT VIEW E&P-01 TERMINAL PIN MAP

Dimension
SIZE : 72*72*107mm
PANEL SIZE : 68*68(+0.6)mm
2 CAUTION
■ POWER INPUT : AC100~AC240V(50HZ/60HZ)
■ In case, there is possibility of fatal injuries, extensive property loss, damages to important parts nearby, must put double safety device.
■ Electric shock : Do not contact AC terminal during power on.
■ Turn off power during checking input power.

3 WIRING DESCRIPTION
■ RTD sensor : A is the other color, B and B' are same color
■ Pressure sensor (General) : P24(+) connect to the pressure sensor"+", (A)port connect to the pressure sensor"-".
Caution : Main power is only for the Power sensor.
■ Self-power Pressure sensor (It is possible to do the self-output of voltage or current.) : Sensor(B') terminal connect Pressure sensor(-). Sensor(A) terminal connect Pressure sensor(+).
■ Valve control : Connect to 'OUT1' terminal (4~20mA).
■ Monitering output : Connect to 'OUT2(PV,SV)' terminal (4~20mA).
■ OUT4 Relay output : Relay will be contact, when have error valve between valve control output current and valve position FEED back current.
■ OUT3 Relay output : To be turn on as Power fail & Sensor error.

4 Names and Functions

LED Lamp Menu User manual & Function


AT : Blinking(Auto tuning) ■ Access & return to output group with 3 sec.
OUT1 : Valve control current, PV/SV - Output Set ■ Press once-blink SV, then change SV value of OUT1 by ▲ ▼ button
OUT2 : Transmission(PV, SV, RPV, RSV) Output ■ Move among each parameter at a time
OUT3 : Temp./Sensor error alarm ■ Move a line

C/ALM(OUT4) : Normal condition - "ON"
If Power fail - OUT4 ="OFF" ■ Change the function & setting value
▲ ▼
PV display
Sensor signal error : "- - - -" ■ If push two buttons together for 3 sec., you can enter the input group
Set + ▲
Sensor error : OUT3=ON, OUT4=OFF
SV display Set
■ If push two buttons together for 3 sec., you can select the current output mode
+ ◀
Ex) Manual output-6.0mA : "6.0"-output
■ If push two buttons together for 3 sec., you can start the auto tuning mode
Set + ▼
■ If push two buttons together for 3 sec. on auto tuning mode, you can stop the mode
■ The auto tuning mode is out of maker's recommendation

5 Class and Range


Input signal Signal code Controller setting Range Quality
RTD PT Pt ―199.9~600.0 ±0.2% of the full range
D.C.voltage 1-5V V.15 ―1999~9999
D.C.current 4-20mA MA.20 ―1999~9999

Output signal Signal code Output terminal Remark


Current output 4~20mA OUT1 Valve control
Current output 4~20mA PV,SV Mornitoring transmission output
Power input(*Normal condition-Relay terminal,"ON" / Power fail & Sensor
Relay A접점 OUT4
error-"OFF")
Relay A접점 OUT3 Temperature & Sensor error - Relay terminal, "ON"
6 Input group

■ Input & Output sort, control way in based on input group


■ Access input group : "set" button + "UP(▲)" button = Push 3sec.
■ Transfer parameter : "set" button - 1 time
■ Value(func.) change : Using "▲" or "▼" button
■ For return : Push the "set" button - 3sec.
■ " " : Parameter on the arrow can't be marked unless it can be chosen <Display symbol letter>
corresponding value.

Parameter Function (Input group)


Input function sensor : PT

Input sensor : PT 100 ohm


1~5V dc
4~20 mA Range "High" : In case of choosing - V15(1-5V), MA20(4-20mA), setting "H,L" Range
(*If Pressure sensor select, Input the max. range for Pressure sensor)
Normal value=PT
Range "Low"

Point range : 0~2

Measured value filter(0, 1, 2, 3, 4, 5, 6, 7, 8, 9)


: Function that prevents from trembling mark value
Normal=0 (The higher value is, the less trembling is.)

Measured value revision(-50~50)


: Function that revises when sensor line lengthens(basic is 3M), connect lines, and decrepancy occurs.
Normal=0.0 Ex.1)If Real value is 50 and BIAS is "10" setting, Display value is "60"

Setting range limit "high" : When set value in here, SV value can't be above it
Ex) SETH : 100, SV can't be set above 100.
Normal=600.0

Setting range limit "low" : It can't be set below setting range.


Ex) SETH:100.0 & SETL:-10.0, SV = It can be set from -10.0 to 100.0
Normal=--199.9

Option
off=Normal case
Normal=OFF dump=Dumping control case

OFF : Data unlock


ON : Data lock setting
Normal=OFF
7 Output group

■ To end output group access & setting, press : "SET" button - 3sec.
■ Move parameter by : "SET" button at a time
■ To change value by : ▲ or ▼ button

Output group
SET

Select for direct or Reverse * Please refer to the "OUT2" for SV / PV


OUt.1
Normal=REV SV, PV, dIr , rEV

"P" setting value P.1 If "C=OFF or T=OFF" is set, it is controlled by the only "P,I,D" value
40.0 SCAN : Output Update time (sec.)

"I" setting value I.1 Normal setting value : I=240, D=20, SCAN=1.0,
240
As the system condition, "P, C, T" value can be adjust

"D" setting value d.1


"C" value : Integral output diameter
20
(Ex:C=1.0 - Normal output, C=2.0 - Nor.x 2 output, C=0.5 - Nor.x 0.5 output)

C
"C" setting value T : The update time fo "I" value = SCAN * T (sec.)
1.0

t
"T" setting value 4

"SCAN" setting SCAn


1.0

"MAH" setting MAH MAH: Limit value for current "High"


20.0

"MAL" setting MAL MAL : Limit value for current "Low"


4.0

"PV or SV" selection OUt.2


Normal=PV RSV, RPV, PV,SV * "RSV, RPV" is REVERSE current output of"SV,PV"

"High value" setting PV(SV)-H *PV output selection : If temperature condition is the same with "PV-H", the current output
100.0 is 20mA or with "PV-L", the current output is 4mA

"Low value" setting PV(SV)-L


0.0 *SV output selection : If temperature condition is the same with "SV-H", the current output
is 20mA or with "SV-L", the current output is 4mA
PV(SV)-bI
"BIAS" setting
0.0

Respond char. Normal


Rise time Overshoot Fixing time
Value Condition
"P" value is Low decrease increase change a little decrease
"I" value is High decrease increase increase delete
"D" valve is High change a little decrease decrease change a little