Lessons Learned in Static Var Compensator Protection
Lessons Learned in Static Var Compensator Protection
| 1| | 2|
| 1|, | 2|
A review of the relay settings and event report indicated Generally the second or fourth harmonics are used to
that the ratio of differential to restraint current was sufficient identify an inrush condition. A similar differential current
to warrant a trip however, operation of the differential was occurs when a transformer core is overexcited. The flux in a
blocked by the 5th harmonic blocking logic. Further transformer core is proportional to the applied voltage and
investigation showed that the 5th harmonic blocking threshold inversely proportional to the frequency [B3]. When the
had been set at the minimum allowable pickup of 5% of applied voltage is too high or the frequency too low the
fundamental. The unfiltered event report was retrieved and resulting transformer core can be driven into saturation. The
indicated the level of 5th harmonic current was approximately core saturation results in higher excitation current that is again
30% of fundamental. The high harmonic content is likely due shunted through the magnetization branch and interpreted as a
to the presence of reactive elements in the fault path. differential current. The excitation current during AC
saturation is high in odd harmonics including the third, fifth,
and seventh. The third harmonic is typically the highest as a
percentage of fundamental current however, this harmonic is
eliminated by either a delta connection of the relay CT’s or a
simulated delta connection within the relay itself. Therefore a
high fifth harmonic content is used to indicate an
overexcitation condition.
Given the preceding discussion the following lessons
learned can be applied when setting TCR and TSC differential
relays.
Harmonic blocking and restraint are based on
detecting the signature harmonics generated by the
saturation of a ferromagnetic core. When air core
Figure 12: Unfiltered event report showing significant
reactors are used in TCRs, these elements are not
harmonic distortion in the fault current.
applicable and should be disabled.
A. Harmonic Blocking Logic In transformers, false differential current is
Harmonic blocking logic is a feature that is included in produced when the transformer saturates and
differential relays to prevent misoperation of the differential excitation current entering one winding is shunted
element during inrush or overexcitation conditions commonly through the excitation branch and is not measured
associated with transformer energization. leaving the protected zone. In TCR and TSC
Inrush occurs when a transformer is energized and the differential applications the entire reactive element
residual flux in the transformer core does not align with the and thyristor valve combination is wrapped by the
ideal instantaneous flux that would exist given the applied differential zone. Inrush currents or other transient
voltage. The resulting flux required can be large enough to currents will travel through the zone of protection
drive the core into saturation, at which point increasingly and be accounted for, no additional restraint or
higher levels of magnetization current is required to achieve blocking logic is required.
relatively small increases in flux. In severe cases of inrush, the
magnetizing current is limited only by the air-core impedance IV. EVENT ANALYSIS, TRIP ON CONTROLLED SHUTDOWN
of the transformer windings. Referring to Figure 13, the In some installations, the SVC controls will allow for a
magnetization current is essentially shunted through the protection stop or a soft (normal) stop. A protection stop
magnetization branch of the transformer equivalent circuit and results from either a protective relay or SVC control system
does not appear on the secondary winding, resulting in a trip which both opens the SVC breaker on high-side of the
measured differential current. coupling transformer and signals the valve controls to gate
block the thyristor valve, stopping conduction. For less critical
failures of auxiliary equipment or operator initiated shutdown,
the SVC is taken offline in a more gradual manner referred to
as a “soft” or “controlled” stop. During a soft stop the SVC
output is adjusted to zero and then the SVC breaker is opened
to disconnect the SVC from the power system. Then the TCR
valves are placed into full conduction for several cycles to
allow the TCRs to quickly discharge the energy stored in the
filter bank capacitors. The discharge step is required due to the
capacitive nature of filter banks, and the desire to be able to
quickly bring the SVC back online without waiting up to 5
minutes for the filters to discharge via an internal discharge
device. Bringing the SVC back online quickly is particularly
Figure 13: Path of magnetization current in transformer critical at installations that are designed to automatically
equivalent circuit. restore operation in a degraded mode following a fault on a
TSC or TCR branch. For example, following a fault on a TSC
6
branch, the SVC can shutdown, open the TSC disconnect, and For reference, Figure 15 shows a full shutdown sequence.
restart with the TCR and filter banks providing partial The negative-sequence overcurrent element in this relay had
functionality. During a controlled shutdown, while the TCR is been torque controlled by the breaker status to prevent the
fully conducting, unbalanced currents will flow between the relay from tripping after the breaker had opened.
filter bank and the TCR. The amount of unbalance is This event highlights a few lessons learned for the
dependent on the point on wave at which the TCRs are placed protection engineer when developing protective relay settings
into full conduction. for an SVC:
Depending on the SVC control design,
Figure 14 shows TCR current waveforms and the associated significant unbalance currents may flow during a
relay response during a controlled SVC shutdown sequence. shutdown even after the breaker has opened.
