Analog & Digital Control Basics
Analog & Digital Control Basics
To-days high capacity capital intensive single engineers and technicians to interact well with
stream plants rely heavily on Automatic each other, troubleshoot and solves problems
controls for safe and economical operation. intelligently. This article attempts to explain the
Clear understanding of control concepts will concepts in simple easy to understand
help operation, maintenance, and process language
.
Introduction: Often we hear the words ‘Analog’
and ‘Digital Control’. Today’s microprocessor
based control systems use a combination of the
two to achieve best results. Still let us study and
understand each of them individually.
FT
Steam Steam Flow
Feedforward Ratio Signal
PT SPC FFC RR
SP
SP
OFT OV
Boiler
V
AFC
Fuel Oil
CV
AFT
Air
Control Fig-3
More on Controllers: The controller C (fig-1) Derivative or differential setting of a
accepts PV signal from the transducer at its input controller changes the speed of travel of final
section or often called ports. Its comparison control element in relation to the speed of offset
element compares the PV and SP and generates occurence. Table-1 below summarizes the
an error signal. The processor inside the 3-modes of control.
controller develops an output signal; processing
to develop the output signal may include PID Hand-Auto Station of Controllers: The
(proportional/ integral/derivative) and other controller output passes to the final control
control strategies to suit the nature and response element FCE via a Hand-Auto Station HAS (fig-1)
of the process for changes in feeds e.g. slow that may be built in as a part of the controller or
process variable changes require slow response may exist as a separate module. Usually HAS
from the controller and vice versa. has a knob with a dial marked ‘Hand’ at one end
and ‘Auto’ at the other end. Positioning the knob
Few Words on PID Control: The alphabet P in Auto position sets the controller in Auto mode
denotes proportional, I Integral or reset and D and Hand position in Hand or Manual mode. The
derivative or rate action of a controller. controller output reaches FCE in case the HAS is
Proportional action of the controller changes the in Auto mode. In case HAS is in Hand Mode, the
output in direct proportion to the difference station blocks the controller output and sends an
between PV and SP known as deviation or offset. operator generated output to FCE. The PV signal
still reaches the controller as before for the
Table-1 Summary of Control Modes operator to read. But as long as the HAS in Hand
Mode changes in PV does not change FCE
CM-Control Mode, Proportional. I-Integral, position until an operator interferes.
D-Derivative
CM Applications Analog Actuators: FCE need actuators to
actuate it e.g. a control valve needs a diaphragm
Where sustained deviations are
P or piston actuator to position the plug along its
acceptable
travel to allow required quantity to flow. Many
Where deviations are unacceptable, and types actuators e.g. piston, diaphragm, hydraulic
process response is moderate to fast. cylinder, pneumatic cylinder, electric motor
I
Most process controls come under this solenoid coils etc. are available to actuate FCE
category. like valves, dampers, motors, fluid couplings,
magnetic couplings, or other similar devices to
As above, but the process response to
make the needed changes in the process. As the
change in manipulated variable is too low
name implies these actuators work using analog
D e.g. a slab reheating furnace of a steel
signals from controllers or HAS.
mill. Hence, not common in process
controls.
Open Loop Controller: the two broad divisions
of Analog Control Loops are ‘open’ and ‘closed’
Proportional Band PB is the magnitude of travel loop control. Open loop controllers do not monitor
per 100% deviation e.g. if a valve travels by 1% the PV continuously till it reaches the set point.
of its full travel for 100% deviation PB is 100 and For example a bread toaster does not monitor the
if travel is 100% for 1% deviation PB is 1. The crispness of the toast to switch off the toaster. It
reciprocal of PB is called ‘gain’. Deeper study of just switches it off at a fixed temp. Crispness of
control technology tells us that sustained offset one type of bread may be OK at a setting but not
will prevail in case of load changes in the case of another type denser and moister at the same
controllers with P-mode only. Let us accept it setting. Open loop control is used for very simple
without going into the complex details. plant applications only.
