LM 1340
LM 1340
RISH LM 1340
DIGITAL MULTIFUNCTION INSTRUMENT
Installation & Operating Instructions
Section Contents
1. Introduction
2. Communication Parameter selection screen
2.1 Address Setting
2.2 RS 485 Baud rate
2.3 RS 485 Parity
2.4 Quit Communication Parameters
3. RS 485 ( ModBus ) Output
3.1 Accessing 3X and 4X registers for Reading Measured values
3.2 Accessing 4X register for Reading & Writing Settings
3.3 Accessing 4X register for Long Energy Reading & Writing
3.4 User Assignable Modbus Registers
4. Connection for Optional Pulse Output / Digital Input / RS 485 / Ethernet Module
1
1. Introduction
The Multifunction Instrument is a panel mounted 96 x 96mm DIN Quadratic Digital Panel Meter, which measures
important electrical parameters in 3 ph 4 wire / 3 wire / 1ph Network and replaces the multiple analog panel meters.
It measures electrical parameters like AC voltage, Current, Frequency, Power, Energy (Active / Reactive /
Apparent), phase angle, power factor, individual harmonics & many more. The instrument integrates accurate
measurement technology (All Voltage & Current measurements are True RMS up to 31st Harmonic) with LCD
display with backlit.
It can be configured & Programmed at site for the following : PT Primary, PT Secondary, CT Primary, CT
Secondary 3 Phase 3W, 3 Phase 4W, 1 Phase 2W system.
The front panel has four push buttons using which the user can scroll through different screens & configure the
instrument. The front panel also has Impulse red led, flashing at rate proportional to measured power.
Energy/Counter Screen
Press “ ” key to advance to “RS 485 Baud Rate” screen (see Section
2.2) or press the “ ” key to advance to the “Quit Communication
Parameters” screen (see Section 2.4).
XX
Press “ ” to enter into edit mode, prompt for first digit. (Flashing digit
indicates cursor position).
Press the “ ” and “ ” keys to scroll the value of the first digit. Press the
“ ” key to advance to next digit.
Similarly, enter second and third digits of address. After entering third digit,
pressing “ ” key confirms the selection and shows “Address Setting”
screen (see Section 2.1).
XX
Pressing “ ” key accepts the present value and advance to the “RS 485
Parity Selection” screen (see Section 2.3) and pressing the “ ” key
accepts the present value and advance to the “Address Setting”
screen(see Section 2.1).
Pressing the “ ” key advances to the “Baud Rate Edit” mode and “ ” &
XX
“ ” keys scrolls the value through 4.8, 9.6, 19.2, 38.4 and 57.6 kbaud.
Pressing the “ ” key sets the value and shows the “RS 485 Baud Rate” screen (see Section 2.2).
3
2.3 RS 485 Parity
This screen allows the user to set Parity & number of stop bits of RS 485 port.
Pressing “ ” key accepts the present value and advances to “Quit
Communication Parameters” screen (see section 2.4).
Similarly, pressing “ ” key accepts the present value and advances to
“RS 485 Baud Rate” screen (see section 2.2).
Pressing the “ ” key advances to the “Parity & Stop bit Edit” mode &
keys “ ” and “ ” scrolls the value through:
nonE1 : no parity with one stop bit nonE2 : no parity with two stop bit
XX
EVEn : even parity with one stop bit odd : odd parity with one stop bit
Pressing “ ” key sets the value and advances to “RS 485 Parity Selection” screen (see Section 2.3).
18
TABLE 1.4 : 3 X and 4 X register addresses for Individual Harmonics
19
TABLE 1.4 Continued...
Address Address Parameter Start Address Hex 3X Start Address Hex 4X
Parameter
(3X) (4X) Number High Byte Low Byte High Byte Low Byte
Note: For 3P3W and 1P2W, phase-wise parameters are not available.
27
TABLE 1.6 : 3 X and 4 X register addresses for Digital Input & Output Parameters
Address Address Parameter Start Address Hex 3X Start Address Hex 4X
Parameter
(3X) (4X) Number High Byte Low Byte High Byte Low Byte
29
TABLE 2 : 3X and 4X register addresses for 32-bit Integer Energy
Address Address Para Start Address Hex 3X Start Address Hex 4X
Parameter
(3X) (4X) No. Hi Byte Lo Byte Hi Byte Lo Byte
30869 40869 35 Sys Total Reactive Energy OVF Count on update Rate* 03 64 03 64
30871 40871 36 Sys Total Apparent Energy OVF Count on update Rate* 03 66 03 66
30873 40873 37 Active Energy Import L1 03 68 03 68
30875 40875 38 Active Energy Import L2 03 6A 03 6A
30877 40877 39 Active Energy Import L3 03 6C 03 6C
30879 40879 40 Active Energy Export L1 03 6E 03 6E
30881 40881 41 Active Energy Export L2 03 70 03 70
30883 40883 42 Active Energy Export L3 03 72 03 72
30885 40885 43 Reactive Energy Capacitive L1 03 74 03 74
30887 40887 44 Reactive Energy Capacitive L2 03 76 03 76
30889 40889 45 Reactive Energy Capacitive L3 03 78 03 78
30891 40891 46 Reactive Energy Inductive L1 03 7A 03 7A
30893 40893 47 Reactive Energy Inductive L2 03 7C 03 7C
30895 40895 48 Reactive Energy Inductive L3 03 7E 03 7E
30897 40897 49 Apparent Energy L1 03 80 03 80
30899 40899 50 Apparent Energy L2 03 82 03 82
30901 40901 51 Apparent Energy L3 03 84 03 84
30909 40909 55 Total Active Energy L1 03 8C 03 8C
30911 40911 56 Total Active Energy L2 03 8E 03 8E
30913 40913 57 Total Active Energy L3 03 90 03 90
30915 40915 58 Total Reactive Energy L1 03 92 03 92
30917 40917 59 Total Reactive Energy L2 03 94 03 94
30919 40919 60 Total Reactive Energy L3 03 96 03 96
30921 40921 61 Total Apparent Energy L1 03 98 03 98
30923 40923 62 Total Apparent Energy L2 03 9A 03 9A
30925 40925 63 Total Apparent Energy L3 03 9C 03 9C
30927 40927 64 OVF Active Energy Import L1 03 9E 03 9E
30929 40929 65 OVF Active Energy Import L2 03 A0 03 A0
30931 40931 66 OVF Active Energy Import L3 03 A2 03 A2
30933 40933 67 OVF Active Energy Export L1 03 A4 03 A4
31
TABLE 2 Continued...
