GENERAL PLUMBING NOTES:

100
1. RUN ALL HORIZONTAL PIPING IN PERFECT ALIGNMENT AND AT A GRADE NOT LESS THAN TWO PERCENT (2%).

LEACHING CO DIGESTIVE
2. ALL CHANGE IN DIRECTION SHALL BE MADE BY APPROPRIATE USE OF FORTY-FIVE DEGREES(45°) WYES, LONG SWEEP QUARTER CHAMBER CHAMBER

OUTLET
BEND, SIXTH-EIGHT OR SIXTEENTH BEND. WHEN THE CHANGE OF FLOW IS FROM HORIZONTAL TO VERTICAL, A SINGLE ONE EIGHT
(1/8) BEND COMBINATION MAY BE USED ON VERTICAL STACKS, AND SHORT QUARTER BENDS MAY BE USED ON WASTE LINE, TEE
MANHOLE MANHOLE
AND CROSSES MAYBE USED IN BENT PIPES.

1500
1300

600
500
CO INTLET

3. NO DOUBLE HUB OR TEE BRANCH SHALL BE USED ON HORIZONTAL SOIL AND WASTE LINES.
500 500
150 600 150 600 600 600
4. THE DRILLINGS AND TAPPING OF HOUSE DRAIN, WASTE OR VENT PIPES AND USE OF SADDLE HUB AND BEND ARE PROHIBITED.

100
5. PROVIDE CLEAN-OUTS UNDER THE FOLLOWING CONDITIONS:
PLAN
a. EVERY CHANGE OF HORIZONTAL DIRECTION EXCEEDING TWENTY TWO AND A HALF DEGREES(22.5°).
b. ONE AND ONE HALF METERS (1.5m) INSIDE THE PROPERTY LINES BEFORE THE HOUSE DRAINAGE CONNECTION .
MANHOLE W/ 12mmØ
c. EVERY FIFTEEN METERS (15m) IN HORIZONTAL RUN OF PIPES. AT THE END OF ANY HORIZONTAL PIPE LINES. CONCEALED LIFT
HANDLE AS SHOWN
3000
6. NOT LESS THAN 0.30 METERS OF AIR SPACE MUST BE LEFT BETWEEN THE TOP OF THE SEWAGE AND THE UNDER PART OF THE TOP 4"Ø PVC
100 900 100 1800 100
OUTLET PIPE
SLAB. 150 600 150 600 600 600
500 500
CO CO
FFL
7. NO SEPTIC VAULT SHALL BE CONSTRUCTED UNDER THE BUILDING.

150
8. ALL PLUMBING WORKS SHALL BE DONE UNDER THE SUPERVISION OF A LICENSED MASTER PLUMBER OR SANITARY ENGINEER.

300
AIR SPACE

9. UNLESS NOTED OTHERWISE, ALL WATER SUPPLY PIPES SHALL BE Ø21" uPVC. INLET
OUTLET 10mmØ HORIZONTAL
BARS AT EVERY 3
DIGESTIVE LAYERS OF CHB

1350
1750
LEACHING CHAMBER
12mmØ BARS SPACED
CHAMBER
AT 150mm ON CENTER
BOTHWAYS
2% SLOPE 12mmØ VERTICAL BARS
SPACED AT 400mm ON
CENTER

LEGENDS:

250
100mm THICK CHB

300

SYMBOL/ABB. DESCRIPTION SYMBOL/ABB. DESCRIPTION SECTION


3-12mm Ø BARS WITH 10mm 12mmØ MATTING BARS
Ø CROSS BARS SPACED AT SPACED AT 150mm ON
CO CLEAN OUT T/A TO ABOVE 300mm ON CENTER CENTER BOTHWAYS

DS DOWN SPOUT T/B TO BELOW

FD FLOOR DRAIN VSTR VENT STACK THRU ROOF

F FAUCET W WASHING MACHINE


F/A FROM ABOVE WC WATER CLOSET
F/B FROM BELOW WCO WALL CLEAN OUT 500
75 350 75
HB HOSE BIB GATE VALVE CONCRETE COVER
W/12mmØ CONCEALED 500
KS KITCHEN SINK ANGLE VALVE LIFT HANDLE