Integral or Reset action repeats the
action of P-mode till the offset vanishes or till the Closed Loop Controller CLC: CLC the most
valve travels to the end position known as widely used controller in process plants comes in
controller saturation. Since Integral action two models viz. “On-Off” and “Modulating or
repeats the action of PB with respect to time, its Continuous Control.
unit is Repeats / Minute R. Inverse of R is known
as Integral Action i.e. the time taken in minutes to ON-OFF Control Loops: the FCE of an ON-OFF
repeat the action of P mode. . Control Loop assumes two positions only e.g. a
valve is fully closed or fully open. On-Off control (steam flow) that could affect the controlled
is acceptable for processes where the capacity of variable (Steam Pressure).
the system or process is lot larger compared to
the energy in flow, as in the case of window air Control Configurations: Three common control
conditioner. At lower than set temp the configurations viz. Ratio Control, Cascade
thermostat breaks contacts and stops the Control and Split Range Control meet most
compressor that causes the cooling. At higher process control application needs.
than set room temp it makes and starts the
compressor to cool the room. Providing a Dead Ratio Control: Ratio Control enables accurate
Band in the thermostat setting e.g. to make at flow rate of one product in proportion to that of
temp above 240C and break below 190C prevents another e.g. combustion air flow to a furnace in
too frequent switching on and off the air proportion to fuel oil flow for complete
conditioner and its motor burnouts. ON-OFF combustion to save on fuel and to avoid too
control though meets the simple needs like air much excess air to avoid wastefully loosing heat
conditioning is inadequate for most process in chimney effluent, another fuel saving measure.
controls as the energy inputs are much large In fig-3, output of Fuel Oil Flow Transmitter OFT
compared to capacity. So controllers capable of is the set point for the ratio setter RS. Operator
Precise Continuous Regulation are must for most sets the ratio of fuel oil flow to combustion air
process controls, for safety, efficiency, man flow in RS. RS generates an output signal
power reduction and product quality assurance. according to the ratio set. RS output is the set
point for the air flow controller. Air flow controller
Feedback: Most process controllers are of the adjusts the damper till the air flow is at the
continuous or modulating type as in fig-3. chosen ratio to the fuel flow. The fuel flow rate is
Suppose the tank level (fig-2) falls below set called the Master or Primary Variable and the Air
point due to increased drawl at the tank outlet. Flow rate the Slave or Secondary Variable. Fig-3
Level Sensor LE reads the new value; Level shows the ratio control between fuel oil and air.
Transmitter LT sends the new value to the level Similar ratio controller exists for controlling the
controller LC; LC outputs a signal to the level ratio between gas flow and combustion air flow
control valve to open valve LV at the inlet pipe to for it. Fig-3 omits it to avoid clutter.
increase the water flow so as to bring the level
back to the SP. Travel of LV stops as soon as Cascade Control: In Cascade Control the output
level reaches SP. LC continuously receives level of one controller is the set point of the second
signal for precise control. This is a simple controller. In the example of the boiler of fig-3 the
example of analog continuous regulation. Tank output of steam pressure controller SPC is the
level signal is known as the feedback signal to set point for the fuel flow controller FFC. In case
the control loop. Thanks to feedback the of a rise in steam pressure its output drops i.e.
controller holds the level precisely at set point reduces fuel flow set point and reduces fuel flow.
with no operator intervention. Any variations of fuel flow due to reasons
like another boiler cutting in, or increased filter
Feedforward: In spite of feedback minor fouling etc. reduces fuel oil flow to the boiler and
deviations from set point may exist for some time in turn steam pressure. In the absence of
due to reaction time of the process. Let us cascade control and SPC directly manipulating
consider steam pressure control from a boiler fuel flow it can act only after steam pressure has
(fig-3). In case of a sudden trip of a large turbine really dropped i.e. after some time lag. The
consuming large quantities of steam the header steam pressure would be lower than set point
pressure would rise rapidly and a simple during this period. In the cascade control
pressure controller SPC would bring back the arrangement shown FFC maintains constant fuel
pressure to normal value by reducing the firing flow and thus does not allow the steam pressure
after severe cycling and considerable time lag as to vary on account of problems in fuel circuit.
it can act only after pressure change. By However any steam pressure variation on
feeding the signal of steam flow also to SPC as in account of increased or decreased steam drawl
fig-3 it responds as soon as steam flow changes from the boiler is controlled by SPC using steam
occur instead of waiting for its effect viz. pressure flow signal as feed forward as explained before.
change. This is known as feedforward. So feed
forward is the signal of the process variable
Inputs
Logic Control Loops: The controller element in
Inputs Output
1 Output 1 a logic loop operates in a similar manner as an