Address Address Para Start Address Hex 3X Start Address Hex 4X
Parameter
(3X) (4X) No. Hi Byte Lo Byte Hi Byte Lo Byte
31073 41073 137 Total Active Energy OVF Count L2 on update Rate* 04 30 04 30
31075 41075 138 Total Active Energy OVF Count L3 on update Rate* 04 32 04 32
31077 41077 139 Total Reactive Energy OVF Count L1 on update Rate* 04 34 04 34
31079 41079 140 Total Reactive Energy OVF Count L2 on update Rate* 04 36 04 36
31081 41081 141 Total Reactive Energy OVF Count L3 on update Rate* 04 38 04 38
31083 41083 142 Total Apparent Energy OVF Count L1 on update Rate* 04 3A 04 3A
31085 41085 143 Total Apparent Energy OVF Count L2 on update Rate* 04 3C 04 3C
31087 41087 144 Total Apparent Energy OVF Count L3 on update Rate* 04 3E 04 3E
31089 41089 145 External Counter 1 Value** 04 40 04 40
31091 41091 146 External Counter 2 Value** 04 42 04 42
31097 41097 149 External Counter 1 OVF** 04 48 04 48
31099 41099 150 External Counter 2 OVF** 04 4A 04 4A
31105 41105 153 Run Hour 04 50 04 50
31107 41107 154 On Hour 04 52 04 52
31113 41113 157 No of Interruption 04 58 04 58
31301 41301 200 Tariff1 Source1 Energy Count 05 14 05 14
31303 41303 201 Tariff1 Source2 Energy Count 05 16 05 16
31305 41305 202 Tariff1 Source3 Energy Count 05 18 05 18
31307 41307 203 Tariff1 Source4 Energy Count 05 1A 05 1A
31309 41309 204 Tariff1 Source5 Energy Count 05 1C 05 1C
31311 41311 205 Tariff1 Source6 Energy Count 05 1E 05 1E
31313 41313 206 Tariff1 Source1 Energy OVF Count 05 20 05 20
31315 41315 207 Tariff1 Source2 Energy OVF Count 05 22 05 22
31317 41317 208 Tariff1 Source3 Energy OVF Count 05 24 05 24
31319 41319 209 Tariff1 Source4 Energy OVF Count 05 26 05 26
31321 41321 210 Tariff1 Source5 Energy OVF Count 05 28 05 28
31323 41323 211 Tariff1 Source6 Energy OVF Count 05 2A 05 2A
31325 41325 212 Tariff2 Source1 Energy Count 05 2C 05 2C
31327 41327 213 Tariff2 Source2 Energy Count 05 2E 05 2E
31329 41329 214 Tariff2 Source3 Energy Count 05 30 05 30
34
TABLE 2 Continued...
Address Address Para Start Address Hex 3X Start Address Hex 4X
Parameter
(3X) (4X) No. Hi Byte Lo Byte Hi Byte Lo Byte
Note:
*1. The values are updated depending on update rate which is settable by user.
For example, if user set update rate 15 min, then the values on these registers (marked with *) will get updated
on every 15 min.
**2. External Counter gets updated when Digital Input is configured in Pulse Mode.
3. OVF stands for OverFlow.
4. For 3P3W and 1P2W System, phase-wise parameters are not available.
35
3.2 Accessing 4 X register for Reading & Writing Settings:
Each setting is held in the 4X registers. ModBus code 03 is used to read the current setting & code 16 is used to
write/change the setting. Refer TABLE 3 for 4X Register addresses.
Example: Reading System type
System type: Start address = 1772 (Hex)
Number of registers = 02
Note: Number of registers = Number of Parameters x 2
Query :
Device Address 01 (Hex) Start Address High : Most significant 8 bits of starting address
of the parameter requested.
Function Code 03 (Hex) Start Address Low : Least significant 8 bits of starting address
Start Address High 17 (Hex) of the parameter requested.
Start Address Low 72 (Hex) Number of register High : Most significant 8 bits of Number of
Number of Registers High 00 (Hex) registers requested.
Number of register Low : Least significant 8 bits of Number of
Number of Registers Low 02 (Hex) registers requested.
CRC Low E4 (Hex) (Note : Two consecutive 16 bit register represent one
CRC High 09 (Hex) parameter.)
36
Example : Writing System type
System type : Start address = 1772 (Hex)
Number of registers = 02
Note: Number of registers = Number of Parameters x 2
Response:
Device Address 01 (Hex) Start Address High : Most significant 8 bits of starting address of
the parameter requested.
Function Code 10 (Hex)
Start Address Low : Least significant 8 bits of starting address
Start Address High 17 (Hex) of the parameter requested.
Start Address Low 72 (Hex) Number of register High : Most significant 8 bits of Number of
Number of Registers High 00 (Hex) registers requested.
02 (Hex) Number of register Low : Least significant 8 bits of Number of
Number of Registers Low registers requested.
CRC Low 61 (Hex) (Note : Two consecutive 16 bit register represent one
CRC High CA (Hex) parameter)
37
3.3 Accessing 4 X register for Long Energy Reading & Writing :
For setting Energy start count in long energy format following query format should be used for writing energy
start count. First, send query (at address 1790) to unlock the parameter.
Note: For parameter to be unlocked, refer TABLE 7 for energy parameter selection.
Response:
Device Address 01 (Hex) Start Address High : Most significant 8 bits of starting address of
the parameter requested.
Function Code 10 (Hex)
Start Address Low : Least significant 8 bits of starting address
Start Address High 17 (Hex) of the parameter requested.
Start Address Low 90 (Hex) Number of register High : Most significant 8 bits of Number of
Number of Registers High 00 (Hex) registers requested.
02 (Hex) Number of register Low : Least significant 8 bits of Number of
Number of Registers Low registers requested.
CRC Low 61 (Hex)
CRC High CA (Hex)
38
Once the Unlock query is sent, next send query for writing Energy start count.
For Example: Query for writing energy start count of 999999999 for System Active Import Energy
Note: Refer TABLE 2 for register address of the selected parameter.
Query: (Query enter System Active Energy Import)
Device Address 01 (Hex) Byte Count : Total number of data bytes received.
10 (Hex) Data register 1 High Byte : Most significant 8 bits of Data
Function Code register 1 of the parameter requested.
Starting Address High 03 (Hex) Data register 1 Low Byte : Least significant 8 bits of Data
Starting Address Low 20 (Hex) register 1 of the parameter requested.
Number of Registers High 00 (Hex) Data register 2 High Byte : Most significant 8 bits of Data
register 2 of the parameter requested.
Number of Registers Low 02 (Hex)
Data register 2 Low Byte : Least significant 8 bits of Data
Byte Count 04 (Hex) register 2 of the parameter requested.
Data Register- 1 High Byte 3B (Hex) (Note : Two consecutive 16 bit register represent one
Data Register- 1 Low Byte 9A (Hex) parameter.)
Data Register- 2 High Byte C9 (Hex)
Value( 3B ,9A, C9,FF ) represents 999999999.
Data Register- 2 Low Byte FF (Hex)
CRC Low 66 (Hex)
CRC High 10 (Hex)
Response:
Device Address 01 (Hex) Start Address High : Most significant 8 bits of starting address of
the parameter requested.
