MANUAL For RDP 20-2600 - OMEGA AIR - EN - v1.5 - 23 - 01 - 30
MANUAL For RDP 20-2600 - OMEGA AIR - EN - v1.5 - 23 - 01 - 30
MANUAL For RDP 20-2600 - OMEGA AIR - EN - v1.5 - 23 - 01 - 30
manual
Refrigeration Dryer Series RDP 20 – 2600
Please read the instructions carefully before installation or use. The proper and safe operation of
the refrigeration air dryer is ensured only by following the recommendations and conditions
stated in the instructions.
20221128
For additional questions, contact the manufacturer and inform him of the information on the data
plate found on the front of the dryer.
3403165 - MANUAL for RDP 20-2600 - OMEGA AIR_EN_v1.5_23_01_30.docx
Dear customer!
Thank you for purchasing our product. In order for the product to serve well and reliably, please read
these installation and operating instructions carefully.
In order to avoid misuse of equipment and potential hazards for the operator, please read thoroughly
and strictly follow the instructions contained in this installation and operating manual.
Before packing and shipping, each unit of the RDP refrigeration air dryers is subjected to rigorous tests
to ensure that the factory defects are removed and all the functions of the device for which it was
designed checked.
After correctly installing the unit in accordance with the instructions in this manual, it will be ready for
use without the need for additional settings. The operation is fully automated, and maintenance is
limited to a few checks and cleanings, as shown in the continuation of this manual.
These instructions must always be present at the unit and be available for the entire operating life
of the device. The instructions are considered as an integral part of each refrigeration air dryer.
This manual provides the user, installer and maintenance technician with all the technical information
needed to install, operate and perform routine maintenance work to ensure long service life. If spare
parts are required, they must be original. Requests for SPARE PARTS and any information relating to
the unit must be sent to the distributor or to the nearest service canter, indicating the MODEL and
SERIAL NUMBER located on the data plate of the device.
Due to uninterrupted technical development, we reserve the right to introduce the necessary changes
without prior notice. If you need further explanation or clarification, contact the manufacturer or
distributor of the device.
2
Table of Contents
1 GENERAL INFORMATION ............................................................................................................................... 4
1.1 DEVICE INFORMATION ........................................................................................................................................ 4
1.2 INFORMATION ON THE SUPPLIER ........................................................................................................................... 4
1.3 BASIC .............................................................................................................................................................. 5
1.4 REFRIGERATION AIR DRYERS ................................................................................................................................. 5
1.5 PROPER USE ..................................................................................................................................................... 5
2 SAFETY INSTRUCTIONS .................................................................................................................................. 6
3 TECHNICAL SPECIFICATIONS .......................................................................................................................... 8
3.1 COMPONENTS................................................................................................................................................... 8
3.2 SPECIFICATIONS ................................................................................................................................................. 8
4 REFRIGERATION AIR DRYER OPERATION ..................................................................................................... 11
5 REFRIGERATION AIR DRYER COMPONENTS ................................................................................................. 12
5.1 COMPRESSOR ................................................................................................................................................. 12
5.2 CONDENSER ................................................................................................................................................... 12
5.3. HEAT EXCHANGER 3IN1 ................................................................................................................................... 12
5.4 CONTROLLER RDC 2 ........................................................................................................................................ 13
5.4.1 ELECTRIC SCHEME RDC 2 ............................................................................................................................... 14
5.4.2 RDC 2 PARAMETERS ..................................................................................................................................... 15
5.4.3 RDC 2 MODBUS COMMUNICATION ............................................................................................................... 17
5.5 EXPANSION VALVES .......................................................................................................................................... 18
5.6 ELECTRONIC CONDENSATE DRAIN ........................................................................................................................ 18
5.7 SAFETY FUNCTIONS .......................................................................................................................................... 21
5.7.1 LOW/HIGH - PRESSURE SWITCH ....................................................................................................................... 21
5.7.2 SAFETY FUNCTIONS OF RDC 2 ......................................................................................................................... 22
5.8 FILTER / DEHYDRATOR ...................................................................................................................................... 22
5.9 CAPILLARY TUBE .............................................................................................................................................. 22
5.10 PRESSURE SWITCH ......................................................................................................................................... 23
6 EFFICIENCY .................................................................................................................................................. 23
7 TRANSPORT ................................................................................................................................................. 23
8 STORAGE ..................................................................................................................................................... 24
9 INSTALLATION ............................................................................................................................................. 24
9.1 GENERAL REQUIREMENTS FOR INSTALLATION ........................................................................................................ 24
9.2 INSTALLATION POSITIONING ............................................................................................................................... 26
9.3 INSTALLATION PROCEDURE ................................................................................................................................ 27
10 START-UP .................................................................................................................................................. 28
10.1 BEFORE START-UP .......................................................................................................................................... 28
10.2 START-UP..................................................................................................................................................... 28
11 REMOVE FROM USE .................................................................................................................................. 29
12 MAINTENANCE .......................................................................................................................................... 29
13 TROUBLESHOOTING TECHNICAL PROBLEMS .............................................................................................. 30
14 SPARE PARTS ............................................................................................................................................. 32
15 WARRANTY ............................................................................................................................................... 33
16 MAINTENANCE NOTEBOOKS ..................................................................................................................... 34
17 DRAWINGS OF RDP REFRIGERATION AIR DRYERS ...................................................................................... 36
18 ELECTRO SCHEMES OF RDP REFRIGERATION AIR DRYER ............................................................................ 42
3
1 General information
Serial number:
Year of manufacture:
Date of installation:
Please fill in the fields carefully. Correct data enables proper and efficient maintenance of the device,
selection of suitable spare parts and technical support.
