Electrical Power Lab..2
Electrical Power Lab..2
Prepared by
2023-2024
Abstract
The electrical power systems laboratory
designed to directly apply theory learned in lectures to devices that will be studied in
the laboratory. The Lab focuses on all aspects of electrical power systems: power
generation, transmission and distribution lines, protection systems, electric power
management systems and a wide range of electrical measurement systems. Research
projects carried out in this laboratory include generation, transmission and distribution
of electrical energy and all facilities that guarantee the safe supply of electrical energy.
In addition to the monitoring, control and supervision systems that are studied and
followed in this laboratory.
Objectives
The laboratory course is intended to provide practical understanding of power system
operation, control and protection. The main goal is to enable students to apply and test
theoretical knowledge they mastered in previous years of studies. The laboratory
course enables them to develop practical skills in various fields of power engineering
References
1- Glover, J. D., Sarma, M. S., & Overbye, T. (2012). Power system analysis & design, SI version.
Cengage Learning.
2- 2- Saadat, H. (1999). Power system analysis (Vol. 2). McGraw-hill.
3- 3- Horowitz, S. H., & Phadke, A. G. (2014). Power system relaying. John Wiley & Sons
Chapter 1
From equation, it is seen that given a particular alternator operating at synchronous speed, the single
factor under the user‟s control is Φ (rotoric excitation).
The rate of rotation of the magnetic fields in the machine is related to the stator electrical frequency
by the following Equation:
The voltage induced in a given stator phase depends on the flux Ф in the machine, the frequency or
speed of rotation, and the machine's construction by the following Equation :
EA = K Ф ω
Synchronous Generator Equivalent Circuit
The per-phase equivalent circuit of this machine is shown in the Figure below
If more load is added at the same power factor, then |IA| increases but remains at the same angle ϴ
with respect to VФ. It is seen that as the load increases, the voltage VФ decreases rather sharply.
Automatic Voltage Regulator (AVR) The generator excitation system maintains generator voltage
and controls the reactive power flow. The automatic voltage regulator (AVR) takes the fluctuate
voltage and changes them into a constant voltage. The fluctuation in the voltage mainly occurs due
to the variation in load on the supply system. The variation in voltage damages the equipment of the
power system.
Objectives:
Figure 1 shows a synchronous generator G1 supplying power to a load, with another generator G2,
about to be paralleled with G1, by closing the switch S1. If the switch is closed arbitrarily at some
moment, the generators are liable to be severely damaged, and the load may lose power. If the
voltages are not exactly the same in each conductor being tied together, there will be a very large
current flow when the switch is closed. To avoid this problem, each of the three phases must have
exactly the same voltage magnitude and phase angle as the conductor to which it is connected. In
other words, the voltage in phase a must be exactly the same as the voltage in phase a', and so forth
for phases b-b' and c-c'.
The conditions required for paralleling two Alternators:
1. Equal phase sequence: the voltage triads of the
generators must run in the same direction. The direction is pre-set by the proper
connections and checked with the
- lamp method. If the 2 triads do not run in the same direction, the 3 lamps never
light off simultaneously.
2. Equal frequencies: This can be seen in the frequency meters of each generator.
Actually, G2 is set at a little higher speed than G1 (this because when “taking
load”, the prime mover will naturally drop the rpm).
4. Equal phase angles: the phase angles of the two a phases must be equal. It is
obvious that if the rotation speeds of both machines are exactly equal, the phases
will be never be equal.
Parallel Operation of a Synchronous Generator
Objectives:
1. To understand the conditions required to parallel synchronous generator with mains.
2. To understand the procedures for paralleling synchronous generator with mains.
3. To understand the effect of increasing the frequency of the generator on the system.
4. To understand the effect of increasing the field current of the generator on the
system
Experiment (1)
Synchronous Generator Operating Alone
prepared by :
OBJECTIVE
DISCUSSION
Saturation in the iron means that there will be a smaller increase in flux for
a given increase in DC field current. Because the generated voltage is
directly related to the magnetic flux intensity, it can be used as a measure
of the degree of saturation.
