nr: _______________________ AREP Hybrid and Solar PV Test Report This Test Report nr: _____________________
User / Owners Contact Details Client's Name and Surname Contact Number:
E-mail address
Physical address
Suburb Province
Accreditation number
Accreditation number
Type of Installation
SSEG Installation - Hybrid /Grid Tied Inverter used in Grid tied configuration without Storage Other
Complete Section 1, 3, 4 and 5 Complete Sections as required and highlight those sections on Page 3
This document can only be issued at a site where there is an existing and valid Certificate of Compliance covering the Main electrical reticulation
For installations with more components please copy or duplicate the required sections
19 Busbar in between inverter and batteries Yes N/A (Where N/A has been selected, please skip the rest of this section)
21 Protection - Busbar to Inverter DC Circuit breaker DC Fuse Fuse or Circuit breaker Size Amps and kA
Fuse Protection
22 Isolation - Busbar to Inverter DC Circuit breaker DC Fuse Fuse or Circuit breaker Size Amps and kA
(Fuse may not be used as an isolation device) - Should be Double Pole Fuse or Circuit Breaker
42 Section 4a - Combiner / Fuse Boxes Combiner Box Fuse Box Other please specify
43 Short Circuit Protection DC Circuit breaker DC Fuse Fuse or Circuit breaker Size Amps and kA
Either Fuse or Circuit breaker Protection can be used on the positive conductors
44 Reverse Current Protection DC Fuse DC Fuse Size Amps and kA
Only Fuses can be used. Circuit breakers do not protect against reverse current, Fuses will be situated on the negative conductors
45 Isolation DC Disconnect DC Rated Isolator Isolation device Size Amps and kA
(Fuse may not be used as an isolation device) - Double Pole
46 String Conductors are numbered and Labelled Combiner Boxes are Installed at floor level and can be reached without a step ladder
47 Combiner Box is labelled with a "Danger - Live DC Conductors - Solar Power" Sign
48 Section 4b - External MPPT ALL MPPT casings are bonded and continuous to earth Yes
49 (Pos) Short Circuit Protection DC Circuit breaker DC Fuse Fuse or Circuit breaker Size Amps and kA
Either Fuse or Circuit breaker Protection can be used on the positive conductors
50 (Neg) Reverse Current Protection DC Fuse DC Fuse Size Amps and kA
Only Fuses can be used. Circuit breakers do not protect against reverse current, Fuses will be situated on the negative conductors
51 Isolation DC Disconnect DC Rated Isolator Isolation device Size Amps and kA
(Fuse may not be used as an isolation device and cannot be opened under load) - Double Pole
52 String Conductors are numbered and Labelled MPPT's are numbered
53 MPPT's are labelled with a "Danger - Live DC Conductors - Solar Power" Sign
54 Section 5 - General Hybrid Inverter is provided with Earth Spike as per SANS 7.12 N/A
55 Earth Leakage has been fitted after inverter Yes N/A Earth Neutral Bond before RCD
56 DC Surge Protection fitted Type 1 and 2 combined Yes N/A Type 2 Yes Type 3 Yes N/A
57 AC Surge Protection has been fitted Type 1 and 2 combined Yes N/A Type 2 Yes Type 3 Yes N/A
58 Metal Wireways and trunking Bonded and continuous to Consumer Earth Bar Yes N/A
59 Earth Loop impedance test before E/L on DB Powered by Inverter Ω Neutral Loop test at point of control Ω
60 Plug Test has been completed and Earth Leakage Units are fully operational Yes N/A