Function Code 10 (Hex)
Start Address Low : Least significant 8 bits of starting address
Start Address High 03 (Hex) of the parameter requested.
Start Address Low 20 (Hex) Number of register High : Most significant 8 bits of Number of
Number of Registers High 00 (Hex) registers requested.
02 (Hex) Number of register Low : Least significant 8 bits of Number of
Number of Registers Low registers requested.
CRC Low 61 (Hex) (Note : Two consecutive 16 bit register represent one
CRC High CA (Hex) parameter.)
39
TABLE 3 : 4 X register addresses
Address Parameter Read/ Modbus Start Addr. Hex Default
Parameter
(Register) No. Write High Byte Low Byte Value
46003 1 System Type R/Wp 17 72 3
46005 2 PT Primary R/Wp 17 74 500
46007 3 CT Primary R/Wp 17 76 5
46009 4 PT Secondary R/Wp 17 78 500
46011 5 CT Secondary R/Wp 17 7A 5
46013 6 System Frequency Selection R/Wp 17 7C 50
46019 9 Demand Integration Time R/Wp 17 82 8
46021 10 Energy Unit R/Wp 17 84 2
46023 11 Energy Digit Reset Count R/Wp 17 86 8
46027 13 Energy Update rate on MODBUS R/Wp 17 8A 15
46029 14 Impulse on Energy Selection R/Wp 17 8C 1
46031 15 Impulse Rate R 17 8E -
46033 16 Energy Para Select for Start Count R/Wp 17 90 0
46035 17 Enter Energy Start Count R/Wp 17 92 0
46037 18 Reset Parameters R/Wp 17 94 0
46039 19 Password R/Wp 17 96 0
46041 20 Factory Reset Mode R/Wp 17 98 0
46045 22 Number of Poles R/Wp 17 9C 2
46047 23 Auto Scroll R/Wp 17 9E 0
46049 24 Current Noise Cutoff (mA) R/Wp 17 A0 0
46051 25 Node Address R/Wp 17 A2 1
46053 26 RS485 Setup Code R/Wp 17 A4 4
46055 27 Register Order/Word Order R/Wp 17 A6 0
46057 28 Pulse Width R/Wp 17 A8 100
46059 29 Pulse Divisor R/Wp 17 AA 1
46061 30 Relay1 Output Select R/Wp 17 AC 0
46063 31 Relay1 Parameter Select R/Wp 17 AE 0
46065 32 Relay1 Limit1 Alarm Setting (Hi/Lo) R/Wp 17 B0 0
46067 33 Relay1 Limit1 Trip point R/Wp 17 B2 10
46069 34 Relay1 Limit1 Hysteresis R/Wp 17 B4 0.5
40
TABLE 3 Continued...
Address Parameter Read/ Modbus Start Addr. Hex Default
Parameter
(Register) No. Write High Byte Low Byte Value
46071 35 Relay1 Limit 2 Para select R/Wp 17 B6 0
46073 36 Relay1 Limit 2 Alarm Setting (High/Low) R/Wp 17 B8 0
46075 37 Relay1 Limit 2 Trip point R/Wp 17 BA 10
46077 38 Relay1 Limit 2 Hysteresis R/Wp 17 BC 0.5
46079 39 Relay1 Limit 3 Para select R/Wp 17 BE 0
46081 40 Relay1 Limit 3 Alarm Setting (High/Low) R/Wp 17 C0 0
46083 41 Relay1 Limit 3 Trip point R/Wp 17 C2 10
46085 42 Relay1 Limit 3 Hysteresis R/Wp 17 C4 0.5
46087 43 Relay1 Logic Operation Setting R/Wp 17 C6 0
46089 44 Relay1 Configuration (Energize/De-Energize) R/Wp 17 C8 1
46091 45 Relay1 Delay(On) R/Wp 17 CA 1
46093 46 Relay1 Delay(Off) R/Wp 17 CC 1
46095 47 Relay1 Energy Selection for Prepaid R/Wp 17 CE 0
46097 48 Relay1 Rate per energy unit for Prepaid R/Wp 17 D0 1
46099 49 Relay1 Topup Recharge for Prepaid R/Wp 17 D2 100
46101 50 Relay1 New Recharge for Prepaid R/Wp 17 D4 100
46103 51 Relay2 Output Select R/Wp 17 D6 0
46105 52 Relay2 Limit1 Para Select R/Wp 17 D8 0
46107 53 Relay2 Limit1 Alarm Setting (High/Low) R/Wp 17 DA 0
46109 54 Relay2 Limit1 Trip point R/Wp 17 DC 10
46111 55 Relay2 Limit1 Hysteresis R/Wp 17 DE 0.5
46113 56 Relay2 Limit 2 Para select R/Wp 17 E0 0
46115 57 Relay2 Limit 2 Alarm Setting (High/Low) R/Wp 17 E2 0
46117 58 Relay2 Limit 2 Trip point R/Wp 17 E4 10
46119 59 Relay2 Limit 2 Hysteresis R/Wp 17 E6 0.5
46121 60 Relay2 Limit 3 Para select R/Wp 17 E8 0
46123 61 Relay2 Limit 3 Alarm Setting (High/Low) R/Wp 17 EA 0
46125 62 Relay2 Limit 3 Trip point R/Wp 17 EC 10
46127 63 Relay2 Limit 3 Hysteresis R/Wp 17 EE 0.5
46129 64 Relay2 Logic Operation Setting R/Wp 17 F0 0
41
TABLE 3 Continued...
Address Parameter Read/ Modbus Start Addr. Hex Default
Parameter
(Register) No. Write High Byte Low Byte Value
46131 65 Relay2 Configuration (Energize/De-Energize) R/Wp 17 F2 1
46133 66 Relay2 Delay(On) R/Wp 17 F4 1
46135 67 Relay2 Delay(Off) R/Wp 17 F6 1
46137 68 Relay2 Energy Selection for Prepaid R/Wp 17 F8 0
46139 69 Relay2 Rate per energy unit for Prepaid R/Wp 17 FA 1
46141 70 Relay2 Topup Recharge for Prepaid R/Wp 17 FC 100
46143 71 Relay2 New Recharge for Prepaid R/Wp 17 FE 100
46229 114 Health Monitor Voltage Unbalance limit R/Wp 18 54 20
46231 115 Health Monitor Current Unbalance limit R/Wp 18 56 20
46233 116 Health Monitor Under Freq Limit R/Wp 18 58 95
46235 117 Health Monitor Under Voltage Limit R/Wp 18 5A 70
46237 118 Health Monitor Over Voltage Limit R/Wp 18 5C 120
46239 119 Health Monitor Over Current Limit R/Wp 18 5E 120
46241 120 Timer 1 Start Stop R/Wp 18 60 0
46243 121 Timer 2 Start Stop R/Wp 18 62 0
46337 168 Digital Input Debounce Time R/Wp 18 C0 100
46339 169 Digital Input 1 Mode R/Wp 18 C2 0
46341 170 Digital Input 2 Mode R/Wp 18 C4 0
46347 173 Digital Input 1 Pulse Multiplier R/Wp 18 CA 1
46349 174 Digital Input 2 Pulse Multiplier R/Wp 18 CC 1
46357 178 Firmware Version Number R 18 D4 -
46365 182 Backlite ON/OFF R/Wp 18 DC 1
46367 183 Contrast for both LCD/ Touch R/Wp 18 DE 3
46369 184 User screen enable R/Wp 18 E0 0
46371 185 User screen1 R/Wp 18 E2 1
46373 186 User screen2 R/Wp 18 E4 2
46375 187 User screen3 R/Wp 18 E6 3
46377 188 User screen4 R/Wp 18 E8 4
46379 189 User screen5 R/Wp 18 EA 5
46381 190 User screen6 R/Wp 18 EC 6
42
TABLE 3 Continued...