The three phases of the alternator are mechanically spaced at equal intervals
from each other, and therefore, the respective generated voltages are not in
phase, but are displaced from each other by 120 electrical degrees.
Refer to the figr (56-1) , to obtain the list of equipment required to perform this exercise
PROCEDURE
CAUTION!
Figure 56-1.
G 2. a. Couple the squirrel-cage motor to the alternator with the timing belt.
b. Set the alternator field rheostat at its full cw position (for zero
resistance). Open switch S.
c. Set the power supply voltage control at its full ccw position (for zero DC
voltage).
b. With zero DC excitation measure and record E1, E2, and E3 (use thelowest
ranges of the voltmeters).
E1 = V ac, E2 = V ac, E3 = V ac
c. Explain why there is an AC voltage generated in the absence of DC
excitation.
G 4. a. Close the switch S.
c. Measure and record in Table 56-1 the three generated voltages E1, E2and E3.
e. Return the voltage to zero and turn off the power supply.
I1 E1 E2 E3 Eac
(amps) (volts) (volts) (volts) (avg.)
0.05
0.10
0.15
0.20
0.25
0.30
0.35
0.40
0.50
Table 56-1.
G 5. Calculate and record in Table 56-1 the average output voltage of the
alternator for each of the listed DC currents.
d. Turn on the power supply. Measure and record the generated voltages
across each of the wye connected stator windings.
E1 to 4 = V ac, E2 to 5 = V ac
E3 to 6 = V ac
e. Return the voltage to zero and turn off the power supply.
f. Compare the results of (a) and (d). Do the results correspond to what
you would expect to find coming from a normal three-phase power
supply?
G Yes G No
G 7. Using your Synchronizing Module, connect the circuit shown in Figure
56-2.Note that the switch is wired to present a dead short across the
alternator windings when it is closed.
Figure 56-2.
I1 = A dc
I2 = A ac
I1 = A dc, I2 = A ac
g. Return the voltage to zero and turn off the power supply.
REVIEW QUESTIONS
E= V ac
E= V ac
e) Explain why the voltage increases less rapidly as the DC current increases.
Figure 56-3.
2. Comment on the reasons for not operating an alternator near the knee of its
saturation curve.
The voltage regulation of an alternator or synchronous generator is defined as the rise in the terminal voltage when the
load is decreased from full-load rated value to zero. The speed and field current of the alternator remain constant.
In other words, the voltage regulation of the alternator can be defined as the change in terminal voltage from no-load
to full load rated value divided by the full-load rated voltage, i.e.,
Where,
The voltage regulation of an alternator depends upon the power factor of the load, i.e.,
An alternator operating at a unity power factor has a small positive voltage regulation.
An alternator operating at a lagging power factor has a large positive voltage regulation.
An alternator operating at lower leading power factors, the voltage rises with increase of the load and hence, the voltage regulation is
negative.
For a certain leading power factor, the full-load voltage regulation is zero. In this case, both the full-load and no-load terminal voltages are
the same.
The direct load test of alternator for determining the voltage regulation is suitable only for small alternators of power
rating less than 5 kVA.
For large alternators, the following three indirect methods are used to determine the voltage regulation of the
alternator, which are given as follows −
The synchronous impedance method or EMF method is used to determine the voltage regulation of the larger alternators. The
synchronous impedance method is based on the concept of replacing the effect of armature reaction by an imaginary
reactance
For an alternator,
= − = − ( + )…( )
At first, the synchronous impedance ( ) is measured and then, the value of actual generated EMF ( a) is calculated.
Thus, from the values of ( a) and V, the voltage regulation of the alternator can be calculated.
DC Resistance Test
Open-Circuit Test
Short-Circuit Test
DC Resistance Test
The circuit diagram for the DC resistance test is shown in Figure-1.
Consider the alternator is star-connected with the field winding open-circuited. Now, measure the DC resistance
between each pair of terminals either by using Whetstone’s bridge or ammeter-voltmeter method. The average of
three sets of resistance values Rt is taken. This value of Rt is divided by 2 to obtain the DC resistance per phase.
While performing the test, the alternator should be at rest, because the AC effective resistance is greater than DC
resistance due to skin effect. The AC effective resistance per phase may be obtained by multiplying the DC resistance
by a factor 1.20 to 1.75 depending upon the size of the alternator.
