Load List Calculation
Load List Calculation
D(iv)E/F/G
Intermittent
Continious
Stand-by
REV. DESCRIPTION DATE DWN CHK APPD APPD APPD DWG NO. xxxx-xxxx SHT 01 OF 05 B
001
3.0 CALCULATION SHEET
MEASURED
POWER KW=A/D CONSUMED LOAD( EXISTING+ADDITIONAL) kvar=kW*tg phi
CURRENT
LOAD FACTOR
P=PVC
ITEM NO.
RESTARTING
class
at load
D(iv)E/F/G
MOTOR FACTOR
ESSENTIAL
ESSENTIAL
ABSORBED (=A/B)
RATING factor C at load X=XLPE OR EPR REMARKS
Intermittent
EQUIPMENT LOAD
DESCRIPTION
Stand-by
factor C
PANEL
NO. C RATING=SITE RATING
Load
A B D E F G
VITAL
IN DEC IN DEC. kW kvar kW kvar kW kvar
NON-
kW kW B DES D
ACT. D COS PHI DES. ACT. DES. ACT. DES. ACT. DES. ACT. DES. ACT. DES. ACT. NO. P/X SQ.MM RATING
33-SB-3303 SWITCHBOARD (0.415kV) LOAD SUMMARY C B
1 33-DB-3303-02 Distribution Board DG Building (0.415kV) 156.4 0.0 123.1 - 0.0 0.0 Calculated Value
2 33-DB-3303-01 Distribution Board Telemetry Building (0.415kV) 17.3 6.1 3.0 1.8 0.1 0.0 Calculated Value
3 24 Volts DC Battery Charger - 1, (Duty Power Supply) 5.00 5.00 1.00 0.95 0.85 5.26 3.26 Vendor Data
4 24 Volts DC Battery Charger - 2, (Standby Power Supply 5.00 5.00 1.00 0.95 0.85 5.26 3.26 Vendor Data
5 110 Volts DC Battery Charger - 1, (Duty Power Supply) 1.65 1.65 1.00 0.95 0.85 1.74 1.08 Vendor Data
6 110 Volts DC Battery Charger -2, (Standby Power Supply 1.65 1.65 1.00 0.95 0.85 1.74 1.08 Vendor Data
7 PACU-01 47 47 1.00 0.8 0.80 58.75 44.06 Calculated Value
8 PACU-02 47 47 1.00 0.8 0.80 58.75 44.06 Calculated Value
9 PACU CONTROL PANEL 0.5 0.5 1.00 0.95 0.85 0.53 0.33 Assumed Value
10 Outdoor Process Area Welding Socket Outlet 16 20 1.00 0.95 0.85 16.84 10.44 Calculated Value
11 Transformer Yard Welding Socket Outlet 8 10 1.00 0.95 0.85 8.42 5.22 Calculated Value
Total Plant Running Load (TPRL) : 292 KW 64 KVAR kW² + kvar² 299 kVA
(Est. X% SumC + Y% SumI) X = 100 % Y = 30 % TOTAL KVA 247.04 59.17 151.30 17.50 58.87 44.10 Power factor without compensation (cos phi) : 0.
(Existing+Additional) (Existing+Additional)
Total Plant Peak Load (TPPL) : 298 KW 69 KVAR kW² + kvar² 306 kVA Power factor with compensation (cos phi) : 0.
(Est. X% SumC + Y% SumI + Z% SumS) X = 100 % Y = 30 % Z = 10 % DES. 254 152 74 required capacitor rating [=kW (tg phi - tg phi)] : kvar
kVA = kW² + kvar²
(Existing+Additional) ACT.
NOTES:
APPD
REV. DESCRIPTION DATE DWN CHK APPD (FERNAS) APPD (QP) DWG NO. 2436-4107 SHT 02 OF 05 B
001
EQUIPMENT EFFICIENCY CABLE DETAILS
MEASURED
POWER KW=A/D CONSUMED LOAD( EXISTING+ADDITIONAL) kvar=kW*tg phi
CURRENT
MOTOR & LOAD FACTOR
ITEM NO.
