ETAP Short Circuit IEC

Download as pdf or txt
Download as pdf or txt
You are on page 1of 46

Short-Circuit Analysis

IEC Standard

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC


Purpose of Short-Circuit
St di
Studies
• A Short
Short-Circuit
Circuit Study can be used to determine
any or all of the following:
– Verify
V if protective
t ti device
d i close
l and
d latch
l t h capability
bilit

– Verify protective device interrupting capability

– Protect equipment from large mechanical forces


(maximum fault kA)

– I2t protection for equipment (thermal stress)

– Selecting ratings or settings for relay coordination

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 2


Types of Short-Circuit Faults

©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 3


Types of Short-Circuit Faults
Types of SC Faults
•Three-Phase Ungrounded Fault
•Three-Phase
Th Ph Grounded
G d dFFaultlt
•Phase to Phase Ungrounded Fault
•Phase to Phase Grounded Fault
•Phase to Ground Fault

Fault Current
•IIL-G
L G can range in utility systems from a few percent to
possibly 115 % ( if Xo < X1 ) of I3-phase (85% of all
faults).
•In industrial systems the situation IL-G > I3-phase is rare
rare.
Typically IL-G ≅ .87 * I3-phase
•In an industrial system, the three-phase fault condition
is frequently
f the only one considered, since this type off
fault generally results in Maximum current.
©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 4
Short-Circuit Phenomenon

v(t) i(t)
v(t) = Vm ∗ Sin(ωt + θ )

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 5


v(t)
()
i(t)

di
v(t) = Ri + L = Vm × Sin(ωt + θ ) (1)
dt
Solving equation 1 yields the following expression

e
RL
-
Vm Vm t
i(t) = × sin(ωt + θ - φ ) + × sin(θ - φ ) ×
Z Z
144424443 1444 424444 3
Steady State Transient
(DC Offset)
Off t)

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 6


AC Current (Symmetrical) with
No AC Decay

DC Current

©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 7


AC Fault Current Including the
DC Offset (No AC Decay)

©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 8


Machine Reactance ( λ = L I )

AC Decay Current

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 9


Fault Current Including AC & DC Decay

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 10


IEC Short-Circuit
C l l ti (IEC 909)
Calculation
• Initial Symmetrical Short
Short-Circuit
Circuit Current (I"k)
(I k)

• Peak Short
Short-Circuit
Circuit Current (ip)

• Symmetrical Short
Short-Circuit
Circuit Breaking Current
(Ib)

• Steady-State Short-Circuit Current (Ik)

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 11


IEC Short-Circuit
C l l ti Method
Calculation M th d
• Ik”
Ik = Equivalent V @ fault location divided by
equivalent Z

• Equivalent V is based bus nominal kV and c


factor

• XFMR and machine Z adjusted based on


cmax, component Z & operating conditions

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 12


Transformer Z Adjustment
• KT -- Network XFMR

• KS,KSO – Unit XFMR for faults on system


side

• KT,S,K
KT,SO – Unit XFMR for faults in auxiliary
system, not between Gen & XFMR

• K=1 – Unit XFMR for faults between Gen &


XFMR
©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 13
Syn Machine Z Adjustment
• KG – Synchronous machine w/o unit XFMR

• KS,KSO – With unit XFMR for faults on


system side

• KG,S,K
KG,SO – With unit XFMR for faults in
auxiliary system, including points between
Gen & XFMR

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 14


Types of Short-Circuits

• Near-To-Generator
Near To Generator Short
Short-Circuit
Circuit
– This is a short-circuit condition to which at least
one synchronous machine contributes a
prospective initial short-circuit current which is
more than twice the generator’s rated current, or
a short-circuit condition to which synchronous
and asynchronous motors contribute more than
5% of the initial symmetrical short-circuit current
( I"k) without
ith t motors.
t
©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 15
Near-To-Generator Short-Circuit

©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 16


Types of Short-Circuits

• Far-From-Generator
F F G t Short-Circuit
Sh t Ci it
– This is a short
short-circuit
circuit condition during which the
magnitude of the symmetrical ac component of
available short-circuit current remains essentially
constant.