Open-Circuit Test
To perform the open-circuit test, the load terminals are kept open and the alternator is run at rated synchronous
speed. The circuit diagram of the open-circuit test is shown in Figure-2.
Initially, the field current is set to zero. Then, the field current is gradually increased in steps and the open-circuit
terminal voltage Et is measured in each step. The field current may be increased to obtain 25 % more than rated
voltage of the alternator.
A graph is plotted between the open-circuit phase voltage (( ℎ= /√3)) and the field current ( ). The obtained
characteristic curve is known as open-circuit characteristic (O.C.C) of the alternator (see Figure-3).
The shape of O.C.C. is same as a normal magnetization curve. When the linear portion of the O.C.C. is extended, it
given the air-gap line of the characteristic.
Short-Circuit Test
For performing the short-circuit test, the armature terminals are short-circuited through three ammeters as shown in
Figure-4.
Before starting the alternator, the field current should be decreased to zero. Each ammeter should have a range more
than the rated full-load value. Now, the alternator is run at synchronous speed. Then, the field current is gradually
increased in steps and the armature current is measured at each step. The field current may be increased to obtain
the armature currents up to 150 % of the rated value.
The field current ( ) and the average of the three ammeter readings is taken at each step. A graph is plotted between
the armature current ( a) and the field current ( ). The obtained characteristic is known as short-circuit characteristic
(S.C.C.) of the alternator and this characteristic is a straight line as shown in Figure-5.
Then, determine the value of short-circuit current ( ) at the field current that gives the rated voltage per phase of the
alternator. The synchronous impedance ( ) will then be equal to the ratio of the open-circuit voltage to the short-
circuit current at the field current which gives the rated voltage per phase, i.e.,
⇒Zs=AB(volts) / AC(amperes)…(3)
=√ ²− ²…(4)
Numerical Example
A 400 V, 35 kVA single-phase alternator has an effective armature resistance of 0.3Ω. An excitation current 15 A
produces 250 A armature current on short-circuit and an EMF of 380 V on open-circuit. Calculate the synchronous
impedance and synchronous reactance of the alternator.
Solution
Xs=√Z²s−R²a
=√1.52²−0.3² =1.49Ω
The circuit model of a cylindrical rotor synchronous generator or alternator is shown in Figure-1.
Let,
= + …(1)
∴ = − …(2)
Where,
Also, for a synchronous generator the excitation voltage ( ) leads the terminal voltage (V) by the load angle ( ).
Thus,
V=V∠0°then Ef=Ef∠δ
ﺟﺎﻣﻌﻪ اﻟﺒﻠﻘﺎء اﻟﺘﻄﺒﻴﻘﻴﺔ
ﻛﻠﻴﺔ اﻟﺤﺼﻦ اﻟﺠﺎﻣﻌﻴﺔ
Experiment (2)
The Alternator Under Load
prepared by :
OBJECTIVE
DISCUSSION
The output voltage of an alternator depends essentially upon the total flux in
the air-gap. At no-load, this flux is established and determined exclusively
by the DC field excitation.
Because the stator MMF has such an important effect upon the magnetic
flux, the voltage regulation of alternators is quite poor, and the DC field
current must continuously be adjusted to keep the voltage constant under
variable load conditions.
EQUIPMENT REQUIRED
Refer to the figr (57-1) , to obtain the list of equipment required to perform this exercise
PROCEDURE
CAUTION!
Figure 57-1.
G 2. a. Couple the DC motor to the alternator with the timing belt.
b. Set the DC motor field rheostat at its full cw position (for minimum
resistance).
c. Set the alternator field rheostat at its full ccw position (for maximum
resistance).
Note: This speed must be kept constant for the remainder of this
Experiment!
I1 = A ac, I2 = A dc
d. Open the three resistance load switches for no load on the alternator
and measure and record the no load E1 and I2. Remember to check the
motor speed and readjust to 1500 r/min if required.
E1 = V ac, I2 = A dc
e. Return the voltage to zero and turn off the power supply.