Name:
Address:
Phone / Fax:
e-mail:
4
1.3 Basic
Compressed air contains contaminants such as water, oil and particles. Impurities need to be removed
or their concentration reduced to an acceptable level according to the requirements of the application.
The ISO 8573-1 standard specifies the purity / quality of the air for contaminants. The humidity (water
vapor content) can be expressed in terms of Pressure Dew Point (PDP). Dew point is the temperature
at which the air is 100% saturated with moisture. When the air temperature falls below the dew point,
moisture condenses. Reduction of moisture content to the point of dew point +3°C can be achieved by
refrigeration air dryers.
Refrigeration air dryers are the best choice in all standard applications, where pressure dew point 3 °C
suffices. Examples of such applications are process air in the processing industry (pneumatic
equipment, wood industry, paint shop, chemical industry, pharmacy, etc.).
⚠ RDP refrigeration air dryers are designed for efficient and quality preparation of dry compressed
air. This device must only be used for the purposes for which it was designed. All other uses of the
device are considered incorrect.
⚠ The manufacturer is not liable under any circumstances for damage resulting from improper,
incorrect or unreasonable use of the device.
⚠ Only use genuine spare parts. Warranty or Reclamation cannot be claimed for damage or
malfunction of the device caused by the use of non-original parts.
5
2 Safety instructions
⚠ Improper use of the compressed air system and electrical installations can lead to injury or death.
⚠ Improper handling (transport, installation, use, maintenance) of a refrigeration air dryer can lead
to serious injury or death. The result of improper use may be damage to the device and/or reduced
efficiency of the dryer.
⚠ When operating the dryer, you must follow all relevant safety and accident prevention instructions,
all regulations and instructions for use. The RDP refrigeration air dryer was developed in accordance
with the generally recognized rules of engineering practice.
⚠ The user or operator of the refrigeration air dryer must be familiar with the installation,
commissioning and operation of the appliance.
⚠ All safety information is intended to ensure your personal safety. If you do not have experience
with such systems, contact the manufacturer or local supplier for technical assistance.
⚠ Before working on the dryer, ensure that the dryer is vented and not under pressure (this also
includes the closest components of the installation in front and behind the dryer) and that the dryer
is not connected to an electrical source.
⚠ Do not exceed the maximum operating pressure or operating temperature (information on the
data label).
⚠ The permissible operating temperatures and working pressures for the accessories of the
adsorption dryer are given in the technical documentation of this accessory. The maximum
temperature and pressure of the assembled system is the lowest maximum temperature or pressure
of any individual part of the system.
⚠ Ensure that the refrigeration air dryer is not subject to vibrations that can cause fatigue and
cracking of material.
⚠ Ensure that the fluctuation of the power supply voltage is below ±10% of the rated voltage.
Voltage fluctuations can cause damage to the device and/or reduced efficiency of the dryer.
⚠ All installation and maintenance work on the refrigeration air dryer can only be carried out by a
qualified and experienced specialist.
⚠ Vent the refrigeration air dryer system before performing any kind of installation or maintenance
work.
6
⚠ Ensure that the refrigeration air dryer is installed in accordance with specifications and without
mechanical loads.
⚠ When transporting the dryer, check and follow the local regulations for lifting and transporting
heavy objects.
