PSP 2nd Sem (Chapter 8) Presented by Group 1
PSP 2nd Sem (Chapter 8) Presented by Group 1
2
OVERCURRENT PROTECTION
✓ The effect of external faults that are not cleared promptly, or steady-state heavy
loads, is to overheat the transformer windings and degrade the insulation.
✓ This will make the transformer vulnerable to internal flashovers.
✓ The effect of a sustained internal fault is arcing, possible fire, and magnetic and
mechanical forces that result in structural damage to the windings, the tank or the
bushings with subsequent danger to personnel or surrounding equipment.
✓ Protection for transformers can be provided by high-side fuses, instantaneous,
and time-delay overcurrent relays or differential relays.
3
PROTECTION WITH FUSES
✓ Fuses are not used to protect transformers with ratings above
2.5 MVA.
✓ The fuse-interrupting capability must exceed the maximum
short-circuit current that the fuse will be called upon to
interrupt.
✓ The continuous rating of the fuse must exceed the maximum
transformer load (i.e., 150%).
✓ The minimum melt characteristic of the fuse should be well
separated from the protective devices on the low side of the
power transformer.
4
TIME-DELAY OVERCURRENT RELAYS
5
INSTANTANEOUS RELAYS
✓ There are several constraints imposed upon the use of instantaneous relay; some
of them depend upon the design of the relay.
✓ Peak magnetizing current in a transformer can be high as 8-10 times peak full-
load current.
✓ Some relay designs – for example electromechanical plunger-type relays respond
to the actual instantaneous value of the current, which includes the DC offset.
✓ Disc-type relays respond only to the AC portion of the current wave and solid-
state or computer-based relays may or may not respond to the DC offset
depending upon their design.
6
PERCENTAGE DIFFERENTIAL PROTECTION
▪ Percentage differential protection, also known as biased differential
protection, is a method used to protect electrical equipment like
transformers and generators from internal faults.
▪ It operates based on the difference in current between the incoming
and outgoing terminals of the equipment. If this difference exceeds a
certain percentage, the relay activates to isolate the faulty section.
▪ The system includes a restraining coil and an operating coil. The
restraining coil helps prevent false trips due to external faults or inrush
currents.
▪ Under normal conditions, the restraining torque (from the restraining
coil) is greater than the operating torque (from the operating coil),
keeping the relay inactive. During an internal fault, the operating
torque exceeds the restraining torque, causing the relay to trip and
isolate the fault.
7
▪ It provides high sensitivity to internal faults and remains stable
during external faults and inrush conditions, reducing the chances
of nuisance tripping.
It is commonly used in protecting transformers, generators, and
feeders.
8
CAUSES OF FALSE DIFFERENTIAL CURRENTS
9
INRUSH CURRENTS
When a transformer is first energized, it experiences a sudden surge of
current known as inrush current.
1. Magnetizing Inrush Current During Energization:
• When voltage is applied to the primary winding of a transformer, it
induces a magnetic field in the core material (usually iron or steel).
• This magnetic field causes the core to become temporarily saturated,
leading to a sudden increase in current.
2. Harmonic Content of the Inrush Current:
• Inrush current contains harmonics due to its abrupt nature.
• These harmonics can affect the power quality of the system such as
voltage distortion, additional heating, causing resonance in the system and
impacting stability.
10
• Harmonics are sinusoidal components at frequencies that are integer
multiples of the fundamental frequency (usually 50 Hz or 60 Hz in AC
systems).
• The most significant harmonics are the 2nd and 3rd harmonics.
3. Magnetizing Inrush During Fault Removal:
• When a fault external to, but near the transformer is removed by the
appropriate circuit breaker, the conditions inside the transformer core are
quite similar to those during magnetization of the transformer.
• As the voltage is applied to the transformer windings jumps from a low
prefault value to the normal (or larger) postfault value, the flux linkages in
the transformer core are forced to change from a low prefault value to a
value close to normal.
• In general, the inrush is smaller than that during transformer energization.
11
4. Transformer Overexcitation:
• Overexcitation of a transformer can trigger differential relay operation. It
results from excessive voltage applied to the transformer.
• During overexcitation, the transformer flux remains symmetric, but goes
into saturation for equal period in the positive and negative half-periods of
the waveform.
12
5. Sympathetic Inrush:
• Sympathetic inrush occurs when a transformer is switched on and is
connected in parallel to an already energized transformer.
• When one of these transformers is un-energized and then switched into
service, it causes an abrupt voltage drop.
• The sudden change in voltage affects the already energized transformer
connected in parallel.
14
SUPERVISED DIFFERENTIAL RELAYS
16
THREE - PHASE TRANSFORMERS
17
MULTI-WINDING TRANSFORMER PROTECTION
✓ It's a protection for transformers with multiple windings, applicable to both three-
phase and single-phase transformers.
✓ Consider a three-winding transformer where one winding is delta-connected and the
other two are wye-connected.
✓ Current transformers (CTs) are crucially connected: wye on the delta side and delta on
the wye side to compensate for phase shifts and keep secondary currents aligned.