100
75 350 75
300
6"Ø DRAINAGE PIPE
LAV LAVATORY SANITARY/DRAINAGE LINES

75
475
700
SHO SHOWER VENT PIPES

300
350

500
125
125
WATER LINES CONCRETE COVER

75
W/12mmØ CONCEALED
LIFT HANDLE

SECTION PLAN

CERTIFIED BY: PRC No. PROJECT TITLE: APPROVAL: SHEET CONTENT: REVISIONS: SHEET NO.:
VALIDITY

SANITARY ENGINEER/ MASTER PLUMBER


PTR No.
ISSUED AT TWO (2) STOREY RESIDENTIAL UNIT
OWNER
AS SHOWN
P
ISSUED ON
TIN
2 2
I CERTIFY THAT THIS WORK WAS PREPARED BY ME
OR DONE UNDER MY DIRECT SUPERVISION LOCATION: PUROK #4, BRGY. MALASIN, AURORA, ISABELA ADDRESS: PUROK #4, BRGY. MALASIN, AURORA, ISABELA NO. DESCRIPTION DATE
CB CB
PVC PIPE 4" DIA. PVC PIPE 4" DIA.

CB
ST

PVC PIPE 4" DIA.

PVC PIPE 2" DIA.

PVC PIPE 4" DIA.


Sink FD
WCPV
C
lav PI
PE
4"
DI
A. CO

PVC PIPE 4" DIA.


VSTR VSTR
PVC PIPE 2" DIA.

.
IA
D
4"
10 11 12 13 14 15 16 17 10 11 12 13 14 15 16 17

PE
lav

.
9 9

IA
PI

D
8 8 CO

2"
C
PVC PIPE 4" DIA.

PV
7 6 5 4 3 2 1 7 6 5 4 3 2 1

PE
WC FD

PI
WC

C
FD RISER

PV
CO

PVC PIPE 4" DIA.


PVC PIPE 4" DIA. PVC PIPE 4" DIA. TR
CB CPO VS ER
FD
CB CB IA. RIS
V
CP
CB WCPVC PIPE 4" DIA. IPE
4" E4
"D
IP
lav DIA
. PV
CP WC
CO FD
TR
VS
TAPPED TO THE
NEAREST DRAINAGE LINE
17
16
15
14 1
13 2
12 3
11 4
10 5
9 6
8 7

1 GROUND FLOOR SANITARY LINE 2 SECOND FLOOR SANITARY LINE CB


.
P 1 1:100mts P 2 1:100mts 4"
DIA
IA. PV
IPE 4"
D CP
CP IPE
IPE
PV 4"
CP DIA
PV .

PVC PIPE 2" DIA.


PVC PIPE 4" DIA.
CB DIA
.
ST 2"
.
DIA IPE
2" CP
IPE PV
IA. PVC
P
FD COPVC
PIP
lav WC
D
4" E4
IPE "D
CP IA.
PV
k
F Sin CB INE
E EL
TH AG
SH TO AIN
CB
17

SINK 16 D
E D R
PP T
15

HB 14

TA RES
1
13 2
12

F
3

CB A
11 4

NE
10 5
9 6
8 7

IA.
LAV 4 "D
IPE
CP
PV

DIA
. CB
4"
10 11 12 13 14 15 16 17 10 11 12 13 14 15 16 17 IPE
9 LAV F 9 F PV
CP
8 8 LAV
7 6 5 4 3 2 1 7 6 5 4 3 2 1

HB HB CB
SH SH

5 ISOMETRIC VIEW
P 1

CV
WM
GV

TAPPED TO THE
NEAREST WATERLINE

3 GROUND FLOOR COLD WATERLINE 4 SECOND FLOOR COLD WATERLINE


P 1 1:100mts P 1 1:100mts

CERTIFIED BY: PRC No. PROJECT TITLE: APPROVAL: SHEET CONTENT: REVISIONS: SHEET NO.:
VALIDITY

SANITARY ENGINEER/ MASTER PLUMBER


PTR No.
ISSUED AT TWO (2) STOREY RESIDENTIAL UNIT
OWNER
AS SHOWN
P
ISSUED ON
TIN
1 2
I CERTIFY THAT THIS WORK WAS PREPARED BY ME
OR DONE UNDER MY DIRECT SUPERVISION LOCATION: PUROK #4, BRGY. MALASIN, AURORA, ISABELA ADDRESS: PUROK #4, BRGY. MALASIN, AURORA, ISABELA NO. DESCRIPTION DATE
GENERAL NOTES
1.ELECTRICAL INSTALLATION HEREIN SHALL BE DONE IN ACCORDANCE WITH
THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE & RULES AND
REGULATION OF THE MUNICIPALITY HAVING JURISDICTION. MESSENGER WIRE