⚠ In the event of fire, do not use extinguishing water on the dryer and nearby objects.
⚠ Wear suitable protective equipment: ear plugs, safety goggles, safety helmet, safety gloves and
safety shoes.
7
3 Technical Specifications
3.1 Components
3.2 Specifications
8
TECHNICAL SPECIFICATIONS
Max. operating pressure 16 barg (RDP 20-1900), 14 barg (RDP 2600)
Max. inlet air temperature 55 °C (for temperature ≠ 35 °C apply correction factor)
Operating ambient temperature 1 °C to 45 °C (for temperature > 25 °C apply correction factor)
Storage conditions 1 °C to 65 °C, <90 % relative humidity
Pressure dew point + 3 °C
Filter requirement (inlet) Prefilter 3 μm
Communication MODBUS
Digital input Remote ON/OFF
Digital output Alarm
Condenser type Air cooled
Max. noise level at 1m < 65 dbA
Compressor operation Non-cycling
Condensate drain Automatic (Zero loss type)
Refrigerant R134a
Protection class IP 20
Handling option Manual (RDP 20-100), Forklift (RDP 140-2600)
MATERIALS
Casing Carbon steel
Casing corrosion protection Epoxy powder paint
Evaporator Brazed plate stainless steel (RDP 20-1900), aluminium (RDP 2600)
Evaporator insulation Polyurethane foam
Condenser Copper tube, aluminium fins
Compressor Carbon steel
Refrigerant piping Copper
Controller enclosure Plastic
SIZES
Compressed air Electrical connection Ambient air Refrigerant Dimensions & Mass
Model (3)Flo Connection Pressure Power supply (4)Power/ Cooling Heat Type Mass WxLxH Net
w drop Consumption flow rejec.
m3/h bar Ph~V-Hz kW m3/h kW kg mm kg
RDP 20 20 G 3/8” BSP-F <0,2 1~230-50* 0,160 / 0,135 350 0,2 R134a 0,190 352 x 485 x 499 25
RDP 35 35 G 3/8” BSP-F <0,2 1~230-50* 0,170 / 0,135 350 0,3 R134a 0,230 352 x 485 x 499 25
RDP 50 50 G 3/4” BSP-F <0,2 1~230-50* 0,20 / 0,18 350 0,4 R134a 0,330 352 x 485 x 499 26
RDP 75 75 G 3/4” BSP-F <0,2 1~230-50/230-60 0,40 / 0,25 350 0,6 R134a 0,380 352 x 485 x 499 27
RDP 100 100 G 3/4” BSP-F <0,2 1~230-50/230-60 0,45 / 0,32 350 0,8 R134a 0,585 352 x 485 x 499 32
RDP 140 140 G 1” BSP-F <0,2 1~230-50/230-60 0,50 / 0,38 700 1,1 R134a 0,61 356 x 551 x 684 50
RDP 180 180 G 1” BSP-F <0,2 1~230-50* 0,60 / 0,45 700 1,5 R134a 0,71 356 x 551 x 684 52
RDP 235 235 G 1” BSP-F <0,2 1~230-50* 0,73 / 0,60 700 1,9 R134a 0,89 356 x 551 x 684 56
RDP 300 300 G 1 1/4” BSP-F <0,2 1~230-50/230-60 1,0 / 0,7 1100 2,4 R134a 1,07 495 x 588 x 826 84
RDP 380 380 G 1 1/4” BSP-F <0,2 1~230-50/230-60 1,1 / 0,8 1100 3,1 R134a 1,20 495 x 588 x 826 90
RDP 480 480 G 1 1/2” BSP-F <0,2 1~230-50/230-60 1,2 / 1,0 1100 3,9 R134a 1,31 495 x 588 x 826 99
RDP 600 600 G 2” BSP-F <0,2 1~230-50/230-60 1,3 / 1,1 2200 4,9 R134a 1,59 489 x 708 x 972 110
RDP 750 750 G 2” BSP-F <0,2 3~400-50/440-60 2,0 / 1,5 2200 6,1 R134a 2,19 489 x 708 x 972 120
RDP 950 950 G 2” BSP-F <0,2 3~400-50/440-60 2,4 / 1,9 2200 7,7 R134a 2,55 489 x 708 x 972 150
RDP 1150 1150 G 2 1/2” BSP-F <0,2 3~400-50/440-60 2,4 / 2,0 1900 9,4 R134a 3,49 670 x 858 x 1534 250
RDP 1300 1300 G 2 1/2” BSP-F <0,2 3~400-50/440-60 2,6 / 2,3 1900 10,6 R134a 3,25 670 x 858 x 1534 280
RDP 1500 1500 G 2 1/2” BSP-F <0,2 3~400-50/440-60 2,7 / 2,4 4600 12,2 R134a 5,00 670 x 858 x 1534 290
RDP 1900 1900 G 2 1/2” BSP-F <0,2 3~400-50/440-60 3,8 / 3,4 3800 15,5 R134a 5,30 662 x 856 x 1534 310
RDP 2600 2600 DN100 <0,2 3~400-50* 8,0 / 3,6 4000 16,1 R134a 11,0 870 x 1500,5 x 1893 500
↓ Larger sizes available upon request ↓
(3)
Nominal conditions: inlet flow 20 °C at 1 bara, ambient 25 °C, dryer inlet 35°C at 7 barg, 3 °C pressure dew point (-20,5 °C atmospheric).