Nuisance trips that occur during a controlled
shutdown can interfere with SVC operations, and
halt auto-reconfiguration schemes.
Negative-sequence elements protecting SVC
branches should consider any intentionally
unbalanced operations, either due to un-symmetrical
operation or filter bank discharge.
The reason turn-to-turn faults are so damaging can best be harmonics that will circulate in the TCR delta connection. The
understood by considering the ideal transformer model. The lesson learned from this event is to be aware of the limitations
ratio of primary to secondary current is related to the primary of the applied protection scheme, depending on the SVC
and secondary turns ratio by the familiar equation: design a high degree of sensitivity for all fault types may not
be practical.
VI. CONCLUSION
When a reactor suffers a turn to turn fault it is essentially SVC protection involves atypical applications of traditional
behaving as a transformer, with the “secondary” winding protective relay schemes. Some features of modern relay
being comprised of the few turns that are shorted. systems, such as harmonic blocking, may serve no purpose but
can adversely affect the performance of the protection system
if ignored or applied incorrectly. Given the increasingly
sophisticated algorithms used in modern microprocessor based
relays, it is critical that the protection engineer understand
both the intended purpose of each algorithm as well as the
context in which they are being applied.
Careful consideration must also be given to the SVC
operation and the protection requirements of the power
electronics equipment. Protective relays must be coordinated
with the SVC’s control system protective schemes to prevent
the unintended operation of protective relays during shutdown
sequences or other periods of intentional unbalanced
Figure 17: Currents in a turn-to-turn fault operation.
For low level faults with only a few turns involved the
VII. REFERENCES
effective turns ratio is high leading to large secondary currents
circulating in the shorted turns.
[B1] Blackburn, J. L., Protective Relaying: Principles and
Applications – Second Edition, Marcel Dekker, Inc., New
York, 1998, ISBN 0-8247-9918-6.
[B2] S.R. Chano, A. Elneweihi, L.H. Alesi, H. Bilodeau,
D.C. Blackburn Jr., L.L. Dvorak, G.E.Fenner, T.F. Gallen,
J.D. Huddleston III, C.A. Stephan, T.E. Weidman, P.B.
Winston, “Static var compensator protection”, IEEE
Transactions on Power Delivery, Vol. 10, No. 3, July 1995.
[B3] James H. Harlow, Electric Power Transformer
Engineering, CRC press, Boca Raton Florida, 2004.
[B4] Robert J. Herrick, Understanding FACTS, IEEE press,
New York, 2000.
[B5] IEEE Standard C37.109, IEEE Guide for Protection of
Shunt Reactors.
[B6] IEEE Standard P1032/D13, Draft Guide for Protecting
Transmission Static Var Compensators.
[B7] Grainger, B., Reed, G.F., Kempker, M., Sullivan, D.J.,
et al, “Technical Requirements and Design of the Indianapolis
Power & Light 138 kV Southwest Static Var Compensator,”
Figure 18: Reactor damage caused by turn-to-to turn fault. IEEE PES T&D Conference and Exposition, Dallas, TX, May
2016.