16mmØ EYE BOLT

0.30m 0.30m
2. ALL ELECTRICAL WORKS HEREIN SHALL BE EXECUTED BY EXPERIENCED
SERVICE SPOOL PORCELAIN
MEN UNDER THE DIRECT SUPERVISION OF A DULY LICENSED ELECTRICAL [ BY OWNER / MERALCO ]
CT METERING BOX

ENGINEER OR A MASTER ELECTRICIAN, WORKS SHALL BE NEATLY PLACED, [ BY MERALCO ]

SECURELY FASTENED AND PROPERLY FINISHED. 20mmØ IMC

VARIES ( CHECK HEIGHT )


3. TYPE PF SERVICE ENTRANCE SHALL BE SINGLE PHASE, TWO WIRES, 230 V, 60 HZ.
KILO-WATTHOUR
METER
[ BY MERALCO ]
4. ALL MATERIALS SHALL BE NEW & APPROVED TYPE FOR THE LOCATION AND PURPOSE.
GROUNDING WIRE
IN 15mmØ PVC

5. ALL INSTALLATION SHALL BE CONCEALED FROM BY INSTALLING CONDUCTOR 2 THHN [ BLACK COLOR ] +
21-30mm GRD.[ WHITE COLOR ]
[ BY OWNER ]

1.80m
IN PVC EMBEDDED IN CONCRETE, PARTITION OR CEILING. IN 65mmØ PVC / IMC
GROUNDING WIRE
[ WHITE COLOR ]
[ LOOP AT GRND. ROD ]
NGL
6. MINIMUM SIZE OF CONDUCTOR AND CONDUIT WHEN NOT INDICATED SHALL BE

0.90m
1.6 mm DIA. ( NO. 14 ) AND 15 mm NOMINAL DIA. FOR CONDUIT RESPECTIVELY. EARTHFILL

1.20m
0.30m
TO PANELBOARD "LP"
7. MOUNTING HEIGHT OF DEVICES SHALL BE AS FOLLOWS: LOCATED INSIDE
KITCHEN
10mmØ GROUNDING ROD
3.0m LENGTH
EARTHFILL [ EMBEDDED ]

A. PANEL BOARD - 1.80 m FROM TOP OF PANEL TO FFL


B. WALL SWITCHES - 1.37 m ABOVE FINISH FLR LEVEL
C. CONVENIENCE OUTLET - 0.30 m ABOVE FIN FLOOR LEVEL
0.15 m ABOVE WORKING COUNTER
LEGEND

LIGHTING OUTLET 1 CIRCUIT HOMERUN

FLUORESCENT LIGHT PANEL BOARD


PB
2-GANG CONVENIENCE OUTLET S3way 3-WAY SWITCH

Sa SINGLE SWITCH WH WATER HEATER

Sab 2-GANG SWITCH

CERTIFIED BY: PRC No. PROJECT TITLE: APPROVAL: SHEET CONTENT: REVISIONS: SHEET NO.:
VALIDITY

ELECTRICAL ENGINEER/MASTER ELECT'N


PTR No.
ISSUED AT TWO (2) STOREY RESIDENTIAL UNIT
OWNER
AS SHOWN
E
ISSUED ON
TIN
2 2
I CERTIFY THAT THIS WORK WAS PREPARED BY ME
OR DONE UNDER MY DIRECT SUPERVISION LOCATION: PUROK #4, BRGY. MALASIN, AURORA, ISABELA ADDRESS: PUROK #4, BRGY. MALASIN, AURORA, ISABELA NO. DESCRIPTION DATE
p o
n
RANGE
Smno REF ACU ACU

z 9 10
a1
m y
l
l Sz 6 5
PB
1 2 Sa1 PB
j 3 4
Sy
Slm S3w
10 11 12 13 14 15 16 17 10 11 12 13 14 15 16 17
10 11 12 13 14 15 16 17 10 11 12 13 14 15 16 17
9 9

8 k 8
w x 9 9

g Sk
8 8
7 6 5 4 3 2 1 7 6 5 4 3 2 1
7 6 5 4 3 2 1 7 6 5 4 3 2 1

Sw Sx
S(3w),g
Sdef Sqrs Stuv 7
ACU
8
ACU
s
c c f v
i
Shij Sabc

b d e t u
h h
r

a a q
q q

1 GROUND FLOOR LIGHTING LAYOUT 2 SECOND FLOOR LIGHTING LAYOUT 3 GROUND FLOOR CONV.OUTLET LAYOUT 4 SECOND FLOOR CONV. OUTLET LAYOUT
E 1 1:100mts E 1 1:100mts E 1 E 1
1:100mts 1:100mts

