Nxr4 Progress

Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Fuel oil/gas boilers

NXR 4 PROGRESS 7 models from 300 to 780 kW

GENERAL DESCRIPTION:
The boilers of the NXR 4 Progress range
are pressurised hot water boilers designed
for connecting to a flue pipe which require
a separate automatic fuel-oil or gas burner :
• Heating body in cast iron
• KSF or KSF CE control panel
540 291 44
• Integrated flow switch

30
240

TECHNICAL CHARACTERISTICS: 680

Conditions of use:
• Maximum operating pressure: 6 bar
• Boiler thermostat setting: 40 to 85°C
• Maximum operating temperature: 100°C 1740
• Safety thermostat: 110°C
(1)

Test condtions:
• CO² Fuel oil = 13%
• CO² Natural gas = 9.5%
• Ambiant temperature: 20°C
L000056-B

Main dimensions: Mk Tapped connection


(1) Inscribed diameter (in mm): Œ Heating outlet - weld
NXR 4 NXR 4 NXR 4 NXR 4 NRX 4 NXR 4 NXR 4
Boiler
Progress 8 Progress 9 Progress 10 Progress 11 Progress 12 Progress 13 Progress 14  Heating return - weld
• Front section: 455
Useful output kW 300-390 390-450 450-540 540-600 600-670 670-720 720-780
• Intermediate section: 530 Ž Rp 2 draining outlet
Power input kW 337-438 438-505 505-606 606-674 674-752 752-808 808-876 Equivalent diameter (in mm): 573  Sludge removal hole Ø Rp 2 1/2 - plugged
Number of sections 8 9 10 11 12 13 14  Integrated flow switch
Water content l 366 409 452 495 538 581 624
∆T = 10K mbar 37 55 86 105 136 161 204
Water resistance (1) ∆T = 15K mbar 20 27 37 47 62,5 78,5 110
∆T = 20K mbar 9,5 13,5 22,5 27 33,5 40 54 Boiler NXR 4 Progress 8 NXR 4 Progress 9 NXR 4 Progress 10 NXR 4 Progress 11 NXR 4 Progress 12 NXR 4 Progress 13 NXR 4 Progress 14
Pressure in the furnace for Ø A (exterior) 250 250 250 300 300 300 300
mbar 1,1 1,5 2,0 2,5 2,5 2,5 2,5
nozzle pressure = 0 (1)
ØB 2" 1/2 2" 1/2 2" 1/2 3" 3" 3" 3"
Smoke temperature (1) (3) °C 220 220 220 220 220 220 220
Fioul kg/h 650 750 900 1000 1116 1200 1450 ØC plate intact or pre-drilled to the diameter specified on order
Mass flue gas flow rate (1) (2)
Gas 700 810 972 1080 1207 1297 1405 D 235 235 235 254 254 254 254

Diameter mm 530 530 530 530 530 530 530 E 1427 1427 1427 1447 1447 1447 1447
Combustion chamber Width mm 638 638 638 638 638 638 638 J 1800 1950 2120 2305 2465 2625 2785
Depth mm 1183 1343 1503 1663 1823 1983 2143
L 1505 1665 1825 1985 2145 2305 2465
Volume m3 0,310 0,354 0,396 0,439 0,481 0,523 0,565
S 1183 1343 1503 1663 1823 1983 2143
Stand-by losses (3) ∆T = 50K W 315 358 413 451 494 505 555
Net weight kg 1802 2072 2238 2454 2638 2880 3057

1 mbar = 10 mmWG = 10 daPa


(1) Nominal operation (top boiler power).
(2) CO2 = 13% on fuel oil and 9.5% on natural gas.
(3) Ambient temperature: 20 °C.

4 5