(4)
For 60 Hz 20 % more than stated, consumption at nominal conditions.
* Special 60 Hz version available.
9
CORRECTION FACTORS
To calculate the correct capacity of a given dryer based on actual operating conditions, multiply the nominal
inlet flow by the appropriate correction factor(s). CORRECTED CAPACITY = NOMINAL FLOW CAPACITY x COP x
CAT x CIN x CDP
10
4 Refrigeration air dryer operation
The refrigeration air dryer is designed to remove moisture from the input air to achieve the desired
dew point at the exit.
All refrigeration air dryers described above operate according to the same principle. The operation of
the refrigeration air dryer can be divided into two main circuits: Air and refrigeration circuit.
c Separator
Air Circuit: Hot, moisture saturated air enters the 3in1 heat exchanger. The air then passes through
the evaporator, also called the air / refrigerant heat exchanger. The air temperature is reduced to
about 2 ° C, which causes condensation of the water vapor. The liquid is merged into larger droplets
and collected in a separator, from where the condensate drain removes it from the system. The cool
air without liquid water is returned through the air / air heat exchanger, where it is heated to
approximately 5 ° C lower temperature than the input air.
Refrigeration circuit: The refrigerant enters the compressor and then enters the condenser at high
pressure, where it transfers heat to the ambient air and condenses. The liquid then passes through the
capillary tube, where its pressure and consequently the temperature decreases. At low pressure, the
liquid refrigerant enters the heat exchanger where it receives heat from the inlet compressed air and
causes the evaporation of the refrigerant. The low-pressure gaseous refrigerant returns to the
compressor, which compresses it and starts the cycle again. During periods of reduced compressed air
load, the excess of the refrigerant automatically passes through the hot gas bypass valve back to the
compressor.
11
5 Refrigeration air dryer components
5.1 Compressor
The compressor sucks the gaseous phase of the refrigerant from the evaporator (low pressure side)
and compresses it to the condensation pressure (high pressure side). Built-in compressors are
manufactured by leading manufacturers and are designed for applications where high compression
ratios and high temperature differences are present. Hermetically sealed structure is tight and
provides high energy efficiency and long service life. The anti-vibration springs that carry the
compressor reduce sound emissions and transmission of vibrations. The refrigerant flowing through
the compressor to the cylinders of the compressor also cools the electric motor. Thermal protection
protects the compressor against overheating and overcurrent. The protection is automatically reset
when normal temperature operating conditions are reached.
5.2 Condenser
The condenser is a component in which the gas coming from the compressor cools, condenses and
changes the aggregate state from the gaseous to the liquid. The condenser is a pipe in which the
refrigerant is flowing, and on which fins are placed. The heat transfer is accelerated by an efficient fan.
It is important to ensure that the room temperature does not exceed the nominal values. It is also
important that the condenser unit is always clean and that dust or other impurities are not
accumulated on it.
The heat exchanger 3in1 combines air / air heat exchanger, air / coolant heat exchanger and
condensate separator. The compressed air counterflow in the air / air heat exchanger ensures
maximum heat transfer. A large cross-section of the flow channel in the heat exchanger 3in1 provides
low speed and low-pressure losses. The large dimensions of the heat exchanger air / refrigerant and
the counter-flow design enable the complete evaporation of the refrigerant (preventing the return of
the liquid to the compressor). A highly efficient condensate separator is located inside the heat
exchanger 3in1. No maintenance required, the effect of collecting drops ensures a high degree of
moisture separation.