LOAD SCHEDULE & COMPUTATION ( PANEL BOARD 1,2 & 3)


Circuit
No.
LOAD DESCRIPTION
LO
Quantity
CO Other
VA Volt
Load
Amp Trip
Circuit Protection
Frame Pole
Size of Wire
( mm2 )
Size of Conduit
( mm DIA. )
GENERAL NOTES AND SPECIFICATIONS:
1 Lighting Outlet ( Ground Flr. ) 20 2,000 230 8.69 15AT 50AF 2 3.5mm2 THHN 15mm
2 Lighting Outlet ( Second Flr. ) 13 1,300 230 5.65 15AT 50AF 2 3.5mm2 THHN 15mm 1. THIS ELECTRICAL INSTALLATIONS SHALL CONFORM WITH THE PROVISION OF THE P.E.C., THE REGULATIONS OF PASIG
3 Convenience Outlet ( Ground Flr.) 10 1,800 230 7.83 15AT 50AF 2 3.5mm2 THHN 15mm
AUTHORITIES AND THE REQUIREMENTS OF MERALCO.
4 Convenience Outlet ( Second Flr.) 9 1,620 230 7.04 15AT 50AF 2 3.5mm2 THHN 15mm
2. POWER SUPPLY SHALL BE 230V, 1 PHASE, 2 WIRE, THERE SHALL BE ONLY ONE SERVICE DROP TO THE BUILDING.
5 Refrigerator 1 1,000 230 4.35 30AT 50AF 2 5.5mm2 THHN 15mm
6 Range 1 4,000 230 17.39 30AT 50AF 2 5.5mm2 THHN 15mm 3. WIRING SHALL BE IN uPVC, UNLESS NOTED OTHERWISE, WIRES SHALL BE COPPER TYPE THHN MINIMUM SIZE SHALL BE 2.0
Aircon Unit -1Hp 1 1,840 230 8.00 30AT 50AF 2 5.5mm2 THHN 15mm SQ.MM.
7
Aircon Unit -1Hp 1 1,840 230 8.00 30AT 50AF 2 5.5mm THHN
2
15mm
8
1,840 230 30AT 50AF 4. ALL METAL, NON- CURRENT CARRYING PARTS OF THE SYSTEM SHALL BE PROPERLY GROUNDED. A THIRD GROUNDING WIRE
9 Aircon Unit -1Hp 1 8.00 2 5.5mm THHN2
15mm
SHALL BE PROVIDED FOR ALL BRANCH CIRCUIT RUNS.
10 Aircon Unit -1Hp 1 1,840 230 8.00 30AT 50AF 2 5.5mm THHN2
15mm
11 Spare 5. ALL MATERIALS TO BE USED SHALL BE THE TYPES APPROVED FOR THE LOCATION AND PURPOSE.
12 Spare
6. THE ELECTRICAL INSTALLATION SHALL BE UNDER THE SUPERVISION OF A REGISTERED ELECTRICAL OR MASTER
ELECTRICIAN.

TOTAL PB 33 19 6 19,080 82.95 70AT 100AF 2 8.0mm 2 THHN 25mm

TOTAL LINE CURRENT ( AMPERE ):

IPB =[ (82.95 X 100%DF) + ( 25% X 8 ) ]


=84.95 AMP
FEEDER CONDUCTOR USE: 2 - 8.0mm 2 THHN 1 - 8.0mm2 THHN in 25mm DIA. RSC

CERTIFIED BY: PRC No. PROJECT TITLE: APPROVAL: SHEET CONTENT: REVISIONS: SHEET NO.:
VALIDITY

ELECTRICAL ENGINEER/MASTER ELECT'N


PTR No.
ISSUED AT TWO (2) STOREY RESIDENTIAL UNIT
OWNER
AS SHOWN
E
ISSUED ON
TIN
1 2
I CERTIFY THAT THIS WORK WAS PREPARED BY ME
OR DONE UNDER MY DIRECT SUPERVISION LOCATION: PUROK #4, BRGY. MALASIN, AURORA, ISABELA ADDRESS: PUROK #4, BRGY. MALASIN, AURORA, ISABELA NO. DESCRIPTION DATE
GENERAL STRUCTURAL NOTES AND TABLE