✓ CT ratios are adjusted so that when any two windings are active, equal currents are
sensed.
✓ In some cases, a two-winding differential relay can protect a three-winding
transformer, especially if only one winding is connected to a source.
✓ However, if multiple windings have sources, paralleling them for protection can be
risky due to potential current imbalances.
18
PROTECTION OF REGULATING TRANSFORMERS
✓ Regulating transformers adjust turns ratio or phase shift between primary and
secondary windings.
✓ They typically consist of two transformers: one for magnetizing current and one for
variable adjustments.
✓ Traditional percentage-differential relays are unsuitable for protecting these
transformers because changes in turns ratio or phase disrupt the balance between
primary and secondary currents.
✓ Manufacturers provide specialized protection recommendations due to these unique
needs.
✓ Sudden Pressure Relays (SPRs) are highly sensitive but cannot protect the regulating
part due to arcing from tap-changing mechanisms triggering false alarms.
19
VOLTS-PER-HERTZ PROTECTION
20
NONELECTRICAL PROTECTION
Transformer protection can include non-electrical methods like pressure and
temperature devices :
• Pressure Devices: These devices, like sudden Temperature Devices: Various devices monitor
transformer temperatures measure the top oil
pressure relays (SPRs) in the US, detect faults
inside transformer tanks by sensing pressure temperature, while others use current and oil
waves caused by fault arcs in the oil. temperature to gauge overall temperature effects.
• They can sound alarms or trip the transformer. • Alarms alert operators to high temperatures,
allowing them to remotely unload the
• However, they may be overly sensitive and transformer or dispatch personnel.
respond to external fault currents or faults • Hot-spot sensors also control cooling systems
outside the tank. like fans and pumps.
• Combining pressure relays with differential • These devices ensure transformers operate
relays provides robust protection. safely by detecting internal faults and
monitoring temperature, helping prevent
damage and enabling prompt corrective actions.
21
PROTECTION SYSTEMS FOR TRANSFORMERS
22
PARALLEL TRANSFORMER BANKS
▪ A setup when two transformers are connected in parallel without
circuit breakers separating them, a single differential relay may
protect both banks.
▪ However, issues like sympathetic inrush currents can trip both
transformers simultaneously.
▪ Using separate differential relays for each transformer solves this
problem.
23
TAPPED TRANSFORMER BANK
▪ A setup where a transformer is directly connected to a high-voltage
transmission line to supply power to isolated industrial or residential loads.
▪ This configuration is cost-effective and practical.
▪ Protection typically involves differential relays that include the high-side
breaker and low-voltage components, ensuring faults are detected and isolated
to maintain reliable service.
▪ Alternatively, a differential relay can be connected to a low-side breaker
depending on the specific installation design.
24
MOTOR-OPERATED AIR BREAK SWITCHES
(MOABS)
▪ Part of a protection system for transformers connected directly to high-voltage
transmission lines.
▪ Unlike traditional circuit breakers, MOABs do not interrupt fault currents
themselves but are controlled by differential relays.
▪ These relays detect internal faults within the transformer and signal remote line
breakers to trip, isolating the fault and preventing damage.
▪ Additionally, a ground switch at the transformer can be used to create a fault
signal that triggers the differential relays and ensures prompt response from the
protection system.
▪ This integrated approach ensures effective protection against faults, maintaining
the reliability and safety of the electrical system.
25
26
SUBSTATION DESIGN
▪ a power transformer interconnects two or more voltage levels, its location requires
special consideration in the design of a substation and the protection of all of the
elements within it.
▪ the various voltage levels are contained within separate areas, each with its own bus
configuration and associated equipment and separated by considerable distances.
▪ In addition to providing dependability the two zones allow ready identification of the
fault location, that is, within the transformer itself or on the high- or low-voltage leads.
27
▪ Variations of this configuration are very common. If the transformer and both
circuit breakers are relatively close to each other, the internal differential can be
omitted and a pressure relay used to indicate a fault within the transformer tank.
▪ Since extra high-voltage (EHV) breakers are expensive, they are often omitted
in station designs such as this with the tapped transformer, the transformer is
tied directly to the EHV bus through a MOAB.
▪ The major disadvantage is the fact that a transformer fault must be cleared by
opening all of the 345 kV bus breakers.
28
STATION SERVICE
29
Generator Station Design
✓ In generator stations designed with unit-connected systems for large fossil-fired
plants, components such as the generator, generator step-up transformer (GSU),
unit auxiliary transformer (UAT), and reserve auxiliary transformer (RAT) are
interconnected for integrated protection and control.
✓ The GSU and UAT are typically protected by unit and overall differential relays
(87U and 87OA), which are harmonic-restrained to account for transformer
inrush currents.
✓ High- and low-voltage lead differentials may be added if leads are extensive, and
pilot wire protection considered for longer distances.
✓ Volts/hertz relays are essential to monitor voltage and frequency during generator
start-up phases, ensuring transformers operate within safe flux levels.
30
Conclusion