12
5.4 Controller RDC 2
The controller can be started by holding SET + UP button for 3 seconds. For RDP 750-2600 it is
recommended that the controller remains in OFF state for at least 2 hours before start-up. At start-up,
the controller shows the message ‘’Comp time 1 min’’ and the compressor starts after a minute passes.
After the countdown is finished, the controller RDC 2 shows the temperature of the dew point reached
by the refrigeration air dryer in the normal operation. By pressing the UP (▲) button, the outlet
temperature of the compressor is displayed. By pressing the DOWN (▼) button, the condensation
temperature is displayed (the temperature sensor is connected) or the condensation pressure is
displayed (the pressure sensor is connected). In case of fault, an alarm will appear on the display. The
alarm automatically turns off when the dryer is restarted and is operating properly.
a) Sensors:
1) Tdew = Dew point temperature
2) Tcomp = Compressor temperature
3) Tcond ali pcond = Condensation temperature or pressure (4-20 mA)
b) Regulated components:
1) Fan (ON/OFF)
• Fan symbol is displayed when in ON state
2) Compressor (ON/OFF)
• Compressor symbol is displayed when in ON state
13
5.4.1 Electric scheme RDC 2
The controller has 3 outputs (230 V), for compressor, fan and drain. The other outputs are for alarm.
The alarm is triggered via opto triac, which can handle 600VAC/50mA. Suggested connection for alarm
terminals:
14
Controller can also be turned OFF/ON via In. Remote by changing the parameter 13 (Remote control)
from 0 to 1. When the circuit is connected, the controller goes to OFF state, when the circuit is
disconnected, the controller is in ON state. (See the attached scheme above).
For the MODBUS communication, the twisted pair cable needs to be screwed to the A and B terminals.
To communicate with the PC, an adapter is needed. The address for the MODBUS communication is 1.
Parameter Allowed to
Parameter Press UP Press DOWN Default
number name change
Increase Decrease
3 no 0
value value
Increase Decrease
4 no 5
value value
Min
Increase Decrease
Compressor yes
5 value value 1 min
OFF time
Increase Decrease
no
6 value value 2
Increase Decrease
7 no 5
value value
Increase Decrease
8 no 0
value value
Increase Decrease
no 0
9 value value
Increase Decrease
no 0
10 value value
Increase Decrease
11 no 40.0
value value
Increase Decrease
12 no 39.5
value value
Remote Increase Decrease
13 yes 0
Control value value
Increase Decrease
15 no 365
value value
15
In the following paragraph, a procedure to change the minimal compressor OFF time is shown.
To change the minimal compressor OFF time, you must choose programming parameter no. 5 and
change the value from default to the desired value. To do that you must:
• You will see the default parameter value (1 min). Change it to a desired value, if necessary, if
not skip the next step
Every other parameter can be changed by similar procedure. Differences are in parameter number and
in parameter value.
To reset the parameters in the WORKING status, you must first hold SET+UP for 3 seconds and you
move to STANDBY status. When in STANDBY status, you can reset the parameters to default values
by holding UP+DOWN for 3 seconds.
16
5.4.3 RDC 2 MODBUS communication
17
5.5 Expansion valves
SETTING
The hot gas bypass valve is factory set during the test
phase. As a rule, no additional settings are needed, but
if an intervention is required, an experienced cooler
technology engineer should do this. Figure 3: Bypass valve
EMD series drains are electronically controlled condensed water drains that discharges water trapped
in the lowest parts of compressed air installation out of the system. The EMD series drains consists of
a water tank, valve assembly and electronics. The water tank should be the lowest part of the
compressed air system where condensed water collects. In the tank, there is a water level sensor. This
way, electronics could detect the tank is full. Then, it operates the electromagnetic valve to discharge
condensed water from compressed air system. The valve is operated by electronics. It opens the valve
when a button on the electronics cover is pressed or when water level in the tank reaches threshold.
By pressing the test button, we could see if EMD is operational. Besides, the test button makes possible
to discharge water that has collected in a system during maintenance manually.
The main mode of operation is a water level triggered discharging. The valve opens when water level
in EMD’s tank reaches threshold and it closes back before the tank is empty. This way, only
condensed water is discharged and no compressed air is lost.
18
Electronic board
Test button
Long green flashes indicate that the tank is
almost full.
LED indicator
Maintenance
Test buttonand troubleshooting
Troubleshooting and maintenance procedures can only be performed by qualified personnel with
the necessary knowledge.
