ETAP Workshop Notes

Short Circuit Analysis


Theoretical Concepts
Electrical power systems composed of a wide range of equipment devoted to generating,
transmitting, and distributing electrical power to various consumption centers. The very
complexity of these systems suggests that failures are unavoidable, no matter how carefully these
systems have been designed. Within the context of short-circuit analysis, system failures
manifest themselves as insulation breakdowns that may lead to one of the following phenomena:
 Undesirable current flow patterns.
 Appearance of currents of excessive magnitudes that could lead to equipment damage
and downtime.
 Excessive over voltages, of the transient and/or sustained nature, that compromise the
integrity and reliability of various insulated parts.
 Voltage depressions in the vicinity of the fault that could adversely affect the operation of
rotating equipment.
 Creation of system conditions that could prove hazardous to personnel.
Because short circuits cannot always be prevented, we can only attempt to mitigate and to a
certain extent contain their potentially damaging effects. One should aim to design the system so
that the likelihood of the occurrence of short circuit becomes small. If a short circuit occurs,
mitigating its effects consists of
 Managing the magnitude of undesirable fault currents.
 Isolating the smallest possible portion of the system around the area of mishap in order to
retain service to the rest of the system.
The main reasons for performing short-circuit studies:
 Verification of the adequacy of existing interrupting equipment. The same type of studies
will form the basis for the selection of the interrupting equipment for system planning
purposes.
 Determination of the system protective device settings.
 Determination of the effects of the fault currents on various system components such as
cables, lines, busways, transformers, and reactors during the time the fault persists.
 Assessment of the effect that different kinds of short circuits of varying severity may
have on the overall system voltage profile.
Basic of AC & DC component of fault

This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved. Page 1 of 17
ETAP Workshop Notes

Short Circuit Analysis


The DC component or shift in zero axis of current from reference or true zero (voltage zero axis)
results from the necessity to satisfy two conflicting requirements:
a) Fault current wave must be maximum (-ve peak) when voltage wave is zero, because of
highly inductive source fault impedance (X/R very high) 90 deg. lag of current.
b) The actual instantaneous fault current at fault is the value determined by the pre-fault
network condition. It will be zero if fault occurs on unloaded circuit. So instantaneous
fault current at t=0 should be zero.
To satisfy (a) and (b) above the AC current wave will have to be shifted by Ip = √2. Iacsymrms,
when fault occurs at zero point of the voltage wave. The shifted current axis is DC component of
fault.

DC Current axis shift initially to √2. Iacsymrms.


Note: In actual practice DC will decay based on fault circuit time constant „Taw‟.

This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved. Page 2 of 17
ETAP Workshop Notes

Short Circuit Analysis


For fault occurring at peak point of voltage wave fault current is already zero (as required from
(a) and (b) above) & Hence no current shift is required & Hence no DC component in fault
current.

Here no DC current axis shift. Hence no DC component when fault current at voltage peak point
in inductive circuit.
Short circuit near to generator

This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved. Page 3 of 17
ETAP Workshop Notes

Short Circuit Analysis


Decay of AC component of fault
For fault close to generator, AC component of fault reduces from initial value as generator
reactance varies from sub-transient to transient and then to steady state values (Xd‟‟, Xd‟, Xd).

Fault close to generator, AC component will decay as shown in the below figure:

AC Decay
For fault at grid bus, AC component of fault does not decay since grid bus is considered to be
remote from a generator (i.e. there are many other reactance components of equipment in series
up to grid bus).

Here, Xt1 + Xline1 + Xt2 >>>> Xd‟‟

This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved. Page 4 of 17
ETAP Workshop Notes

Short Circuit Analysis


Hence any change in Xd” to Xd‟ will not have a big change in net total X hence AC component
of fault at grid bus does not decay.

Decay of DC component of fault


DC component of fault will decay based on L/R of the equivalent source circuit impedance
(applies both to grid & to generator)

Thevenin‟s equivalent of all source impedance (series parallel combination).


Tau= of the source circuit in seconds.
Tau in terms will have to be converted in terms of as follows:
ω Tau= ω = (X= ω L)
ω Tau= (where Tau is in second and ω = 2Пf )
(or) Tau =
DC decay
DC component decay is given as
Idc (t) = Idc (t=0) × e-t/Tau
Where,
Idc (t=0) = Peak of normal rms value of AC symmetrical fault current.
Idc (t=0) = √2 × Iac-sym.rms
Hence, Idc (t) = √2 × Iac-sym.rms × e-t/Tau

This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved. Page 5 of 17
ETAP Workshop Notes

Short Circuit Analysis


Generator DC decay
Generator DC decay is based on „Ta‟ of generator.
Where Ta = armature dc short circuit time given in seconds.
If Ta is given by vendor as 0.3 sec then for 50 Hz generator then,
ω Ta = = 0.3 × 314.2 = 94
Note: In ETAP, value needs to be entered, not Ta.
Asymmetrical break fault current of CB
Ib asym (kArms) at any instant of time„t‟ which is CB breaking time from fault initiation is given
as,
Ib asym (kArms) = √ (Iac-sym rms (t)2 + Idc(t)2)
=√ (Iac-rms (t)2 + Idc(t)2)
The system calculated asymmetrical break fault current should be less than selected CB‟s
asymmetrical break fault current duty (kArms).
% DC component of fault
% DC component at any instant =
Inp-ac = Normal peak of ac symmetrical rms fault current
Standard MV CB short circuit duty
Standard MV CB are type tested as per IEC 62271 with a fault dc decay circuit time constant of
Tau = 45 milliseconds (i.e. 0.045 second) based on test generator (short circuit test on generator)
having ‘No AC fault decay’ (i.e. Xd” = Xd‟).
The ac & dc test fault current at any instant that a tested CB is subjected to short circuit rating of
25 kA ac sym rms for 50 Hz or 60 Hz are shown below.