Address Parameter Read/ Modbus Start Addr. Hex Default
Parameter
(Register) No. Write High Byte Low Byte Value
46383 191 User screen7 R/Wp 18 EE 7
46385 192 User screen8 R/Wp 18 F0 8
46387 193 User screen9 R/Wp 18 F2 9
46389 194 User screen10 R/Wp 18 F4 10
46391 195 Tariff Selection Mode R/Wp 18 F6 1
46393 196 No of Tariff R/Wp 18 F8 2
46395 197 Tariff Energy Source 1 R/Wp 18 FA 0
46397 198 Tariff Energy Source 2 R/Wp 18 FC 1
46399 199 Tariff Energy Source 3 R/Wp 18 FE 2
46401 200 Tariff Energy Source 4 R/Wp 19 00 3
46403 201 Tariff Energy Source 5 R/Wp 19 02 4
46405 202 Tariff Energy Source 6 R/Wp 19 04 24
46407 203 Active Tariff R/Wp 19 06 1
46701 205 IP Address 1 R 1A 2C 192.168
46703 206 IP Address 2 R 1A 2E 11.11
46705 207 Subnet Mask 1 R 1A 30 255.255
46707 208 Subnet Mask 2 R 1A 32 255.0
46709 209 Default Gateway 1 R 1A 34 192.168
46711 210 Default Gateway 2 R 1A 36 1.1
46713 211 Server Port R 1A 38 502
NOTE: Wp - Write protected , R - Read only , R/Wp - Read & Write protected
43
Explanation for 4 X register :
NOTE: Writing any invalid values (non-applicable values) to any of the following locations will result in modbus error.
Address Parameter Description
46003 System Type This address is used to set the System type.
Write one of the following value to this address.
1 : 1 Phase 2 Wire
3 : 3 Phase 3 Wire
3 : 3 Phase 4 Wire.
46005 PT Primary This address allows the user to set PT Primary value (in terms of VL-L).
The settable range is 100 VL-L to 1200 kVL-L for all system types & also
depends on the per phase 1800MVA Restriction of power combined with
CT primary.
46007 CT Primary This address allows the user to set CT Primary value.
The settable range is 1 to 9999. It also depends on the per phase
1800 MVA Restriction of power combined with PT primary.
46009 PT Secondary This address is used to read and write the PT secondary value.
The settable range is 100-600VLL.
46011 CT Secondary This address is used to read and write the CT secondary value. Write one of the
following values to this address.
1: 1A CT secondary
5: 5A CT secondary
46013 System This address is used to set the frequency of the input.
Frequency Write 50 : For 50 Hz input 60 : For 60Hz input
Selection
46019 Demand Demand period represents demand time in minutes. The applicable values are
Integration Time ranging from 5 to 60.
46021 Energy Unit This address is used to set energy output in Wh,kWh & MWh.
Write one of the following value to this address.
1 : Energy in Wh. 2 : Energy in KWh.
3 : Energy in MWh.
46023 Energy Digit This address is used to set maximum energy count after which energy on
Reset Count modbus will roll over to zero. Valid values are 7, 8 and 9.
46027 Energy Update This address is used to specify update rate of energy in corresponding
Rate 3X registers. The valid values for update rate are from 1 to 60 min.
44
Address Parameter Description
46029 Impulse on This address is used to select the energy to which impulse is to be assigned.
Energy Selection Writing any other value will return an error. To assign the value refer TABLE 5.
46031 Impulse Rate This address allows the user to read the impulse rate which is calculated
depending on the nominal system power.
46033 Energy Para This address is used to select the parameter whose start count (initial value) is
Select for Start to be set. Refer TABLE 7.
Count
46035 Enter Energy This address is used to set the start count of the parameter selected in address
Start Count 46033. The start count of the parameter should be in the range specified in
TABLE 7.
46037 Reset This address is used to reset different parameters. Write specific value to this
Parameters register to reset the corresponding parameter. Following are the values to reset
various data.
1: Energy Reset 2: Demand Reset
3: System Min Values Reset 4: System Max Values Reset
5: Run hour & On hour Reset 6: No of Interruptions Reset
7: Reset All data 8: Tariff log Reset
9: DI External Energy Reset
46039 Password This address is used to set & reset the password.
Valid Range of Password can be set is 0000 - 9999.
1) If password lock is present & if this location is read it will return zero.
2) If password lock is absent & if this location is read it will return one.
3) If password lock is present & to disable this lock first send valid password to
this location then write “0000” to this location
4) If password lock is present & to modify 4X parameter first send valid
password to this location so that 4X parameter will be accessible for
modification.
5) If for in any of the above case invalid password is send then meter will return
exceptional error 2.
46041 Factory Reset This address allows the user to reset the instrument to factory settings. Refer
the Default Values in TABLE 3 for factory settings. Write 5555 at this address to
reset the instrument.
46045 Number of Poles This address is used to set the no. of poles of generator of which RPM
is to be measured. The value must be between 2 to 40 and a multiple of 2.
45
Address Parameter Description
46047 Auto scroll This address is used to activate or de-activate the auto scrolling.
Write 0: Deactivate 1: Activate
46049 Current Noise This address is used to set the noise current cutoff. The valid values ranges
Cut-off (mA) from 0 to 30 (mA).
46051 Node Address This register address is used to set Device address between 1 to 247 .
46053 RS485 Set-up This address is used to set the baud rate, Parity and Number of stop bits.
Code Refer to TABLE 4 for details.
46055 Word Order Word Order controls the order in which Multifunction Meter receives or sends
floating - point numbers:- normal or reversed register order. In normal mode, the
two registers that make up a floating point numbers are sent most significant bytes
first. In reversed register mode, the two registers that make up a floating point
numbers are sent least significant bytes first. To set the mode, write the value
‘2141.0’ into this register-the instrument will detect the order used to send this value
and set that order for all ModBus transaction involving floating point numbers.