LEDany
Before indicator
maintenance or service parts make sure that:
- no part or device is powered and must not be connected to a power source
- that no part or device is under pressure and must not be connected to a compressed air
system under pressure,
Test- that
button
the maintenance staff fully and accurately read the operating instructions, and in
particular the chapters relating to safety at work.
LED indicator
For EMD to work reliably, a strainer should be cleaned regularly. The Strainer of EMD is located in the
entrance to a valve. Its purpose is to intercept larger solid particles that would clog valve. Cleanings
period depends on condition of compressed air system.
19
Strainer cleaning procedure
Keep to the safety rules when working with
pressure equipment.
First, close the valve then press the test button to
depressurize EMD.
In case there is no valve at condensate drain, use
valves at dryer’s input and output.
After powering EMD, it enters overload mode and afterwards, it enters alarm mode.
During power down, large amount of condensed water has collected in compressed air system. Hold the
test button until all the water is drained.
EMD enters alarm mode occasionally. But it gets back to normal mode immediately after all the water is
drained by holding the test button.
The reason might be extremely hot and moist day.
EMD is undersized and it should be replaced by bigger drain.
There is no LED signal although the valve could be opened by pressing test button.
The LED is not bright enough to be seen in daylight.
20
Fuse is blown.
Check integrity of electronics. Replace the fuse if there is no visible damage on electronics.
Air leaks through the drain pipe even when EMD is disconnected from power.
There might be debris in valve or valve may be damaged. Check integrity of strainer. The valve assembly
should be cleaned or replaced by authorized person.
Long flashes of green LED indicate full tank although the tank is empty.
Clean the water level sensor surface.
EMD is in alarm and valve opens, but there is no water or air drained.
Path between EMD’s tank and valve is clogged. Clean the tank, strainer and valve assembly. Replace
strainer or valve assembly when they are damaged.
Condensed water is not drained automatically. Instead, it is drained only when test button is pressed.
If the amount of drained water is small, then the water in tank hasn’t reached the threshold, yet.
If water is drained during pressing the test button, then we should check the piping in front of EMD.
Pipe’s inclination is too small or there may be debris in the pipe so that air in the EMD’s tank is trapped.
When the test button is pressed, this air escapes through drainage and makes place for condensed
water. Solution: clean pipe, build venting. Switch timer function on.
For protection against low/high-pressure, the low/high-pressure switch is added (RDP 750-2600).
Other safety functions are implemented in the controller.
LPS: Low-pressure protection device on the suction side of the compressor trips, if the pressure drops
below the pre-set value. The values are automatically reset when the nominal conditions are restored.
HPS: High-pressure protection device trips, if the pressure exceeds the pre-set value. The
values need to be manually reset when the nominal conditions are restored by pressing
the red rubber button.
21
5.7.2 Safety functions of RDC 2
Moisture and impurities can be present in the refrigeration circuit. This can reduce the lubrication of
the compressor and block the expansion valve or capillary tube. The dryer filter / dehydrator is located
in front of the capillary tube to remove moisture and impurities from the circulation system.
The capillary tube is located between the condenser and the evaporator and functions as a metering
device for reducing the pressure of the refrigerant. The pressure reduction is a design-based function.
The length and inner diameter of the capillary tube are precisely dimensioned, ensuring good
performance in all designed conditions.
22
5.10 Pressure switch
Set the switch for the fan motor to stop at 8,5 bar and start at 11,5 bar.
6 Efficiency
The efficiency of the refrigeration air dryer and the desired pressure dew point temperature depends
mainly on the right size of the RDP drier. To ensure efficient operation, the RDP refrigeration air dryers
are available in a large number of sizes and operating conditions.
• Working pressure
• Working volume flow
• Ambient temperature
• Inlet air temperature
• Dew point requirement
7 Transport
23
(7.7)
The refrigeration air dryer may be damaged during transport. In the event of damage to the interior
components of the dryer, the installation and use may result in injury or death! Check the dryer for
any visible damage after removing the packaging. If the refrigeration air dryer is damaged, contact the
transport operator and the dryer manufacturer.
8 Storage
In order to prevent damage to the refrigeration air dryer during storage, the following conditions must
be provided:
• The dryer should only be stored in a dry and enclosed space <90 % relative humidity.
• During storage, the ambient temperature must be within the temperature range of 1 ° C to
65 ° C. Contact the manufacturer for other storage temperatures.
• Make sure the refrigeration air dryer input and output are sealed.