This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved. Page 6 of 17
ETAP Workshop Notes

Short Circuit Analysis


Standards LV CB are tested as per IEC 60947. These CB‟s are tested at system short circuit
power factor (i.e. System source short circuit impedance R/2 value).
Range of CB Short circuit PF Peak make factor
CB‟s > 50 kA 0.2 2.2
CB‟s between 20 to 50 kA, including 50 kA 0.25 2.1

This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved. Page 7 of 17
ETAP Workshop Notes

Short Circuit Analysis

This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved. Page 8 of 17
ETAP Workshop Notes

Short Circuit Analysis

This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved. Page 9 of 17
ETAP Workshop Notes

Short Circuit Analysis


Selection of short circuit rating of circuit breaker or Switchgear
Circuit breaker or switchgear should be selected to satisfy „MAKE‟, „BREAK‟ & „THERMAL‟
short circuit duty.
MAKE (kAp) = Peak making duty (at ½ cycle).
This is maximum instantaneous fault current magnitude seen by CB/ switchgear during fault.
Maximum value occurs at ½ cycle.
BREAK (kArms) = Asymmetrical break current in kArms at instant of break of a CB (opening
time of CB + relay opening time).
THERMAL = 1 or 3 sec short circuit duty.
Duty of CB/switchgear
As per test Calculated fault as per
Time
HV- IEC 62271 IEC 60909.
LV- IEC 60947
Peak make duty as per IEC.
In ANSI IEEE, it is also called Calculated
½ cycle
as Momentary duty or instantaneous fault of
10 msec at 50 Hz
Make duty or system at a given bus
8.33 msec at 60 Hz
Close & latch duty “Ipm_cal” (kAp)
“Ipm_rtd” (kAp)
Ib_asymm_rtd (kArms)
CB break time
= √( Iacrms2 + Idc2)
40 or 50 or 60 in Ib_asymm_cal (kArms).
at opening time
milliseconds
As per IEC test Tau.

Switchgear selection
Switchgear is ok if,
a) Ipm_rtd > Ipm_cal
b) Ib_asymm_rtd > Ib_asymm_cal (at CB opening time)
(CB opening time in second should be entered in CB rating page for the calculation)
c) Ithermal_rtd (at 1 sec) > Ithermal_cal (at 1 sec)
If 3 sec then 3 sec values are compared for calculation. Thermal withstand needs to be
entered in CB rating.
To select CB, use factors from next sheet. These factors are useful to select switchgear rating
require for calculated system.

This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved. Page 10 of 17
ETAP Workshop Notes

Short Circuit Analysis

This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved. Page 11 of 17
ETAP Workshop Notes

Short Circuit Analysis


Purpose and Description
The purpose of this exercise is to introduce Short Circuit Module interface by using the system
modelled and thereby calculating the total short circuit currents as well as the contributions from
individual motors, generators and utility ties in the system.

Procedure
1. Open LF-Example1 OTI file shown below.

2. Click on “Short circuit Analysis Module” in Mode toolbar as shown.

Click this button for


short circuit mode.

3. Create a New Study Case by clicking the toolbar as shown below.

Click this button to create new


short circuit study case.

This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved. Page 12 of 17
ETAP Workshop Notes

Short Circuit Analysis


4. Name the study case to “Fault 3Phase” as shown below.

5. Select “Fault 3Phase” from Short Circuit study case and proceed to Edit Study Case
option as shown below.

Click this button to edit the


short circuit study case.
6. Adjust the study case settings for “Fault 3Phase” as shown.

This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved. Page 13 of 17
ETAP Workshop Notes

Short Circuit Analysis


7. Select “All Buses” and Click “<<Fault” to create a fault on the selected buses.

Select All Buses


& Click <<Fault

8. To study different faults for the selected buses, click “60909” & give name for Output
File Name as shown below.

This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved. Page 14 of 17
ETAP Workshop Notes

Short Circuit Analysis


9. Results of Three phase faults will be displayed as shown below.

10. Go to Display Options to change the type of fault on the selected buses as shown below.

Check Show Units


for displaying
units in OLV.

Change the Type of


Fault & click OK for
displaying fault
currents of a specific
fault on OLV.

This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved. Page 15 of 17
ETAP Workshop Notes

Short Circuit Analysis


11. ETAP results shows the total bus fault currents, individual contributions of each branch
and also the contributions of the dynamically modelled load as shown below for three
phase fault.

12. To view the short circuit report, go to Report Manager in Short Circuit Toolbar and
Click on Result & select Short-Circuit Report as shown below. Select the type of file
format to view it.

13. Sizing of HV and LV switchgear can be done from short circuit results obtained from
3-Phase Device Duty (IEC 60909) in Short Circuit toolbar.

This document is confidential and proprietary to ETAP / ETAP Automation and may not be reproduced, published
or disclosed to others without written authorization of ETAP / ETAP Automation. All Rights Reserved. Page 16 of 17
ETAP Workshop Notes

Short Circuit Analysis


14. Run 3-Phase device duty calculation and check Peak Short Circuit Results as shown
below.

15. Proceed to Alert View in short circuit toolbar for list of alerts for inadequate sizes of
breakers.