CERTIFIED BY: PRC No. PROJECT TITLE: APPROVAL: SHEET CONTENT: REVISIONS: SHEET NO.:
VALIDITY

ARCHITECT / CIVIL ENGINEER


PTR No.
ISSUED AT TWO (2) STOREY RESIDENTIAL UNIT
OWNER
AS SHOWN
S
ISSUED ON
TIN
3 3
I CERTIFY THAT THIS WORK WAS PREPARED BY ME
OR DONE UNDER MY DIRECT SUPERVISION LOCATION: PUROK #4, BRGY. MALASIN, AURORA, ISABELA ADDRESS: PUROK #4, BRGY. MALASIN, AURORA, ISABELA NO. DESCRIPTION DATE
0.10m THK. CHB WALL
PLASTERED FINISH

BEAM SCHEDULE D10mm VERTICAL BARS


@ 0.60m ON CENTER

D10mm HORIZONTAL BARS


@ EVERY 3 LAYERS OF CHB

(NOTE 3)
VARIES
JOINT SEALANT

200
NON-EXTRUDING TYPE
JOINT FILLER

FIN. FLR. LINE ELEV. +0.70

SPOT DETAIL 1/A


0.10m THK. GRAVEL BED
WELL COMPACTED TO 95% MDD
BASED ON ASTM D-698

D10mm TRANSVERSE BARS


@ 0.30m ON CENTER

3-D10mm LONGITUDINAL BARS

0.10m THK. GRAVEL BED


WELL COMPACTED TO 95% MDD
BASED ON ASTM D-698

SUBGRADE COMPACTED TO
95% MDD BASED ON ASTM
D-698

SPOT DETAIL 1/B SCALE MTS.

2X14 ANGLE BAR

1 21 X16
3
ANGLE BAR

6.12M

2.59M

0.92M 0.92M

5.55M

HALF TRUSS DETAIL

2X14 ANGLE BAR

8.27M
1 12 X16
3
ANGLE BAR

2.59M

0.98M 0.98M 0.98M

7.85M

TYP. BEAM SECTION HIP TRUSS-1 DETAIL

2X41 ANGLE BAR


1 12 X16
3
ANGLE BAR

6.12M

2.59M

0.92M 0.92M
11.10M

TRUSS-1 DETAIL

TYP. SLAB SECTION 2X14 ANGLE BAR


NTS
1 3
1 2 X16 ANGLE BAR

5.86M
SLAB SCHEDULE SLAB CONSTRUCTION NOTES 0.83M

1. EDGE PANELS:
1.00M 1.00M
EXTEND TOP BARS OF ADJACENT INTERIOR PANEL AND
11.60M
TERMINATE THE EDGE WITH A STANDARD 90° HOOK.
PROVIDE BOTTOM TEMPERATURE STEEL IN THE OPPOSITE TRUSS-2 DETAIL
TYP. BEAM ELEVATION DIRECTION.

2. INTERIOR PANELS:
NTS
EXTEND TOP BARS OF ADJACENT PANELS AT LEAST L/4 2X14 ANGLE BAR
OR MINIMUM DEVELOPMENT LENGTH WHICHEVER GREATER
AND PROVIDE BOTTOM TEMPERARUTRE STEEL IN BOTH DIRECTIONS.
1 12 X16
3
ANGLE BAR

4.46M

1.40M

1.00M

4.24M

HIP TRUSS-2 DETAIL

CERTIFIED BY: PRC No. PROJECT TITLE: APPROVAL: SHEET CONTENT: REVISIONS: SHEET NO.:
VALIDITY

ARCHITECT / CIVIL ENGINEER


PTR No.
ISSUED AT TWO (2) STOREY RESIDENTIAL UNIT
OWNER
AS SHOWN
S
ISSUED ON
TIN
2 3
I CERTIFY THAT THIS WORK WAS PREPARED BY ME
OR DONE UNDER MY DIRECT SUPERVISION LOCATION: PUROK #4, BRGY. MALASIN, AURORA, ISABELA ADDRESS: PUROK #4, BRGY. MALASIN, AURORA, ISABELA NO. DESCRIPTION DATE
11.90M

A B C D A B C D 2.78M 3.18M 3.18M 2.78M


2.19M

14.40M
14.40M

4.60M 5.54M 4.26M


4.60M 5.54M 4.26M
2.78M
USE 2X4 C-PURLINS
SPACED @0.60M O.C.