VNL- VFL
Regulation '
VFL
x 100%
= %
c. Repeat procedure 3 and record the full load values of I1 and I2.
I1 = A ac, I2 = A dc
E1 = V ac, I2 = A dc
e. Return the voltage to zero and turn off the power supply.
f. Calculate the alternator regulation with inductive loading.
= %
g. With an inductive load, does the stator MMF aid or oppose the rotor
MMF?
I1 = A ac, I2 = A dc
E1 = V ac, I2 = A dc
e. Return the voltage to zero and turn off the power supply.
= %
g. With an inductive load, does the stator MMF aid or oppose the rotor
MMF?
e. Return the voltage to zero and turn off the power supply.
G 7. a. Connect the circuit shown in Figure 57-2. Note that only one
of the alternator phases has a load.
Figure 57-2.
b. Turn on the power supply and adjust the DC motor rheostat for a motor
speed of 1500 r/min.
c. Adjust the DC excitation of the alternator until the voltage across the
2200 Ω load E1 = 380 V ac. Measure and record the two other phase
voltages E2 and E3.
E2 = V ac, E3 = V ac
d. Turn off the power supply without touching any of the variable controls.
e. Reconnect the three AC voltmeters so they will measure the voltages across each
of the three stator windings.
f. Turn on the power supply. Measure and record the voltages across each of the
alternator windings.
E1 to 4 = V ac
E2 to 5 = V ac
E3 to 6 = V ac
g. Return the voltage to zero and turn off the power supply.
G Yes G No
REVIEW QUESTIONS
1. Explain why the alternator output voltage increases with capacitance loading.
G Yes G No
3. The rotor of an alternator, at rated power, dissipates more heat at a low power
factor (lagging) load than a high power factor load. Explain.
Alternator Synchronization
prepared by :
DISCUSSION
The frequency of a large electric power utility system is established by the speed of
rotation of many powerful alternators all connected by various tie-lines into the
total network. The collective inertia and power of these generators is so great that
there is no single load or disturbance which would be large enough to change
their speed of rotation. The frequency of an electric system is, therefore,
remarkably stable.
The next thing to watch for when we push gears together is to see that the tooth of
one meets the slot of the other. In electrical terms the voltage of the alternator must
be in phase with the voltage of the supply.
Finally, when meshing gears we always choose a tooth depth which is compatible
with the master gear. Electrically, the voltage amplitude of the alternator should be
equal to the supply voltage amplitude. With these conditions met, the alternator is
perfectly synchronized with the network and the switch between the two can be
closed.
PROCEDURE
CAUTION!
G 3. a. Turn on the power supply and, using your hand tachometer, adjust the
power supply output for a motor speed of approximately 1500 r/min.
E2 = V ac
G 4. a. Carefully adjust the DC motor speed until the beat frequency becomes
quite low.
b. Do all three lights become bright and then dark, at the same time?
G Yes G No
c. If they do not all become dark and then bright simultaneously, the
phase sequence is wrong. Turn off the power supply and interchange
any two of the leads coming from the stator.
d. Carefully adjust the motor speed until all three lights slowly darken and
then slowly brighten. Your alternator frequency is very nearly equal
to that of the power company.
e. When all of the lights are completely dark, the alternator and supply
voltages are in phase.
f. When all of the lights are fully bright, the alternator and supply voltages
are 180˚ degrees out of phase. (This is the “tooth-to-tooth”
condition, and the synchronizing switch should never be closed under
these conditions).
G 5. a. Close the synchronizing switch when all three lights are dark and note
the behavior of I1 at the moment of closure.
b. Close the synchronizing switch when all three lights are dim and
note the behavior of I1 at the moment of closure.
c. Close the synchronizing switch when all three lights are partially
bright and note the behavior of I1 at the moment of closure.
b. Adjust the motor speed until all three lamps are synchronized.
c. Close the synchronizing switch when all three lights are dimmest and
note the effect upon I1 at the moment of closure and after closure.
I1 at closure =
I1 after closure =
e. Return the voltage to zero and turn off the power supply.
e. Return the voltage to zero and turn off the power supply.
f. How can you remedy this situation without again reversing the
DC motor?