242 - EEE 3205 - Lecture#8 - GrayScale
242 - EEE 3205 - Lecture#8 - GrayScale
Summer 2024
United International University
Components of a Power
System
A power system consists of different components. Some common components are:
• Generator
• Transformer
• Motor etc.
12-07-2024
Equivalent Circuit of a
Generator
• The equivalent circuit for a synchronous generator is represented by that shown in fig. below.
Xs
Ia
+
+ +
Xar - +
Xl - +
Ra -
Ef Vt
-
-
Ra is usually so much smaller than XS that its omission is not of great consequence.
+ +
Xg -
+
Xm - +
Eg Vt Em
- -
Generator Motor
12-07-2024
0.6 Ω
25 MVA 25 MVA 25 MVA
If we want to make three phase transformer out of the three single phase transformer we can
make, wye-wye, wye-delta, delta-wye or delta-delta.
If the transformer supplies a three phase load made out of the three resistors, they can be
connected either in wye or delta.
Let us examine three combinations.
0.6 Ω
0.6 Ω
66 kV 6.6kV
38.1 kV 3.81 kV 0.6 Ω
◇ Three single phase transformer each rated 25 MVA, 38.1/3.81 kV are used.
◇ If we make Y-Y connection, total rating is 75 MVA, 66/6.6 kV [as √3 x 38.1 kV = 66kV]
◇ Per phase load resistance referred to primary, R=0.6 x (38.1/3.81)2 =60 Ω.
◇ In stead of phase voltage if line voltages are considered, the result would be same. R=0.6 x
(66/6.6)2 =60 Ω.
12-07-2024
66 kV
38.1 kV 0.6 Ω
3.81 kV
0.6 Ω
0.6 Ω
66 kV 3.81 kV
38.1 kV 2.2 kV 0.6 Ω
Exercise #2
◇ Three single phase transformers, each rated at 25 MVA, 38.1/3.81 kV are connected Y-∆ as
shown in the previous slide with the balanced load of three 0.6Ω Y-connected resistors.
Choose a base of 75 MVA, 66 kV for the high tension side of the transformer and specify the
base for the low-tension side. Then determine the load resistance referred to the high tension
side and the per-unit value of this resistance on the chosen base.
Solution
◇ The 3-phase rating of the transformer is 75 MVA,66 kV/3.81 kV.
◇ Base impedance on the low tension side = (3.81)2/75=0.1935 Ω.
◇ So, PU impedance on the low tension side, RL=0.6/0.1935=3.1 per-unit
◇ Base impedance on the high tension side is 662/75=58.1 Ω
◇ RL, impedance referred to primary (see the previous slide) = 180 Ω.
◇ Hence on the high tension side, RL=180/58.1=3.1 per-unit
Exercise #1
A ∆-connected resistive load of 8000 kW is connected to the low-tension, ∆-connected side of a Y-∆
transformer rated 10,000 kVA, 138/13.8 kV. Find the load resistance in ohms in phase as measured
from line to neutral on the high tension side of the transformer.
Resistance of the load
(in equivalent Y)
=kVph2x 1000/kW ph
=7.972x1000/(8000/3)=23.8 ohms
138 kV 13.8 kV 8000
kW
Resistance referred from high
tension side=23.8 x
10000 kVA
(79.7/7.97)2=2380 ohms.
OR,
23.8 x (138/13.8)2
138 kV 7.97 13.8 kV =2380 ohms.
79.7
kV kV
12-07-2024
Exercise #2
A three phase transformer is rated 400 MVA, 220Y/22∆ kV. The reactance of the transformer measured
from the low tension side is 0.121 Ω. Determine the per unit reactance of the transformer (on its own
base) and the value to be used to represent this transformer to a system whose base on high tension
side of the transformer is 100 MVA, 230 kV.
Solution: On its own base:
Base kV at the LT side =22 kV and Base MVA=400 MVA.
Hence Base Impedance = kV2/MVA=222/400=1.21 Ω.
Hence per unit impedance = actual/base = 0.121/1.21 = 0.1 pu.
PU value is independent of the sides of the transformer. Hence it is also pu value in the HT side.
On the system base: New Base kV = 230 kV , New Base MVA=100 MVA.
Exercise#3
◇ For the network below, following data are given:
◇ Generator – 30 MVA, 13.8 kV, X”=15%
◇ Motor 1 – 20 MVA, 12.5 kV, X” = 20%
◇ Motor 2 – 10 MVA, 12.5 kV, X”=20%
◇ Transformer 1 & 2 – 35 MVA, 13.2 kV /115 kV Y, X=10%,
◇ Line – X=80 ohms,
◇ Draw the single line diagram for the network showing all reactance values in PU,
assume the ratings of the generator as the base for the generator circuit.
12-07-2024