1 1
3.10M 2.78M
3.10M

2 2
11.10M

2.78M
2.65M
2.65M

3 11.10M

3 11.10M

2.78M
3.25M
3.25M

4 4 2.00M
2.19M 2.19M
2.10M
2.10M

5 5 1.70M 3.00M 3.00M 1.43M 2.78M

11.90M

1 FOUNDATION PLAN 2 2ND FLOOR FRAMING PLAN ROOF FRAMING PLAN


3
S 1 1:100mts S 1 1:100mts S 1 1:100mts

COLUMN SCHEDULE
NOTE: MAIN REINFORCEMENT, ASTM GRADE 60
LATERAL TIES, ASTM GRADE 40

COMPACTED SUBGRADE C1 C2 C3
0.10m BASE COURSE
LEVEL FDN-2ND FLOOR FDN-ROOF BEAM FDN-TOP OF BEAM

6MIL PE VAPOR BARRIER

CONF. REINF.
0.12m THK SLAB ON GRADE 120 MM THK SLAB ON GRADE

D
COMPACTED SUBGRADE
0.12m

JOINT REINF.
0.10m BASE COURSE
L

D-10 TIES 2 X 50, R200


0.40m

6MIL PE VAPOR BARRIER

CONF. REINF.
D
TIE BEAM REINFORCEMENT FOR COL. BAR SPLICES
(SEE DETAIL) SEE TABLE OF MIN. LAP 6 -D16 MAIN BARS
SPLICE LENGTH OF COL.
TIE BEAM REINFORCEMENT

COLUMN TIES AS
PER SCHEDULE
W W TYP. TB SECTION
H

C1
TYPICAL PLAN

CONF. REINF.
D
LEVEL 2ND - ROOF BEAM

150MM THK CHB WITH

JOINT REINF.
10Ø VERT./HOR.
BARS @ 600 O.C.

FOOTING SCHEDULE
120 MM THK
SLAB ON GRADE

CONF. REINF.
D
REINFORCEMENT
D

MARK W L D H REMARKS FOOTING REINFORCEMENT


GRADE 60 (SEE SCHED)
SQUARE
F1 1.20 0.40 2.00 8 - 16 MMØ BW.
FOOTING
100MM COMPACTED
SQUARE BASE COURSE
F2 1.00 0.40 2.00 6 - 16 MMØ BW. W
W

FOOTING
NOTES:

SECTION
1. YIELD STRESS OF HOOPS = 40 KSI
2. D = USE MAXIMUM COLUMN DIMENSION,
1/6 CLEAR HEIGHT OR 18" (450mm)
TYP. WALL TO TIE BEAM
WHICHEVER IS GREATER.
3. NUMBER OF HOOP TIES SAME AS PER
CONNECTION DETAIL
COLUMN TIES SCHEDULE.
FOOTING DETAIL 4. ALL CONCRETE REINFORCEMENT DETAIL
SHOULD BE DONE IN ACCORDANCE WITH
ACI DETAILING MANUAL 1980 PUB SP-66
5. THE CONTRACTOR SHALL NOTIFY THE ENGINEER
AFTER FOOTING EXCAVATION HAS BEEN COMPLETED,
TO CONFIRM THE DESIGN SOIL BEARING CAPACITY.
FOOTING AND COLUMN TO BE ADJUSTED UPON
CONFIRMATION OF THE ACTUAL SOIL BEARING
CAPACITY.

COLUMN ELEV. SHOWING


DOWELS AND TIES SPACING DET.

CERTIFIED BY: PRC No. PROJECT TITLE: APPROVAL: SHEET CONTENT: REVISIONS: SHEET NO.:
VALIDITY

ARCHITECT / CIVIL ENGINEER


PTR No.
ISSUED AT TWO (2) STOREY RESIDENTIAL UNIT
OWNER
AS SHOWN
S
ISSUED ON
TIN
1 3
I CERTIFY THAT THIS WORK WAS PREPARED BY ME
OR DONE UNDER MY DIRECT SUPERVISION LOCATION: PUROK #4, BRGY. MALASIN, AURORA, ISABELA ADDRESS: PUROK #4, BRGY. MALASIN, AURORA, ISABELA NO. DESCRIPTION DATE
1 2 3 4 5 A B C D

1 S E C T I O N A 2 S E C T I O N B
A 3 1:100mts A 3 1:100mts
3 R O O F P L A N
A 3 1:100mts

SCHEDULE OF DOOR AND WINDOWS


0.80M 0.80M 0.80M 0.80M 0.90M 0.80M 0.60m

2.10M 2.10M 2.10M 2.10M 2.10M

D D D D D
1 2 2 3 4

(1 SET) (1 SET) (3 SETS) (4 SETS) (3 SETS)