46057 Pulse Width of This address is used to set pulse width of the Pulse output. Write one of the
Relay following values to this address:
60 : 60 ms 100 : 100 ms 200 : 200 ms
46059 Pulse Divisor This address is used to set pulse divisor of the Pulse output.
Write one of the following values to this address for energy unit Wh:
1 : Divisor 1 10 : Divisor 10 100 : Divisor 100 1000 : Divisor 1000
In energy unit kWh or MWh, divisor will be 1 by default.
46061 Relay 1 Output This address is used to select the Relay operation as None / Pulse / Limit /
Select Timer / Health Monitor / Pre Paid Energy.
Write one of the following values to this address.
0 : None 1 : Pulse 2 : Limit 3 : Timer
4 : Health Monitor 5 : Pre Paid Energy
46063 Relay 1 This address is used to assign the Parameter to Relay.
Parameter Pulse relay : Refer TABLE 8.
Select Limit - 1 relay : Refer TABLE 9.
Timer relay : Refer TABLE 6.
46065 Relay 1 Limit - 1 This address is used to set the alarm for the selected Limit -1 parameter
Alarm Setting 0 : High Alarm 1 : Low Alarm
46
Address Parameter Description
46067 Relay 1 Limit - 1 This address is used to set the trip point in %. Any value between 10 to 100 for
Trip Point Lo- alarm & 10 to120 for Hi-alarm can be written to this address. For energy
parameters, the valid range is 10-9999999. (refer TABLE 9).
46069 Relay 1 Limit - 1 This address is used to set the hysteresis between 0.5% to 50.0%.
Hysteresis
46071 Relay 1 Limit - 2 This address is used to assign the parameter for Limit 2 (refer TABLE 9) to
Para Select Relay 1.
46073 Relay 1 Limit - 2
Alarm Setting
Same as Relay 1 Limit - 1
46075 Relay 1 Limit - 2
Trip Point
47
Address Parameter Description
46093 Relay 1 Delay This address is used to set the Off delay in seconds in range of 1 to 9999 for
(Off) Limit and Timer Relay
46095 Relay 1 Energy This register address is used to assign the Parameter to Pre Paid Energy Relay.
Selection for Refer TABLE 8 for details.
Pre Paid
46097 Relay 1 Rate per This register address is used to assign unit (1 kilo) cost for the energy parameter
Energy Unit for in the range of 1 to 999.
Prepaid
46099 Relay 1 Topup This register address is used to assign topup recharge for the energy parameter
Recharge for in the range of 1 to 999999 when energy unit is set as “2” or “3” and 1 to 9999
Prepaid when energy unit is set as “1”.
46101 Relay 1 New This register address is used to assign new recharge for the energy parameter
Recharge for in the range of 1 to 999999 when energy unit is set as “2” or “3” and 1 to 9999
Prepaid when energy unit is set as “1”.
46103 Relay 2 Output
Select
46105 Relay 2
Parameter
Select
46107 Relay 2 Limit - 1
Alarm Setting
46109 Relay 2 Limit - 1
Trip Point
Same as Relay - 1
46111 Relay 2 Limit - 1
Hysteresis
46113 Relay 2 Limit - 2
Para Select
46115 Relay 2 Limit - 2
Alarm Setting
46117 Relay 2 Limit - 2
Trip Point
48
Address Parameter Description
46119 Relay 2 Limit - 2
Hysteresis
46121 Relay 2 Limit - 3
Para Select
46123 Relay 2 Limit - 3
Alarm Setting
46125 Relay 2 Limit - 3
Trip Point
46127 Relay 2 Limit - 3
Hysteresis
46129 Relay 2 Logic
Operation
Setting
46131 Relay 2
Configuration Same as Relay - 1
Select
46133 Relay 2 Delay
(On)
46135 Relay 2 Delay
(Off)
46137 Relay 2 Energy
Selection for
Pre Paid
46139 Relay 2 Rate per
Energy Unit for
Prepaid
46141 Relay 2 Topup
Recharge for
Prepaid
46143 Relay 2 New
Recharge for
Prepaid
49
Address Parameter Description
46229 Health Monitor This address is used to set the limit of voltage unbalance. Valid range is
Voltage 5% to 20%.
Unbalance limit
46231 Health Monitor This address is used to set the limit of current unbalance. Valid range is
Current 5% to 20% and to disable it, set 0.
Unbalance limit
46233 Health Monitor This address is used to set the under frequency limit. Valid range is 95% to 99%
Under Frequency of system frequency and to disable it, set 0.
Limit
46235 Health Monitor This address is used to set the under voltage limit. Valid range is 70% to 90% of
Under Voltage nominal and to disable it, set 0.
Limit
46237 Health Monitor This address is used to set the over voltage limit. Valid range is 105% to 120%
Over Voltage of nominal and to disable it, set 0.
Limit
46239 Health Monitor This address is used to set the over current limit. Valid range is 50% to 120%
Over Current of nominal and to disable it, set 0.
Limit
46241 Relay Timer 1 This address is used to start/stop the timer for Relay 1 in timer mode with
Start / Stop following options: 0: Stop 1: Start
46243 Relay Timer 2 This address is used to start/stop the timer for Relay 2 in timer mode with
Start / Stop following options: 0: Stop 1: Start
46337 Digital Input This address is used to set the De-bounce time of Digital Input. Valid range is
De-bounce Time 1 to 9999.
46339 Digital Input 1 This address is used to select mode of Digital Input 1. Write one of the following
Mode values to this address.
0: Status 1: Tariff* 2: Pulse
*Note : When DI is selected in Tariff mode, then no input present on DI1 indicates
Tariff 1 and an input present on DI1 indicates Tariff 2.
46341 Digital Input 2 This address is used to select mode of Digital Input 2. Write one of the following
Mode values to this address.
0: Status 2: Pulse
50
Address Parameter Description
46347 Digital Input 1 This address is used to set the pulse multiplier of Digital Input 1 between
Pulse Multiplier 1 to 9999. This parameter is useful when DI is configured in Pulse Mode. The
Pulse count is available as “External Counter” on modbus (refer TABLE2).
46349 Digital Input 2 This address is used to set the pulse multiplier of Digital Input 2 between
Pulse Multiplier 1 to 9999. This parameter is useful when DI is configured in Pulse Mode. The
Pulse count is available as “External Counter” on modbus (refer TABLE2).
46357 Firmware Version This address is read only and displays the firmware version of the meter.
46365 Backlite ON/OFF This address is used to Turn ON or Turn OFF the backlit. Valid values are:
1: Backlit On 0: Backlit Off
46367 Contrast This address is used to change the contrast of the display. The options available
are 1 to 4, in increasing order of contrast.
46369 User Assignable This address is used to activate or deactivate the User Assignable Screen
Screen Enable feature which enables the user to select the screens to be displayed over the
screen. 0: Disable 1 to 10: Corresponding number of user assignable screens.