In case you intend to store a dryer that has already been used, follow the instructions below:
9 Installation
The RDP refrigeration air dryer is designed to operate in an environment that ensures the following
conditions:
The air supplied to the refrigeration air dryer must satisfy the following conditions:
24
• The quality of compressed air 2 for particulate matter (if the dryer is equipped with a super
fine coalescent filter 0,01um)
• The quality of compressed air 2 for oil particles (if the dryer is equipped with a super fine
coalescent filter 0,01um)
• Absence of aggressive substances
25
9.2 Installation positioning
Below are the two most common configurations of installations in which the RDP refrigeration
air dryer is installed. The schemes below are not mandatory and they are just a sample. A
different arrangement of components is always possible.
Type A installation is recommended when the compressor operates at a reduced interruption rate and
total consumption that equals the flow of the compressor.
Type B installation is recommended when air consumption is usually repeated with conical values that
are much higher than the compressor flow. The capacity of the pressure vessel must be dimensioned
according to possible instantaneous needs (peak consumption).
26
9.3 Installation procedure
• The RDP refrigeration air dryer is typically delivered on the standard pallet on which it is
screwed with four screws.
• The RDP refrigeration air dryer can be lifted with forklift trucks.
• Remove the screws and the pallet before positioning the dryer at the desired location.
• The refrigeration air dryer should be installed in such a way that it is protected from weather
(for example, a compressor station).
• It is recommended to have 1 m of space around the dryer. This measure facilitates
maintenance.
• Make sure that the dryer is protected against vibration and mechanical wear.
• The dryer must stand firmly on a horizontal basis. The tilt of the unit must not exceed ± 3 °.
The best way to achieve these conditions is to fasten the dryer with screws onto a horizontal
base through the appropriate openings on the base. If the dryer is not installed properly, there
may be improper operation. Fastening the dryer with screws is not obligatory.
• RDP 20 - 235 drier models can be attached to
the wall with wall screws - the position of the
holes in the illustration is shown. (maximum
size M8)
• The pipe connections for the compressed air
in the front and back of the dryer must be
fitted with suitable valves that allow the
independent installation or removal of the
dryer from the system.
• Install a super fine coalescent filter on the
input side and pre-filter on the output side. It
only applies if the dryer has no built-in filters.
• Check that the air is properly treated before
the dryer (air conveyor, cyclone separator,
filters, condensate separators ...).
• Remove the plastic covers from the dryer's
input and output.
• Connect the air source to the dryer.
• The temperature and flow of the intake air
into the refrigeration air dryer must remain
within the limit values indicated on the
nominal label of the device.
• The pipelines of the system must be free of dust, rust, filings and other impurities and must
correspond to the flow of the dryer.
• It is also recommended that you arrange an air bypass line.
• Connect the dryer to the power source. Ensure that the supply voltage and the frequency
correspond to the data on the type label (± 5% acceptable tolerance for the supply voltage).
• Remove the packaging and other material that could hinder the dryer during normal
operation.
27
10 Start-up
Before start-up, check that the operating parameters correspond to the nominal values indicated on
the data label of the dryer (frequency, air pressure, air temperature, ambient temperature, ...). This
dryer has been fully tested, packaged and checked before shipping. Nevertheless, it may happen that
it is damaged during transport. Before starting it up for the first time, check its compliance, and for the
first few hours of operation, you should also carefully monitor its behaviour.
10.2 Start-up
• Connect the dryer to the power supply. For dryers RDP 750-1900, the power supply should
be connected to terminals 8, 10 and 12.
28
11 Remove from use
To switch off the refrigeration air dryer, move the switch to the OFF position - pos. O on the switch.
Disconnect the refrigeration air dryer from the power supply. Ensure that the dryer is not pressurized
(check bypass conduit valves). Disconnect the dryer from the compressed air system.
To protect the RDP refrigeration air dryer during storage, seal the input and the output of the dryer,
clean the front of the condenser and cover it with a cover.
12 Maintenance
During the maintenance work on the refrigeration air dryer, turn it off and wait 30 minutes for it to
cool down. Some components can reach high temperatures during operation.
Weekly check that the dew point shown on the controller is appropriate. Also check the correct
operation of the condensate drainage system. In case of impurities on the condenser, clean them.
Monthly clean the condenser with an air jet from the inside to the outside. Repeat the procedure from
the opposite direction, making sure that you do not damage the aluminium ribs of the condenser.
Annually check for potential refrigerant leakages. Measure and record the compressor and condensing
temperature.