ALUMINUM FRAME DOOR ALUMINUM FRAME DOOR SOLID WOOD PANEL TYPE FLASH DOOR TYPE PVC DOOR TYPE
TINTED GLASS TINTED GLASS SWING DOOR SWING DOOR SWING DOOR
SLIDING DOOR SWING DOOR
LOCATION: BACKDOOR LOCATION: BEDROOM LOCATION: T&B
LOCATION: ENTRANCE DOOR LOCATION: BALCONY

0.50M 1.20M 1.00M 1.40M 1.20m 0.60m

0.50M 0.60m

1.20m 1.20m 1.00M

W W W W
1 2 3 4 W W
(7 SETS) (2 SETS) (8 SET ) (2 SET )
5 6
ALUMINUM POWDER COATED ALUMINUM POWDER COATED ALUMINUM POWDER COATED ALUMINUM POWDER COATED (1 SETS ) (3 SETS )
TINTED GLASS TINTED GLASS TINTED GLASS TINTED GLASS
ALUMINUM POWDER COATED ALUMINUM POWDER COATED
AWNING WINDOWS FIXED WINDOWS SLIDING WINDOWS FIXED WINDOWS
TINTED GLASS TINTED GLASS
LOCATION: BEDROOMS, LIVING AREA LOCATION: GUEST & MASTER BEDROOM LOCATION: BEDROOM, CARPORT LOCATION: BEDROOM, CARPORT SLIDING WINDOWS SLIDING WINDOWS
LOCATION: KITCHEN SINK LOCATION: T&B

CERTIFIED BY: PRC No. PROJECT TITLE: APPROVAL: SHEET CONTENT: REVISIONS: SHEET NO.:
VALIDITY

ARCHITECT / CIVIL ENGINEER


PTR No.
ISSUED AT TWO (2) STOREY RESIDENTIAL UNIT
OWNER
AS SHOWN
A
ISSUED ON
TIN
3 3
I CERTIFY THAT THIS WORK WAS PREPARED BY ME
OR DONE UNDER MY DIRECT SUPERVISION LOCATION: PUROK #4, BRGY. MALASIN, AURORA, ISABELA ADDRESS: PUROK #4, BRGY. MALASIN, AURORA, ISABELA NO. DESCRIPTION DATE
A B C D B C D A B C D

14.40M 9.80M

4.60M 5.54M 4.26M 5.54M 4.26M APEX


RIBTYPE
1.21M

W W W W W

1 1
5 3 3 6 3

1.35M

Top of Roof Beam


2.10M Decostone/Wall Tiles
3.10M 3.10M 3.10M W 3.10M
3
W W
Painted ( Wood Finished )
3 3

1.58M 3.00M
2.85M
2 2 Groove Finished
W 3.17M Decostone/Wall Tiles
3 SECOND FFL
10 11 12 13 14 15 16 17 10 11 12 13 14 15 16 17
Stainless Railing
2.65M W 9
2.65M 2.65M W
9 3.05M 2.65M
4
8
2.35M 9.10M 4 8
9.10M
W
7 6 5 4 3 2 1 1.62M W
6 7 6 5 4 3 2 1 1.50M 6

Window Glass with


Aluminum Frame
3 11.10M
3 11.10M 3.20M

1.95M 1.95M Groove Finished


OPEN
BELOW 2.08M GROUND FFL
W
3.25M 3 3.25M
N.G.L.
0.20M

1.40M 1.40M

4 W W W W W W
4 W W W
1 1 1 1 1 2 1 1 2
3 FRONT ELEVATION
2.10M 2.00M 2.10M 2.00M A 2 1:100mts
1.00M

5 5
4.50M 1.70M 4.00M 4.20M 1.70M 4.00M 4.20M

14.40M 9.90M

1 GROUND FLOOR PLAN 2 SECOND FLOOR PLAN


A 2 1:100mts A 2 1:100mts

5 4 3 2 1 1 2 3 4 5 D C B A

APEX APEX APEX

1.21M

2.56M 2.56M

1.35M

Top of Roof Beam Top of Roof Beam Top of Roof Beam

3.00M 3.00M 3.00M


Plastered Finished
Plastered Finished

SECOND FFL SECOND FFL SECOND FFL


Plastered Finished

4.35M
Plastered Finished
3.20M 3.20M Plastered Finished 3.20M
Painted ( Wood Finished )