46371 to User Screens 1 These addresses are used to assign maximum 10 selectable screen numbers in
46389 to 10 corresponding sequence. User needs to put the combination of key number and
screen number to this address. Refer TABLE 11 for screen numbers.
For example, to select the screen number 3 of V/A key (key number 1), assign
103 to the corresponding user screen. Similarly, P key and Sys key have key
numbers 2 and 3, respectively.
46391 Tariff Selection This address is used to select the mode of Tariff. Valid values are:
Mode 0: Digital Input (This value is valid only when Digital Input 1 Mode is set as Tariff)
1: Modbus Command
When Di1 is selected in Tariff Mode, then no input present on DI1 indicates
Tariff 1 and an input present on DI1 indicates Tariff 2.
46393 Number of Tariff This address is used to select the number of Tariff. Valid values are:
1: Single Tariff 2: Dual Tariff
Note : Only Digital Input 1 can be used for Tariff Selection.
46395 to Tariff Energy These addresses are used to assign the energy parameters to six tariff sources.
46405 Source 1 to 6 Refer TABLE 8 for the energy parameters numbers.
46407 Active Tariff This address is used to select active tariff, only when Tariff selection mode is set
as “Modbus Command”. Write one of the following values to this address.
1: 1st Tariff 2: 2nd Tariff
51
Address Parameter Description
46701 IP Address 1 This address is read only and represents the high 16 bits of IP address.
46703 IP Address 2 This address is read only and represents the low 16 bits of IP address.
46705 Subnet Mask 1 This address is read only and represents high 16 bits of subnet mask address.
46707 Subnet Mask 2 This address is read only and represents low 16 bits of subnet mask address.
46709 Default gateway 1 This address is read only and represents high 16 bits of default gateway address.
46711 Default gateway 2 This address is read only and represents low16 bits of default gateway address.
46713 Server Port This address is read only and represents server port.
NOTE:
Changing system type, PT/CT ratio, Energy Output, Energy Digit Reset Count will reset the energy.
TABLE 4 : RS 485 Set-up Code
Baud Rate Parity Stop Bit Decimal
value
4800 NONE 1 0
4800 NONE 2 1
4800 EVEN 1 2
4800 ODD 1 3
9600 NONE 1 4
9600 NONE 2 5
9600 EVEN 1 6
9600 ODD 1 7
19200 NONE 1 8
19200 NONE 2 9
19200 EVEN 1 10
19200 ODD 1 11
38400 NONE 1 12
38400 NONE 2 13
38400 EVEN 1 14
38400 ODD 1 15 NOTE : Codes not listed in the TABLE 4
57600 NONE 1 16 may give rise to unpredictable results
57600 NONE 2 17 including loss of communication.
57600 EVEN 1 18 Exercise caution when attempting to
57600 ODD 1 19 change mode via direct Modbus writes.
52
TABLE 5 : Impulse Energy Selection
Parameter Parameter 3P3W 1P2W
3P4W
Number
0 None
1 System Active Energy
2 System Reactive Energy
3 System Apparant Energy
4 Active Energy L1
5 Active Energy L2
6 Active Energy L3
7 Apparant Energy L1
8 Apparant Energy L2
9 Apparant Energy L3
10 Reactive Energy L1
11 Reactive Energy L2
12 Reactive Energy L3
0 Unlimited
53
TABLE 7 : Energy Parameter Selection and Start Count
Parameter Parameter Range
Number
1 Sys Active Energy Import 1 to 999999999
2 Sys Active Energy Export 1 to 999999999
3 Sys Reactive Energy Cap. 1 to 999999999
4 Sys Reactive Energy Ind. 1 to 999999999
5 Sys Apparent Energy 1 to 999999999
7 Sys Active Energy Import Overflow Count 1 to 999999
8 Sys Active Energy Export Overflow Count 1 to 999999
9 Sys Reactive Energy Capacitive Overflow Count 1 to 999999
10 Sys Reactive Energy Inductive Overflow Count 1 to 999999
11 Sys Apparent Energy Overflow Count 1 to 999999
25 Sys Total Active Energy 1 to 999999999
26 Sys Total Reactive Energy 1 to 999999999
27 Sys Total Apparent Energy 1 to 999999999
28 Sys Total Active Energy Overflow Count 1 to 999999
29 Sys Total Reactive Energy Overflow Count 1 to 999999
30 Sys Total Apparent Energy Overflow Count 1 to 999999
37 Active Energy Import L1 1 to 999999999
38 Active Energy Import L2 1 to 999999999
39 Active Energy Import L3 1 to 999999999
40 Active Energy Export L1 1 to 999999999
41 Active Energy Export L2 1 to 999999999
42 Active Energy Export L3 1 to 999999999
43 Reactive Energy Capacitive L1 1 to 999999999
44 Reactive Energy Capacitive L2 1 to 999999999
45 Reactive Energy Capacitive L3 1 to 999999999
46 Reactive Energy Inductive L1 1 to 999999999
47 Reactive Energy Inductive L2 1 to 999999999
48 Reactive Energy Inductive L3 1 to 999999999
49 Apparent Energy L1 1 to 999999999
50 Apparent Energy L2 1 to 999999999
51 Apparent Energy L3 1 to 999999999
55 Total Active Energy L1 1 to 999999999
54
TABLE 7 Continued...
Parameter Parameter Range
Number
56 Total Active Energy L2 1 to 999999999
57 Total Active Energy L3 1 to 999999999
58 Total Reactive Energy L1 1 to 999999999
59 Total Reactive Energy L2 1 to 999999999
60 Total Reactive Energy L3 1 to 999999999
61 Total Apparent Energy L1 1 to 999999999
62 Total Apparent Energy L2 1 to 999999999
63 Total Apparent Energy L3 1 to 999999999
64 Overflow Active Energy Import L1 1 to 999999
65 Overflow Active Energy Import L2 1 to 999999
66 Overflow Active Energy Import L3 1 to 999999
67 Overflow Active Energy Export L1 1 to 999999
68 Overflow Active Energy Export L2 1 to 999999
69 Overflow Active Energy Export L3 1 to 999999
70 Overflow Reactive Energy Capacitive L1 1 to 999999
71 Overflow Reactive Energy Capacitive L2 1 to 999999
72 Overflow Reactive Energy Capacitive L3 1 to 999999
73 Overflow Reactive Energy Inductive L1 1 to 999999
74 Overflow Reactive Energy Inductive L2 1 to 999999
75 Overflow Reactive Energy Inductive L3 1 to 999999
76 Overflow Apparent Energy L1 1 to 999999
77 Overflow Apparent Energy L2 1 to 999999
78 Overflow Apparent Energy L3 1 to 999999
82 Total Active Energy Overflow Count L1 1 to 999999
83 Total Active Energy Overflow Count L2 1 to 999999
84 Total Active Energy Overflow Count L3 1 to 999999
85 Total Reactive Energy Overflow Count L1 1 to 999999
86 Total Reactive Energy Overflow Count L2 1 to 999999
87 Total Reactive Energy Overflow Count L3 1 to 999999
88 Total Apparent Energy Overflow Count L1 1 to 999999
89 Total Apparent Energy Overflow Count L2 1 to 999999
90 Total Apparent Energy Overflow Count L3 1 to 999999
55
TABLE 7 Continued...
