ETAP Short Circuit IEC
ETAP Short Circuit IEC
ETAP Short Circuit IEC
IEC Standard
Fault Current
•IIL-G
L G can range in utility systems from a few percent to
possibly 115 % ( if Xo < X1 ) of I3-phase (85% of all
faults).
•In industrial systems the situation IL-G > I3-phase is rare
rare.
Typically IL-G ≅ .87 * I3-phase
•In an industrial system, the three-phase fault condition
is frequently
f the only one considered, since this type off
fault generally results in Maximum current.
©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 4
Short-Circuit Phenomenon
v(t) i(t)
v(t) = Vm ∗ Sin(ωt + θ )
di
v(t) = Ri + L = Vm × Sin(ωt + θ ) (1)
dt
Solving equation 1 yields the following expression
e
RL
-
Vm Vm t
i(t) = × sin(ωt + θ - φ ) + × sin(θ - φ ) ×
Z Z
144424443 1444 424444 3
Steady State Transient
(DC Offset)
Off t)
DC Current
AC Decay Current
• Peak Short
Short-Circuit
Circuit Current (ip)
• Symmetrical Short
Short-Circuit
Circuit Breaking Current
(Ib)
• KT,S,K
KT,SO – Unit XFMR for faults in auxiliary
system, not between Gen & XFMR
• KG,S,K
KG,SO – With unit XFMR for faults in
auxiliary system, including points between
Gen & XFMR
• Near-To-Generator
Near To Generator Short
Short-Circuit
Circuit
– This is a short-circuit condition to which at least
one synchronous machine contributes a
prospective initial short-circuit current which is
more than twice the generator’s rated current, or
a short-circuit condition to which synchronous
and asynchronous motors contribute more than
5% of the initial symmetrical short-circuit current
( I"k) without
ith t motors.
t
©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 15
Near-To-Generator Short-Circuit
• Far-From-Generator
F F G t Short-Circuit
Sh t Ci it
– This is a short
short-circuit
circuit condition during which the
magnitude of the symmetrical ac component of
available short-circuit current remains essentially
constant.
• Required
q to account for:
• Transformer taps
• Breaking kA is more
conservative if the option
No Motor Decay is
selected
If = 3 × Ia 0
3 × VPr efault
If =
Z1 + Z 2 + Z0
if Zg = 0
I a 2 = − I a1
3 × VPr efault
If =
Z1 + Z 2
I a 2 + I a1 + I a 0 = 0 = I a
VPr efault
If =
⎛ Z0 Z2 ⎞
Z1 + ⎜⎜ ⎟⎟
⎝ Z0 + Z2 ⎠
if Zg = 0