Jignesh.

Parmar
CALCULATION OF VOLTAGE DROP AND CABLE SIZE FOR MOTOR / ELECT.LOAD www.electricalnotes.wordpress.com
[email protected]

INPUT DATA SHEET RESULT


Select Your Load Motor (Only) Electrical Load Total Load 40.00 Kw
Toal Electrical Load 40 Kw Demand Factor (Assume) 1
Dol Consumed Load 40.00 Kw
0.75 Starting CosØ 0.75
0.75 Starting SinØ 0.66
80 Runing CosØ 0.80
Demand Factor 1 Runing SinØ 0.60
System Voltage V(L-L) 440 Volt 3 Ph Load in KVA 50.00 KVA
System Voltage V(L-N) 254 Volt 1.732
P.F 0.80 Full Load Current 65.61 Amp
Enter Short circuit Current If You Know K.Amp
Cable Installation Media Ground 2 2 Cable Installation Media Ground
Ground Temperature (K2) 45 °C
No of Trench 1
No of Cable/Trench 1 Ground Temp. Correction Factor (K2) 0.80
Distance Between Cable Nill Soil Correction Factor for Air (K3) 1.21
No. of Runs of selected cable 1 Group Factor for Ground (K4) 1.00
Cable Laying on The Depth of 1 Meter Cable Laying Depth Factor (K5) 1.00
Soil Thermal Resistiivty Not Known Km/Watt Total Derating Factor 0.97 0.97
Nature of Soil (k3) Very Wet Soil Conductor Resistance. 1.11 Ohm / km
Distance 200 Meter Conductor Reactance 0.080 Mho/km
Type of Cable LT XLPE (Up to 1.1 KV) 3cX 35 AL Cable Current Capacity 116 Amp
Allowable voltage drop 5 % Derating Current 112.29 Amp
10 Min.No of Runs of Selected Cable 0.58
Voltage Drop 4.83 %
Receving end Voltage 418.73 Volt
Allowable voltage drop 22 Volt
N.B: Enter Your Data in White Background Cell
Formula For % Voltage Drop:= S.C Capacity of Selected Cable 3.29 K.Amp
(1.732 X (Full Load Current)X(RCosØ+j SinØ)XLengthX100) / Line
VoltageXNo of RunX1000