Parameter Parameter Range
Number
200 Tariff1 Source1 Energy Count 1 to 999999999
201 Tariff1 Source2 Energy Count 1 to 999999999
202 Tariff1 Source3 Energy Count 1 to 999999999
203 Tariff1 Source4 Energy Count 1 to 999999999
204 Tariff1 Source5 Energy Count 1 to 999999999
205 Tariff1 Source6 Energy Count 1 to 999999999
206 Tariff1 Source1 Energy Overflow Count 1 to 999999
207 Tariff1 Source2 Energy Overflow Count 1 to 999999
208 Tariff1 Source3 Energy Overflow Count 1 to 999999
209 Tariff1 Source4 Energy Overflow Count 1 to 999999
210 Tariff1 Source5 Energy Overflow Count 1 to 999999
211 Tariff1 Source6 Energy Overflow Count 1 to 999999
212 Tariff2 Source1 Energy Count 1 to 999999999
213 Tariff2 Source2 Energy Count 1 to 999999999
214 Tariff2 Source3 Energy Count 1 to 999999999
215 Tariff2 Source4 Energy Count 1 to 999999999
216 Tariff2 Source5 Energy Count 1 to 999999999
217 Tariff2 Source6 Energy Count 1 to 999999999
218 Tariff2 Source1 Energy Overflow Count 1 to 999999
219 Tariff2 Source2 Energy Overflow Count 1 to 999999
220 Tariff2 Source3 Energy Overflow Count 1 to 999999
221 Tariff2 Source4 Energy Overflow Count 1 to 999999
222 Tariff2 Source5 Energy Overflow Count 1 to 999999
223 Tariff2 Source6 Energy Overflow Count 1 to 999999
NOTE : For 3P3W and 1P2W, phase-wise parameters are not available.
56
TABLE 8 : Parameters for Pulse Output / Pre Paid Energy / Tariff Energy
Parameter Parameter 3P4W 3P 3W 1P 2W
Number
0 Sys Wh import
1 Sys Wh export
2 Sys VARh import
3 Sys VARh export
4 Sys VAh
6 Active Energy Import L1
7 Active Energy Import L2
8 Active Energy Import L3
9 Active Energy Export L1
10 Active Energy Export L2
11 Active Energy Export L3
12 Reactive Energy Capacitive L1
13 Reactive Energy Capacitive L2
14 Reactive Energy Capacitive L3
15 Reactive Energy Inductive L1
16 Reactive Energy Inductive L2
17 Reactive Energy Inductive L3
18 Apparent Energy L1
19 Apparent Energy L2
20 Apparent Energy L3
24 Total Sys Active Energy
25 Total Sys Reactive Energy
26 Total Sys Apparent Energy
27 Total Active Energy L1
28 Total Active Energy L2
29 Total Active Energy L3
30 Total Reactive Energy L1
31 Total Reactive Energy L2
32 Total Reactive Energy L3
57
TABLE 9 : Parameters for Limit output
Parameter 3P 3P 1P Trip Point 100%
Parameter
Number 4W 3W 2W Set Range Value
0 None - -
1 Volts 1 10 - 120 % Vnom (L-N)
2 Volts 2 10 - 120 % Vnom (L-N)
3 Volts 3 10 - 120 % Vnom (L-N)
4 Current 1 10 - 120 % Inom
5 Current 2 10 - 120 % Inom
6 Current 3 10 - 120 % Inom
(3)
7 Watt 1 10 - 120 % Nom
8 Watt 2 10 - 120 % Nom (3)
(3)
9 Watt 3 10 - 120 % Nom
10 VA 1 10 - 120 % Nom (3)
(3)
11 VA 2 10 - 120 % Nom
12 VA 3 10 - 120 % Nom (3)
(3)
13 VAr 1 10 - 120 % Nom
14 VAr 2 10 - 120 % Nom (3)
15 VAr 3 10 - 120 % Nom (3)
16 PF1 10 - 90 % 90°
17 PF2 10 - 90 % 90°
18 PF3 10 - 90 % 90°
19 PA1 10 - 90 % 360°
20 PA2 10 - 90 % 360°
21 PA3 10 - 90 % 360°
22 Volts Average 10 - 120 % Vnom (2)
24 Current Average 10 - 120 % Inom
27 Watts sum 10 - 120 % Nom (3)
29 VA sum 10 - 120 % Nom
(3)
58
TABLE 9 Continued...
Parameter 3P 3P 1P Trip Point 100%
Parameter
Number 4W 3W 2W Set Range Value
38 Sys Wh Export 10 - 9999999 Nom
(3)
(3)
214 Reactive Energy Capacitive L3 10-9999999 Nom
215 Reactive Energy Inductive L1 10-9999999 Nom (3)
216 Reactive Energy Inductive L2 10-9999999 Nom (3)
217 Reactive Energy Inductive L3 10-9999999 Nom
(3)
(3)
219 Apparent Energy L2 10-9999999 Nom
220 Apparent Energy L3 10-9999999 Nom (3)
224 Total Sys Active Energy 10-9999999 Nom
(3)
Note : (1) Parameters 1,2,3 are L-N Voltage for 3P 4W & L-L Voltage for 3P 3W.
(2) For Frequency 0% corresponds to 45 Hz and 100% corresponds to 66 Hz.
(3) For 3P 4W and 1P2W the nominal value is VLN and that for 3P 3W is VLL.
(4) Nominal Value for power is calculated from Nominal Voltage and Current values.
Nominal Value is to be considered with set CT/ PT Primary values.
For 1P2W, L1 Phase values are to be considered as System values.
Trip Point for Energy Parameters is a whole (non-decimal) number.
For e.g. :
1) Health Status is valid for Three Phase system only
2) bit15, bit14, bit13, bit12, bit11, bit10, bit9 and bit8 will always be 00000000.
3) The fault parameter bit will be 1.
4) If only over current fault is present, then OC bit will 1.
5) Binary value of OC is 0000000010000000 and decimal value is 128.
6) This value will be shown in health status indication buffer (refer TABLE 1.6) at corresponding address.