The options for detecting these types of faults are limited. [B8] O’Connor, J., Reed, G.F., Sullivan, D.J., Shimokaji,
Negative-sequence current elements can detect some of turn- N., Birsa, J., “Testing and Commissioning Experiences for the
to-turn faults but are less sensitive to lower level faults. Duke Energy Progress Static VAR Compensator at
Traditional voltage unbalance schemes that rely on the neutral Jacksonville, NC,” FACTS Panel Session, IEEE PES T&D
connection of a wye connected reactor bank are also not an Conference and Exposition, Chicago, IL, April 2014.
option due to the delta connection of the TCRs. [B9] Sullivan, D.J., Pape, R., Birsa, J.J., Riggle, M., et al,
For some SVCs, sensitive unbalance protection could be “Managing Fault-Induced Delayed Voltage Recovery in
possible by summing the delta currents directly to measure the Metro Atlanta with the Barrow County SVC,” Facts Panel
reactor unbalance current [B6]. This approach cannot be Session, IEEE PES Power Systems Conference and
applied on SVC’s that are intended to operate Exposition, Seattle Washington, March 2009.
unsymmetrically, and will have to be insensitive to the triplen
8
[B10] Johnson, A, Tucker, R., Tran, T, Paserba, J., commercial management of Mitsubishi Electric’s Flexible AC
Sullivan, D., Anderson, C., Whitehead, D., “Static Var Transmission Systems (FACTS) and HVDC business in North
Compensation Controlled via Synchrophasors” WPRC, America. Dan’s leadership of system engineering and
Spokane, Washington, October 2007 sales/marketing teams ensures technical expertise of all
[B11] Grainger, B., Reed, G.F., Kempker, M., Sullivan, FACTS (SVC/STATCOM) products, including engineering
D.J., et al, “Technical Requirements and Design of the and system design aspects from initial planning stages through
Indianapolis Power & Light 138 kV Southwest Static Var design, construction, and commissioning of FACTS systems.
Compensator,” IEEE PES T&D Conference and Exposition, Mr. Sullivan has authored technical IEEE papers and
Dallas, TX, May 2016. publications, and lectured at the University of Wisconsin,
[B12] O’Connor, J., Reed, G.F., Sullivan, D.J., Shimokaji, University of Pittsburgh, and IEEE tutorials on topics such as
N., Birsa, J., “Testing and Commissioning Experiences for the Dynamic Reactive Power Control, Static Var Compensators,
Duke Energy Progress Static VAR Compensator at HVDC, and insulation coordination. Dan is a Senior Member
Jacksonville, NC,” FACTS Panel Session, IEEE PES T&D of IEEE, registered Professional Engineer in Pennsylvania,
Conference and Exposition, Chicago, IL, April 2014. earned MSEE degree from University of Pittsburgh and held
[B13] Sullivan, D.J., Pape, R., Birsa, J.J., Riggle, M., et al, leadership roles in PES Subcommittees and Working groups
“Managing Fault-Induced Delayed Voltage Recovery in on HV Power Electronics.
Metro Atlanta with the Barrow County SVC,” Facts Panel
Session, IEEE PES Power Systems Conference and Jan Paramalingam is a systems engineer in Mitsubishi
Exposition, Seattle Washington, March 2009. Electric Power Products, Inc’s (MEPPI) Power Electronics
[B14] Johnson, A, Tucker, R., Tran, T, Paserba, J., Product Line providing engineering design, apparatus
Sullivan, D., Anderson, C., Whitehead, D., “Static Var engineering, and technical support for Mitsubishi Electric’s
Compensation Controlled via Synchrophasors” WPRC, Flexible AC Transmission Systems (FACTS) business in
Spokane, Washington, October 2007 North America. He has been involved in many SVC projects,
and is responsible for design of FACTS systems, including
commissioning and testing of system performance. Jan has
VIII. BIOGRAPHIES conducted numerous design and performance studies to
Aaron Findley, P.E. is a protection engineer with POWER determine SVC configuration, component ratings, and assess
Engineers Inc. and is based out of Portland OR. While at harmonic performance within the power system. He has a
POWER Mr. Findley has worked on a wide variety of broad technical background of HVDC, FACTS, and Series
protective relaying projects ranging from distribution Compensation products, including engineering and power
protection up to EHV series compensated line protection and system analysis aspects from initial planning stages through
RTDS modeling/testing. He has recently served as the lead study, design, construction, and commissioning of FACTS
protection engineer on several SVC installations. He earned systems. Jan is an active member of the Capacitor and HV
his bachelor’s degree in Energy Engineering from the Oregon Power Electronics Subcommittees within IEEE, and is
Institute of Technology in 2010 and is currently registered as a currently WG P1531 chair.
Professional Engineer in the state of California and a member .
of IEEE.