P=PVC
class
RESTARTING
at load
D(iv)E/F/G
FACTOR
ESSENTIAL
ESSENTIAL
NON-MOTOR (=A/B)
ABSORBED factor C at load X=XLPE OR EPR REMARKS
Intermittent
LOAD RATING
DESCRIPTION factor C
Stand-by
PANEL
NO. C IN DEC. RATING=SITE RATING
Load
A B IN DEC D E F G
VITAL
kW kvar kW kvar kW kvar
NON-
kW kW B DES D
ACT. D COS PHI DES. ACT. DES. ACT. DES. ACT. DES. ACT. DES. ACT. DES. ACT. NO. P/X SQ.MM RATING
Aircond Load C B
1 Dewan AHU Motor-1 11.00 11.00 1.00 0.80 1.00 13.75 0.00 Calculated Value
2 Dewan AHU Motor -2 11.00 11.00 1.00 0.80 1.00 13.75 0.00 Calculated Value
3 Dewan Modular Chiller 104.00 104.00 1.00 0.90 1.00 Calculated Value
4 Admin 1.80 1.80 1.00 0.85 1.00 2.12 0.00 Calculated Value
5 Shop 6.40 6.40 1.00 0.80 1.00 8.00 0.00 Calculated Value
6 Kaunter 1.80 1.80 1.00 0.85 1.00 2.12 0.00 2.12 0.00 Calculated Value
Bowling Alley AHU-1 7.50 7.50 1.00 0.85 1.00 8.82 0.00 8.82 0.00 Calculated Value
Bowling Alley AHU-2 7.50 7.50 1.00 0.85 1.00 8.82 0.00 8.82 0.00 Calculated Value
Bowling Modular Chiller 86.00 86.00 1.00 0.85 1.00 101.18 0.00 101.18 0.00 Calculated Value
Total System Running Load (TRL) : 193 KW 0 KVAR kW² + kvar² 193 kVA
(Est. X% SumC + Y% SumI) X = 100 % Y = 30 % TOTAL 156.44 0.00 123.06 0.00 0.00 0.00 Power factor without compensation (cos phi) : 0.
(Existing)
Total System Peak Load (TPL) : 193 KW 0 KVAR kW² + kvar² 193 kVA Power factor with compensation (cos phi) : 0.
(Est. X% SumC + Y% SumI + Z% SumS) X = 100 % Y = 30 % Z = 10 % DES. 156 123 0 required capacitor rating [=kW (tg phi - tg phi)] : kvar
kVA = kW² + kvar²
(Existing) ACT.
NOTES:
MEASURED
POWER KW=A/D CONSUMED LOAD kvar=kW*tg phi
CURRENT
ABS MOTOR & LOAD FACTOR
P=PVC
Load class
RESTARTING
at load
D(iv)E/F/G
MOTOR FACTOR
ESSENTIAL
ESSENTIAL
EQU ORB NON-MOTOR (=A/B)
RATING factor C at load X=XLPE OR EPR REMARKS
Intermittent
RATING
DESCRIPTION factor C
Stand-by
LOA
PANEL
ENT B
A B IN DEC C IN DEC. D E F G RATING=SITE RATING
VITAL
kW kvar kW kvar kW kvar
NON-
D
NO.
kW kW B kW B DES D
ACT. D COS PHI DES. ACT. DES. ACT. DES. ACT. DES. ACT. DES. ACT. DES. ACT. NO. P/X SQ.MM RATING
33-DB-3303 Distribution Board Telemetry Building (0.415kV) C B
1 Outdoor Process Area Lighting 13.20 13.20 1.00 1.00 0.95 13.20 4.34 Calculated Value
2 Telemetry Bldg. Outdoor Lighting 0.60 0.60 1.00 1.00 0.95 0.60 0.20 Calculated Value
3 Telemetry Bldg. Indoor Lighting 2.12 2.12 1.00 1.00 0.95 2.12 0.70 Calculated Value
4 Telemetry Bldg. Exit and Emergency Lighting 0.12 0.12 1.00 1.00 0.95 0.12 0.04 Calculated Value
5 Telemetry Bldg. Indoor Socket Outlet 2.00 2.00 1.00 1.00 0.85 2.00 1.24 Calculated Value
6 Outdoor Process Area Socket Outlet 0.18 0.18 1.00 1.00 0.85 0.18 0.11 Calculated Value
7 Telecom Cabinet Power Supply Unit 0.80 0.80 1.00 1.00 0.85 0.80 0.50 Calculated Value
8 Power Supply of Batt. Rm Exhaust Fan Contol Pnl 0.50 0.50 1.00 1.00 0.85 0.50 0.31 Calculated Value
9 Telecom Cabinet Cubicle Lighting 0.10 0.10 1.00 1.00 0.85 0.10 0.06 Assumed Value
10 RMU Space Heater 0.20 0.20 1.00 1.00 0.85 0.20 0.12 Assumed Value
11 24 Volts DC UPS Space Heater 0.30 0.30 1.00 1.00 0.85 0.30 0.19 Assumed Value
12 110 Volts DC UPS Space Heater 0.30 0.30 1.00 1.00 0.85 0.30 0.19 Assumed Value