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 17


Far-From-Generator Short-Circuit

©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 18


Factors Used in If Calc
• κ – calc ip based on Ik”

• μ – calc ib for near-to-gen & not meshed network

• q – calc induction machine ib for near-to-gen & not


meshed network

• Equation (75) of Std 60909-0, adjusting Ik for


near to gen & meshed network
near-to-gen

• λmin & λmax – calc ik

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 19


IEC Short-Circuit Study Case

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 20


Types of Short-Circuits

When these options


are selected
• Maximum voltage factor is used

• Minimum impedance is used (all negative


tolerances are applied and minimum
resistance temperature is considered)

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 21


Types of Short-Circuits

When this option is


selected
• Minimum voltage factor is used

• Maximum impedance is used (all positive


tolerances are applied and maximum
resistance temperature is considered)

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 22


Voltage Factor (c)
• Ratio between equivalent voltage &
nominal voltage

• Required
q to account for:

• Variations due to time & place

• Transformer taps

• Static loads & capacitances

• Generator & motor subtransient behavior


©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 23
Calculation Method

• Breaking kA is more
conservative if the option
No Motor Decay is
selected

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 24


IEC SC 909 Calculation

©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 25


Device Duty Comparison

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 26


Mesh & Non-Mesh If
• ETAP automatically determines mesh & non-
meshed contributions according to individual
contributions

• IEC Short Circuit Mesh Determination


Method – 0,
0 11, or 2 (default)

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 27


L-G Faults

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 28


L-G Faults
Symmetrical Components

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 29


Sequence Networks

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 30


L-G Fault Sequence
N t
Network
kC Connections
ti

If = 3 × Ia 0
3 × VPr efault
If =
Z1 + Z 2 + Z0
if Zg = 0

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 31


L-L Fault Sequence Network
C
Connections
ti

I a 2 = − I a1
3 × VPr efault
If =
Z1 + Z 2

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 32


L-L-G Fault Sequence
N t
NetworkkC
Connections
ti

I a 2 + I a1 + I a 0 = 0 = I a
VPr efault
If =
⎛ Z0 Z2 ⎞
Z1 + ⎜⎜ ⎟⎟
⎝ Z0 + Z2 ⎠
if Zg = 0

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 33


Transformer Zero Sequence Connections

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 34


Solid Grounded Devices
and
d L-G
L G Faults
F lt
Generally a 3 - phase fault is the
most severe case. L - G faults can be
greater if :
Z1 = Z 2 & Z 0 < Z1
If this conditions are true then :
I f3φ < I f 1φ
This may be the case if Generators or
Y/Δ Connected transformer are solidly
Y/Δ solidl
grounded.

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 35


Zero Sequence Model
• Branch susceptances and static
loads including capacitors will be
considered when this option is
checked
• Recommended by IEC for
systems with isolated neutral
neutral,
resonant earthed neutrals &
earthed neutrals with earth fault
factor > 1.4

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 36


Unbalanced Faults Display
&R
Reports
t
Complete reports that include individual
branch contributions for:
•L-G Faults
•L-L-G Faults
L L Faults
•L-L

One-line diagram displayed results that


include:
•L-G/L-L-G/L-L fault current
contributions
•Sequence voltage and currents
•Phase Voltages

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 37


Transient Fault Current
C l l ti (IEC 61363)
Calculation
Total Fault Current Waveform

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 38


Transient Fault Current
C l l ti (IEC 61363)
Calculation
Percent DC Current Waveform

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 39


Transient Fault Current
C l l ti (IEC 61363)
Calculation
AC Component of Fault Current Waveform

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 40


Transient Fault Current
C l l ti (IEC 61363)
Calculation
Top Envelope of Fault Current Waveform

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 41


Transient Fault Current
C l l ti (IEC 61363)
Calculation
Top Envelope of Fault Current Waveform

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 42


IEC Transient Fault Current
C l l ti
Calculation

©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 43


Unbalanced Faults Display
&R
Reports
t
Complete reports that include individual
branch contributions for:
•L-G Faults
•L-L-G Faults
•L L Faults
•L-L

One-line diagram displayed results that


include:
•L-G/L-L-G/L-L fault current
contributions
Sequence voltage and currents
•Sequence
•Phase Voltages

©1996-2010 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 44


©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 45
©1996-2009 Operation Technology, Inc. – Workshop Notes: Short-Circuit IEC Slide 46