GROUND FFL GROUND FFL GROUND FFL


N.G.L. N.G.L. N.G.L.
0.20M 0.20M 0.20M

4 LEFT SIDE ELEVATION 5 RIGHT SIDE ELEVATION 6 REAR ELEVATION


A 2 1:100mts A 2 1:100mts A 2 1:100mts

CERTIFIED BY: PRC No. PROJECT TITLE: APPROVAL: SHEET CONTENT: REVISIONS: SHEET NO.:
VALIDITY
PTR No.
ISSUED AT TWO (2) STOREY RESIDENTIAL UNIT
AS SHOWN
A
ISSUED ON
TIN
2 3
I CERTIFY THAT THIS WORK WAS PREPARED BY ME
OR DONE UNDER MY DIRECT SUPERVISION LOCATION: PUROK #4, BRGY. MALASIN, AURORA, ISABELA ADDRESS: PUROK #4, BRGY. MALASIN, AURORA, ISABELA NO. DESCRIPTION DATE
Republic of the Philippines
DRAWING LIST Department of Public Works &
TECHNICAL DESCRIPTIONS SHEET CONTENTS
Highways
OFFICE OF THE BUILDING OFFICIAL
LINE BEARING DISTANCE ARCHITECTURAL
LOT 2643-PART, PLS 1085-D A1 PERSPECTIVE

AREA=1,273 Sq.m. SITE DEVELOPMENT PLAN


VICINITY MAP District/City/Municipality

TP 1 S 82 19' E 6968.99m LOCATION MAP


A2 GROUND FLOOR PLAN
1 2 N 20 00' E 62.20m SECOND FLOOR PLAN

2 3 S 63 50' E 19.91m FRONT ELEVATION


RIGHT SIDE ELEVATION
3 4 S 24 24' W 10.65m LEFT SIDE ELEVATION
REAR ELEVATION
4 5 S 66 08' E 2.47m A3 LONGITUDINAL,SECTION A
Land Use and Zoning

5 6 S 21 55' W 51.94m CROSS,SECTION B


ROOF PLAN
6 1 N 62 24' E 19.88m SCHEDULE OF DOORS
SCHEDULE OF WINDOWS

STRUCTURAL
LO
T2 S1 FOUNDATION PLAN

Y
2 643 Line & Grade
PL -PA
SECOND FLOOR FRAMING PLAN
S-1 RT ROOF FRAMING PLAN
085 ,

A
-D TYPICAL ISOLATED FOOTING
TYPICAL STRAP FOOTING
SCHEDULE OF COLUMN FOOTING

W
S2 BEAM SCHEDULE
3 STAIR DETAIL
TYPICAL BEAM DETAIL

F
Architectural
TYPICAL TWO WAY SLAB DETAIL
TRUSS DETAIL
1 PERSPECTIVE

O
S3 GENERAL CONSTRUCTION NOTES AND TABLE

A 1 SCALE NTS ELECTRICAL


4 E1 GROUND FLOOR LIGHTING LAYOUT

T
5 SECOND FLOOR LIGHTING LAYOUT
GROUND FLOOR POWER LAYOUT
Structural

H
SECOND FLOOR POWER LAYOUT
LOAD SCHEDULE & COMPUTATION
GENERAL NOTES

G
A=1,273 Sq.m.

-D
THE SITE E2 GENERAL NOTES

85
Sitio Tagaytay Dalid,

-10
Tabuelan,Cebu

LS
R

,P
PLUMBING & SANITARY Sanitary

RT
P1 GROUND FLOOR SANITARY LAYOUT

-PA
SECOND FLOOR SANITARY LAYOUT

D
GROUND FLOOR WATERLINE LAYOUT

643
1 ISOMETRIC VIEW
A

T2
CATCH BASIN DETAIL
SEPTIC TANK DETAIL

LO
O

SYMBOLS
Electrical
(R. GENERAL NOTES
R.O
.W
R

LO )
T2 6
PL 64
S-1 3-P
085 AR
-D T,
Mechanical

2 VICINITY MAP 3 SITE DEVELOPMENT PLAN


A 1 SCALE NTS
A 1 SCALE NTS

Bureau of Fire Protection

CERTIFIED BY: PRC No. PROJECT TITLE: APPROVAL: SHEET CONTENT: REVISIONS: SHEET NO.:
VALIDITY

ARCHITECT / CIVIL ENGINEER


PTR No.
ISSUED AT TWO (2) STOREY RESIDENTIAL UNIT
OWNER
AS SHOWN
A
ISSUED ON
TIN
1 3
I CERTIFY THAT THIS WORK WAS PREPARED BY ME
OR DONE UNDER MY DIRECT SUPERVISION ISSUED AT LOCATION: PUROK #4, BRGY. MALASIN, AURORA, ISABELA ADDRESS: PUROK #4, BRGY. MALASIN, AURORA, ISABELA NO. DESCRIPTION DATE