The condensate drain is designed to to work for more than 4 000 000 condensate releases. In case of
malfunction use the condensate drain service kit for refurbishment.
29
13 Troubleshooting technical problems
During the maintenance work on the refrigeration air dryer, turn it off and wait for at least 30 minutes
for it to cool down. Some components can reach high temperature during operation. Avoid contact
with these components until they completely cool down.
30
● Check the dampening of the pipe connections.
.....................................................................................................
31
14 Spare Parts
PART RDP
DESCRIPTION
NUMBER 20 35 50 75 100 140 180 235 300 380 480 600 750 950 1150 1300 1500 1900 2600
1401365 1 1 1
1401437 1
1401431 1 1
1401369 1
1401439 1
1401440 1 1
Compressor
1401441 1 1
1401507 1
1401508 1 1 1
1401376 1
1401410 1
1401421 1
2101729 1 1 1
2101700 1 2
Fan & Condenser pack 2101701 1 1 2 2
2101732 1 1
2101802 2
2101732 2
2101822 1 1
Condenser 2101839 1 1 1
2101855 1
Fan 1101981 1
Fan motor 2101864 1 1 1 1 1
Fan blade 2101865 1 1 1 1 1
Fan diffuser 2101863 1 1 1 1 1
2204801 1 1 1 1 1 1 1 1
2204746 1 1
Hot gas by-pass valve 2204736 1 1 1
2204748 1 1 1
2204749 1 1 1 1
Expansion valve 2204771 1
Expansion valve connector 2204773 1
2101578 1 1 1 1
2100441 1 1
2100597 1 1
Filter 2101609 1 1
2300921 1 1 1 1
2300922 1 1 1 1
2300925 1
Fan regulation pressure switch 3000412 1 1 1 1 1 1 1 1 1 1 1
High pressure switch 3001154 1 1 1 1 1 1 1
Low pressure switch 3001111 1 1 1 1 1 1 1
RDC 2 Controller 2101826 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
Pressure transducer PP011 2101898 1
PT1000 probe PMT6-67 3000857 1
XEV 22 D Dixell Driver 2101897 1
NTC temperature probe 1m 4001120 3 3 3 3 3 3 3 3 3 3 3 3
NTC temperature probe 2m 4001141 3 3 3 3 3 3 3
Main 1 - phase Switch 1219579 1 1 1 1 1 1 1 1 1 1 1 1
3001135 1 1 1 1 1 1
Main 3 - phase Switch
3001156 1
Main 3 - phase Switch - handle 3001136 1 1 1 1 1 1 1
Electronic drain 321900860 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 - phase circuit breaker 3003681 1 1 1 1 1 1 1
3003715 1 1 1 1 1 1
3- phase circuit breaker
3003713 1
Phase protection relay 3003527 1
3001134 1 1 1 1 1 1
Contactor
3001162 1
3003680 1
3003682 1 1 1
Motor protection 3003683 1 1
3003695 1
3003699 1
32
15 Warranty
The warranty is valid for 12 months from the date of purchase and no more than 14 months from the
date of dispatch.
During this time, the parts that were originally incomplete will be repaired or replaced free of charge.
This does not include travel costs, accommodation and food for our technicians.
The guarantee excludes any possible direct or indirect damage to people, animals or property resulting
from improper use or inadequate maintenance of the device, and is limited solely to production errors.
When claiming a warranty, you must provide information from the identification label.
33
16 Maintenance notebooks
First installation
34
MAINTENANCE TYPE DATE SIGNATURE NOTES
35
17 Drawings of RDP refrigeration air dryers
RDP 20 - 100
36
RDP 140 - 235
37
38
RDP 300 - 480
RDP 600 - 950
39
40
RDP 1150 - 1900
RDP 2600
41
18 Electro schemes of RDP refrigeration air dryer
RDP 20 - 235
42
RDP 300 - 600
43
RDP 750- 1900
44
RDP 2600
45
46
EC Declaration of Conformity
Omega Air d.o.o. Ljubljana
Cesta Dolomitskega odreda 10
1000 Ljubljana
Slovenia
Declares that
Product: RDP
Model: RDP 20, RDP 35, RDP 50, RDP 75, RDP 100, RDP 140, RDP 180, RDP 235, RDP 300,
RDP 380, RDP 480, RDP 600, RDP 750, RDP 950, RDP 1150, RDP 1300, RDP 1500, RDP 1900,
RDP 2600
Description: Compressed air refrigeration dryer
A.Dobnikar
Technical manager
47