65
Table 11.3 Power Parameters Screens :
Parameter On Display On Modbus
Parameters
No. 3P 4W 3P 3W 1P 2W 3P 4W 3P 3W 1P 2W
1 L1 VA-VAr-Watt
2 L2 VA-VAr-Watt
3 L3 VA-VAr-Watt
4 L1-L2-L3 Power Factor
5 L1-L2-L3 Degree
6 System VA-VAr-Watt
7 System VA-VAr-PF
8 L1 Max VA-VAr-Watt
9 L1 Min VA-VAr-Watt
10 L2 Max VA-VAr-Watt
11 L2 Min VA-VAr-Watt
12 L3 Max VA-VAr-Watt
13 L3 Min VA-VAr-Watt
14 L1-L2-L3 Max Power Factor
15 L1-L2-L3 Min Power Factor
16 L1-L2-L3 Max Degree
17 L1-L2-L3 Min Degree
18 L1-L2-L3 Displacement Power Factor
19 L1-L2-L3 Reactive Power Factor
20 L1-L2-L3 LF Factor SgnQ(1-(P/S))
21 L1-L2-L3 Distortion VAr
22 L1-L2-L3 Fundamental VAr
23 L1-L2-L3 Max Reactive Power Factor
24 L1-L2-L3 Min Reactive Power Factor
25 L1-L2-L3 Max LF Factor SgnQ(1-(P/S))
26 L1-L2-L3 Min LF Factor SgnQ(1-(P/S))
NOTE : The Display screens of Table 11.3 can be scrolled through P / Down Key.
66
Table 11.4 Voltage/Current Parameters Screens :
Parameter On Display On Modbus
Parameters
No. 3P 4W 3P 3W 1P 2W 3P 4W 3P 3W 1P 2W
1 L1-L2-L3 Voltage
2 L12-L23-L31 Voltage
3 L1-L2-L3 Current
4 Neutral Current
5 L1-L2-L3 Voltage %THD
6 L1-L2-L3 Current %THD
7 Current Reversal
8 Phase Rotation Error
9 Phase Absent Indication
10 System Voltage-Current-Frequency
11 L1-L2-L3 Max Voltage
12 L1-L2-L3 Min Voltage
13 L12-L23-L31 Max Voltage
14 L12-L23-L31 Min Voltage
15 L1-L2-L3 Max Current
16 L1-L2-L3 Min Current
17 Individual Harmonics V (upto 31st)
18 Individual Harmonics A (upto 31st)
NOTE : The Display screens of Table 11.4 can be scrolled through V/A Key.
67
3.4 User Assignable Modbus Registers:
The Multifunction Instrument contains 20 user assignable registers in the address range of 0x1450 (35201) to
0x1476 (35239) for 3X registers (see TABLE 12) and address range of 0x1450 (45201) to 0x1476 (45239) for 4X
registers (see TABLE 12).
Any of the parameter addresses (3X register addresses and 4X register addresses of TABLE 1) accessible in the
instrument can be mapped to these 20 user assignable registers.
Parameters (3X and 4X registers addresses) that reside in different locations may be accessed by the single
request by re-mapping them to adjacent address in the user assignable registers area.
The actual address of the parameters (3X and 4X registers addresses) which are to be accessed via address
0x1450 to 0x1476 are specified in 4X Register 0x2710 to 0x2723 (see TABLE 13).
68
TABLE 13 : User Assignable mapping register ( 4X registers)
Address Modbus Start Address (Hex)
(4X) Assignable Register High Byte Low Byte
410001 Map Address for Assignable Register 1 27 10
410002 Map Address for Assignable Register 2 27 11
410003 Map Address for Assignable Register 3 27 12
410004 Map Address for Assignable Register 4 27 13
410005 Map Address for Assignable Register 5 27 14
410006 Map Address for Assignable Register 6 27 15
410007 Map Address for Assignable Register 7 27 16
410008 Map Address for Assignable Register 8 27 17
410009 Map Address for Assignable Register 9 27 18
410010 Map Address for Assignable Register 10 27 19
410011 Map Address for Assignable Register 11 27 1A
410012 Map Address for Assignable Register 12 27 1B
410013 Map Address for Assignable Register 13 27 1C
410014 Map Address for Assignable Register 14 27 1D
410015 Map Address for Assignable Register 15 27 1E
410016 Map Address for Assignable Register 16 27 1F
410017 Map Address for Assignable Register 17 27 20
410018 Map Address for Assignable Register 18 27 21
410019 Map Address for Assignable Register 19 27 22
410020 Map Address for Assignable Register 20 27 23
69
Assigning parameter to User Assignable Registers:
To access the Voltage2 (3X address 0x0002) and Power Factor1 (3X address 0x001E) through user assignable
register assign these addresses to 4x register (TABLE 13) 0x2710 and 0x2711 respectively.
70
Reading Parameter data through User Assignable Registers:
In assigning query, Voltage 2 & Power Factor 1 parameters were assigned to 0x2710 & 0x2711 (TABLE 13) which
will point to user assignable 3x registers 0x1450 and 0x1452 (TABLE 12). So to read Voltage2 and Power Factor1
data reading query should be as below.
}
Start Address Low 50 (Hex) Data Register- 1 High Byte 43 (Hex)
Number of Registers Hi 00 (Hex) Data Register- 1 Low Byte 5B (Hex) Voltage
Number of Registers Lo 04 (Hex) Data Register- 2 High Byte 4E (Hex) 2 Data
CRC Low F0 (Hex) Data Register- 2 Low Byte 04 (Hex)
}
CRC High 71 (Hex) Data Register- 3 High Byte 3F (Hex)
80 (Hex) Power
Data Register- 3 Low Byte
Start Address High : Most significant 8 bits of Factor 1
starting address of Userassignable register. Data Register- 4 High Byte 00 (Hex) Data
Start Address low :Least significant 8 bits of Data Register- 4 Low Byte 00 (Hex)
starting address of User assignable register. CRC Low 79 (Hex)
Number of register Hi : Most significant 8 bits of
Number of registers requested. CRC High 3F (Hex)
Number of register Lo : Least significant 8 bits
of Number of registers requested.
71
User Assignable mapping Registers User Assignable Data Registers
( 4X Registers TABLE 13 )
(Starting Address) (Starting Address)( 3X Registers TABLE 12 )
0x2710 Voltage 2 (0x0002) 0x1450 0x1450 0x1451
(16 bit) (16 bit)
0x1474 0x1475
0x2722 Current 1 (0x0006) 0x1474 (16 bit) (16 bit)
0x1476 0x1477
0x2723 VAh (0x0050) 0x1476 (16 bit) (16 bit)
To get the data through User Assignable Register go through the following steps:
1) Assign starting addresses (TABLE 1) of parameters of interest to “User assignable mapping registers” in a
sequence in which they are to be accessed (see Section “Assigning Parameter to User Assignable Registers”
of Section 3.4).
2) Once the parameters are mapped, data can be acquired by using “User assignable data register” Starting
address. i.e to access data of Voltage2, Power factor1,Wh import, Frequency send query with starting address
0x1450 with number of register 8 or individually parameters can be accessed. For example, if current1 is to be
accessed use starting address 0x01474. (see Section Reading Parameter data through User Assignable
Registers of Section 3.4).
72
4. Connection for Optional Pulse Output / Digital Input / RS 485 /
Ethernet Module (rear view of Multifunction Meter):
2.Up Side
- + - +
IN 1 IN 2
73
74